Enduro 1-3kva Pure Sinewave On-line Ups User Manual

Enduro 1-3kva Pure Sinewave On-line Ups User Manual

ENDURO logo1-3kVA Pure Sinewave On-Line UPS
User ManualENDURO 1-3kVA Pure Sinewave On-Line UPS1-3KVA, 1:1 Phase
Pure Sinewave On-Line UPS
USER MANUAL

1-3kVA Pure Sinewave On-Line UPS

All rights reserved. The information in this document is subject to change without notice.
Publish statement
Thank you for purchasing the Enduro UPS series. This series UPS is an intelligent, single phase in single phase out, high frequency online UPS designed by our R&D team who is with years of designing experienceson UPS. With excellent electrical performance, perfect intelligent monitoring and network functions, smart appearance, complying with EMC and safety standards, The UPS meets the world’s advanced level.
Read this manual carefully before installation
This manual provides technical support to the operator of the equipment. The ENDURO range of UPS systems are intended for installation in a contaminant free environment with a temperature range between 0°C and 40°C.

Important Safety Warning

SAVE THESE INSTRUCTIONS. This manual contains important instruction that should be followed during installation and operation of the UPS and batteries.
Do not operate this unit before reading through all safety information and operating instructions carefully
The UPS contains its own power source (the battery). The power outlets may be energized even if the system is disconnected from the AC power source.
Dangerous voltage levels and high temperature components are present within the system. The UPS and its External Battery Modules should be opened exclusively by suitably trained and qualified personnel.
The batteries supplied within the system are valve regulated lead acid (VRLA) and contains small amounts of toxic materials. The batteries are certified as complying with UN2800 Special Provision A67 of the International Air Transport Association (IATA) Dangerous Goods Regulations.
Safety instructions in this manual act as a supplementary for the local safety instructions. PSS Distributors will not assume the liability that caused by disobeying safety instructions.
1-1 Transportation
Please transport the UPS system only in the original package to protect against shock and impact.
1-2 Preparation
Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environment. Do not install the UPS system near water or in moist environments. Do not install the UPS system where it would be exposed to direct sunlight or other heat sources. Do not block ventilation holes in the UPS housing.
1-3 Installation

  • Do not connect appliances or devices with high inrush currents to the UPS system (e.g. laser printers, compressors, fridges and motors).
  • Place cables in such a way that no one can step on or trip over them.
  • Do not connect domestic appliances such as hair dryers to UPS output sockets.
  • The UPS can be operated by any individuals with no previous experience.
  • Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system.
  • Use only Australian approved AC cables to connect the UPS system to the building supply and to connect the loads to the UPS system.
  • When installing the equipment, it should ensure that the sum of the leakage current of the UPS and the connected devices does not exceed 3.5mA.

1-4 Operation
Do not disconnect the mains cable on the UPS system or the building wiring outlet (shockproof socket outlet) during operations since this would remove the protective earthing of the UPS system and of all connected loads. The UPS system features its own, internal current source (batteries). The UPS output sockets may be energized even if the UPS system is not connected to the building wiring outlet. To fully disconnect the UPS system, first press the OFF/Enter button to disconnect the mains. Isolate the UPS and check for hazardous voltage upstream and downstream during lockout-tagout operation. Prevent fluids or other foreign objects from entering the UPS system.
1-5 Maintenance

  • The UPS system operates with hazardous voltages. Repairs and maintenance must be carried out by qualified UPS maintenance personnel.
  • Caution – risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.
  • Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present, and no hazardous voltage exists at within the system.
  • Caution – risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present!
  • Batteries
    • Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
    • The battery supplied with the system contains small amounts of toxic materials.
    • Use appropriate PPE when handling the batteries.
    • If a battery case is damaged there is potential exposure to sulfuric acid and lead.
    • When replacing batteries, replace with the same type, capacity and number of batteries or battery packs.
    • Do not mix old and new batteries and ensure that the batteries have the same state of charge and internal resistance.
    • Read the battery manufacturer’s Safety Data Sheet prior to replacement.
    • Dispose in accordance with federal, state, or local regulations.
    • Recycle wherever possible
  • Maintenance
    • The UPS should be regularly maintained (12 Months, 6 Months etc)
    • Maintenance intervals are dependent on the operating environment and the application.
    • PSS offers a wide range of cost-effective preventative maintenance solutions.
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 1
Non Contract – ONE-OFF ServiceDOMETIC CDF18 Compressor Cooler - IconXXXX
BASIC CONTRACTDOMETIC CDF18 Compressor Cooler - IconXXX
COMPREHENSIVE CONTRACTDOMETIC CDF18 Compressor Cooler - IconDOMETIC CDF18 Compressor Cooler - IconDOMETIC CDF18 Compressor Cooler - IconDOMETIC CDF18 Compressor Cooler - IconX
COMPREHENSIVE PLUSDOMETIC CDF18 Compressor Cooler - IconDOMETIC CDF18 Compressor Cooler - IconDOMETIC CDF18 Compressor Cooler - IconDOMETIC CDF18 Compressor Cooler - IconDOMETIC CDF18 Compressor Cooler - Icon

