Mokon Oac-30 Outdoor Central Chiller Owner's Manual

OAC-30 Outdoor Central Chiller

Product Information:

Mokon Outdoor Central Chiller systems are designed for exterior
installation, allowing for valuable indoor equipment space to be
freed up. These central chiller systems are factory tested and
wired, arriving on site in complete working order. They are
constructed with easy lifting provisions for quick and trouble-free
installation and are designed for safe and easy service.

The chiller systems are available in air-cooled and water-cooled
models, with a range of capacities from 30 to 120 tons. The
air-cooled models include OAC-30, OAC-40, OAC-50, OAC-60, OAC-80,
OAC-100, and OAC-120. The water-cooled models include OWC-30,
OWC-40, OWC-50, OWC-60, OWC-80, OWC-100, and OWC-120.

The chiller systems come with various pump options to meet
process conditions or specific performance needs. The pump options
include different horsepower (Hp) ratings and flow rates (GPM) with
corresponding pressure ratings (PSI). The connection types vary
between FNPT (Female National Pipe Thread) and flange
connections.

The approximate dimensions of the chiller systems range from 143
x 54 x 80 inches to 205 x 54 x 80 inches, depending on the model
and tank size (in gallons).

The chiller systems feature an advanced programmable
microprocessor-based controller designed specifically for chiller
applications. The controller provides lead lag functionality to
extend compressor life, capacity control staging, built-in delay,
safety functions, and more. The controllers are compact yet
accurate and powerful.

Standard features of the chiller systems include energy
reduction capabilities and a remote control panel. Common options
and accessories are available to enhance the functionality of the
chiller systems.

All Mokon outdoor central chillers undergo rigorous simulated
field tests and are 100% factory calibrated and run tested. Mokon
offers a 1-year warranty on the chiller systems.

Technical data is subject to change without notice, and Mokon
reserves the right to make dimensional and design changes as
required.

Product Usage Instructions:

  1. Select the appropriate model of the Outdoor Central Chiller
    system based on your cooling requirements and available space.
  2. If you require a water-cooled model, choose the desired process
    pump with the suitable horsepower (Hp) rating, flow rate (GPM), and
    pressure rating (PSI).
  3. If you require an air-cooled model, no additional pump
    selection is necessary.
  4. Ensure that the pump connections match your existing plumbing
    system, choosing between FNPT and flange connections.
  5. Determine the tank size (in gallons) based on your application
    needs.
  6. Consider the dimensions of the chiller system to ensure proper
    installation space.
  7. Connect the chiller system to the power supply and follow the
    installation instructions provided in the user manual.
  8. Use the advanced programmable microprocessor-based controller
    to set up and control the chiller system. Refer to the user manual
    for detailed instructions on programming and utilizing the
    controller’s features.
  9. Monitor the chiller system during operation, ensuring it
    maintains the desired cooling performance. Adjust settings as
    necessary using the controller.
  10. For any issues or concerns, refer to the troubleshooting
    section of the user manual or contact Mokon customer support for
    assistance.

Please note that the information provided is a general guide.
Always refer to the specific user manual and follow the
manufacturer’s instructions for your particular model of the Mokon
Outdoor Central Chiller system.

OUTDOOR CENTRAL CHILLERS
30 to 120 Tons

Mokon’s Outdoor Central Chiller systems are designed for exterior installation, freeing up valuable indoor equipment space. The central chiller systems are factory tested and wired and arrive on site in complete working order. Mokon outdoor central chiller systems are constructed with easy lifting provisions for quick and trouble-free installation and are designed for safe and easy service.