Installation and setup

NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package has been damaged. Please keep the shipping cartons and packing materials in a safe place for future use.
2-1 Unpack checking

  • When removing the UPS or EBM from the packaging:
    • Do not lift the UPS from the front panel.
    • Do not lean the UPS when moving it out from the packaging.
    • The UPS is heavy. Removing it from the carton requires a minimum of two people.
  • Check to see if the UPS is visibly damaged during the transportation, do not switch on the UPS if any damage found. Please contact the supplier right away.
  • Verify that the following additional items are included with the UPS:
    • User manual
    • Software Suite CD
    • USB cable
    • Input AC Power cord
    • base brackets kit (tower installation)
    • Rack brackets (rack installation)

2-2 Real panel view
EN1000 – 1KVAENDURO 1-3kVA Pure Sinewave On-Line UPS fig 2
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 3

  1. Output receptacles (10A)
  2. External Battery Connector
  3. SNMP intelligent slot (optional SW006 SNMP card)
  4. Network /Fax/Modem Surge Protection
  5. RS-232 communication port
  6. AC input receptacle
  7. Input resettable fuse
  8. Connector for EPO (Emergency Power Off)
  9. USB communication port
  10. Output receptacle (16A)

2-3 Installing the UPS
Rackmount installation
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 4If installing optional external battery module(s) EBM(S), make sure to install the EBM(S) directly below the UPS module and the connector(s) are securely plugged in as detailed below.
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 5FRONT VIEW Optional adjustable rack mounting kits, part number RK1000 are available from your Enduro supplier. ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 6Tower InstallationENDURO 1-3kVA Pure Sinewave On-Line UPS fig 7Connect the base brackets together for a single unit installation. Utilize the 1U base extender(s) to add
2-4 UPS startup and turn off
Startup operation

  1. Turn on the UPS ONLINE mode
    NOTE Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm.
    a) Once mains power is plugged in, the UPS will startup in bypass mode (Bypass LED lit)
    b) Press and hold the ON key for more than half a second to start the UPS.
    c) The inverter will start, and the UPS will perform a self-test.
    d) On completion of the self-test, the green LED will be lit, indicating the UPS is working ONLINE mode.
  2. Turn on the UPS by DC without mains power
    a) Ensure that the earth is connected via the AC supply cord.
    b) Press and hold the ON key for more than half a second to start the UPS.
    c) The inverter will start, and the UPS will perform a self-test.
    d) On completion of the self-test, the amber battery LED will be lit, indicating the UPS is working ONLINE mode but drawing power from the batteries. An audible alarm will be heard. the self-test, the corresponding LED lights andthe UPS is working in battery mode.

Turn off operation

  1. Bypass the UPS
    a) Press and hold the OFF key for more than half a second to turn off the inverter.
    b) The Green ONLINE LED will extinguish, and the Bypass LED will be lit.
  2. Turning off the UPS
    c) Switch off the AC power supplying the UPS.
    d) The UPS will shut down.

2-5 Configuring Battery Settings

  • Set the UPS for the number of EBMs installed.
  • To ensure maximum battery runtime, configure the UPS for the correct number of EBMs, refer to the table below for the appropriate setting.
  • Refer to UPS Settings, section 3.3 screen number 4.
All UPS and EBM CabinetsBattery Capacity
UPS only (internal batteries)9Ah(default)
UPS+1EBM27Ah
UPS+2EBMs45Ah
UPS+3EBMs63Ah
UPS+4EBMs81Ah

NOTE The UPS contains 1 battery string; each EBM contains 2 battery strings.
2-6 LCD control panel
2-7 Setup the UPS

Step 1: UPS input connection

  • Using the AC power cord supplied, plug the UPS into the AC supply socket.
  • Avoid the use of multiplugs and extension leads.

Step 2: UPS output connection

  • Plug the load devices into the UPS.