Air-Cooled1

Model

Cooling5 Capacity (BTU/Hr) @ 50°F (10°C)

Water-Cooled2

Process Pump

Connections

Model

Cooling5 Capacity (BTU/Hr) @ 50°F (10°C)

Pump

Min/Max Flow Rate

Nominal Pressure

Condenser Process Water-
Cooled

Tank Size (Gallons)

Approximate Dimensions4 (L x W x H)

OAC-30 356,000 OWC-30 366,000 OAC-40 447,000 OWC-40 460,000 OAC-50 554,000 OWC-50 570,000 OAC-603 724,000 OWC-60 745,000 OAC-803 890,000 OWC-80 916,000 OAC-1003 1,114,000 OWC-100 1,147,000 OAC-1203 1,448,000 OWC-120 1,491,000

Select a standard pump to meet Process conditions or specify performance needs.

Hp

GPM (up to)

PSI

3

60

34

5

80

38

7.5

100

40

7.5

120

35

2″ FNPT
2″ FNPT
3″ FNPT
3″ FNPT
3″ Flange
4″ Flange
4″ Flange

1-1/2″ FNPT
1-1/2″ FNPT
3″ FNPT
3″ FNPT
3″ Flange
4″ Flange
4″ Flange

100 143″x 54″ x 80″ 100 205″ x 54″ x 80″ 150 205″ x 54″ x 80″ 150 205″ x 54″ x 80″ 500 205″ x 54″ x 80″ 500 205″ x 54″ x 80″ 750 205″ x 54″ x 80″

1. Air-Cooled based on 50°F chilled water at 2.4 GPM/Ton and 90°F ambient air 2. Water-Cooled based on 50°F chilled water at 3 GPM/Ton and 85°F condensing water. 3. Provided with remote air-cooled condenser. 4. Water-Cooled chiller dimensions are the same or smaller than Air-Cooled models. 5. Derate chilling capacity based on pump Hp selected.
Energy Reduction
Advanced programmable microprocessor-based controller designed specifically for chiller applications. The controller provides lead lag (controls run time to extend compressor life), staging for capacity control, built-in delay, safety functions, and much more. The controllers are compact yet extremely accurate and powerful.

(Remote control panel shown)

Standard Features
· Air-cooled with low ambient kit or water-cooled condensing · Designed for outdoor ambient temperature of -20°F
to 95°F (-29°C to 35°C) · Fluid temperature 20°F to 65°F (-7°C to 18°C) · Hermetically sealed scroll compressors · Green friendly refrigerant · Highly efficient brazed plate evaporator · Microprocessor-based controller in easily
accessible panel · Smart lead/lag operation · Highly accurate hot gas bypass circuit · Filter dryer · Chiller & process pump pressure gauges · TEFC pump motor · UV protected Armaflex insulation of tank and evaporator · NEMA/Type 4 Outdoor (local) enclosure with main power
door disconnect and E-stop · NEMA/Type 12 Indoor (remote) enclosure including
microprocessor-based controller with safety indication and start/stop switch · Flow switch factory installed · Powder coated cabinet with mounting feet · cULus 508A labeled electrical panel

Common Options and Accessories
· Alarms ­ audible and visual · Automatic fill · Blown fuse indication · Control options and communication ports · Flow meters · Low water level indication · NEMA/Type 4X · Other voltages, phases, frequencies · Overhead piping kit · Phase indicator · Process fluid purge (manual and automatic) · Pump modifications to increase flow capacity
or elimination of supply pump · Large-pump Tank · Special paint and stainless steel cabinetry · Supply and return thermometers · Tank upgrades and modifications · Timers · UL, CSA, CE and EAC certifications · Valved process bypass · Water filters/strainers

Product Testing and Warranty
All Mokon outdoor central chillers are qualified for service by rigid, simulated field tests and are 100% factory calibrated and run tested. Mokon offers a 1 year warranty on system.
Technical data shown is subject to change without notice. The company will endeavor to supply the equipment as illustrated but reserves the right to make dimensional and other design changes as required.

2150 Elmwood Avenue Buffalo, New York 14207
P (716) 876-9951 F (716) 874-8048 E [email protected]
mokon.com

9001/14001:2015 OCC 7/22 MOK8293