Step 3: Communication connection
To allow for unattended UPS shutdown/start-up and status monitoring, connect the communication cable one end to the USB port and the other to the communication port of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or Relay card. When installing either SNMP (part number SW006) or Relay card (part number SW011), it will provide advanced communication and monitoring options.
Communication ports:
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 9Step 4: Turn on the UPS

Refer to section 2.4 Note: The battery charges fully during the first five hours of normal operation.
Step 5: Install software
For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown. You may insert provided CD into CD-ROM to install the monitoring software. The software can be download at http://www.megatec.com.tw/Download.htm

Operations

3-1 Button Operation

Button Function 
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 10Turn on the UPS: Press and hold ON button for at least 2  seconds to turn on the UPS.
Switch the UPS from bypass mode to ONLINE mode.
UPS Setting Mode
Choosing different value: When the UPS enters the setting mode, press this button to select the required value.
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 11Turn off the UPS: Press and hold button at least 2 seconds to turn off the UPS in battery mode.
Switch the UPS from ONLINE mode to bypass mode.
UPS Setting Mode
Down key: Press button to display the next selection.
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 12Switch LCD message: Press button to change the LCD message for input voltage, input frequency, battery  voltage, output voltage and output frequency etc.
Rotate Key: Hold for 10 seconds to rotate the LCD screen.
Mute the mains failure alarm: Hold button for at least 5 seconds  to disable or enable the alarm system.
UPS Setting Mode
Up key: Press button to display previous selection.
Switch to UPS self‐test mode: Press button for 2 seconds.
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 13Access UPS Setting Mode
Press buttons simultaneously for 5 seconds.

3-2 LCD display
Part one: Rack display
There are 8 interfaces available in the LCD display.
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 14ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 15ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 163-3 UPS settings
The UPS should come preset and not require any adjustments. The setting function is controlled by the three buttons as detailed below. To access the setup, press the After the UPS turn ON, press buttonsDown+UP for 5 seconds.

Item Settings Content display 
01MODE 
Press Enter buttonENDURO 1-3kVA Pure Sinewave On-Line UPS icon to change the setting (NOA or ECO or CF).
Press UP button ▲ to select  the previous setting.
Press DOWN ▼ button to select the next setting.
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 17
02OUTPUT VOLTAGE 
Press Enter button to change the setting (200V – 240V).
Press UP button ▲ to select the previous setting.
Press DOWN ▼ button to select the next setting.
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 18
03FREQUENCY
Press Enter button ENDURO 1-3kVA Pure Sinewave On-Line UPS icon to change the setting (50Hz /60Hz).
Press UP button ▲ to select the previous setting.
Press DOWN ▼ button to select the next setting.
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 19
04BATTERY CAPACITY
Press Enter buttonENDURO 1-3kVA Pure Sinewave On-Line UPS icon to  change the setting.
Default is 9Ah refer to section 2.5.
Press UP button ▲ to select the previous setting.
Press DOWN ▼ button to select the next setting.
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 20
05LOW VOLTAGE ALARM 
Press Enter button ENDURO 1-3kVA Pure Sinewave On-Line UPS icon to change the setting.
Default setting: 185V / Cell
Press UP button ▲ to select the previous setting.
Press DOWN ▼ button to select the next setting.
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 20
06EOD
Press Enter buttonENDURO 1-3kVA Pure Sinewave On-Line UPS icon to  change the setting.
Default setting: 185V / Cell
Press UP button ▲ to select the  previous setting.
Press DOWN button ▼ to  select theprevious setting.
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 20
07Bypass Voltage Upper limit
Press Enter buttonENDURO 1-3kVA Pure Sinewave On-Line UPS icon to  change the setting. (230‐264Vac)
Press UP button ▲ to selectthe  previous setting.
Press DOWN button ▼ to select the  previous setting.
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 21
08Bypass Voltage Lower limit
Press Enter button ENDURO 1-3kVA Pure Sinewave On-Line UPS icon to  change the setting. (170‐ 220Vac)
Press UP button▲to select the  previous setting.
Press DOWN button▼to select the  previous setting.
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 22

3-4 Operating Mode Description 

Mode Description Indicator 
Line ModeThe green LED is on.
o Input AC mains is within limits, the UPS will function in ONLINE mode.
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 23
Battery ModeThe battery amber LED is on.
o The alarm  beeps once every 4 seconds.
o Input AC mains is out of limits.
The battery amber LED flashes.
o The battery voltage has reached the limit setin section 3.3 (05)
UPS power off
o The battery voltage has reached the limit set in section 3.3 (06)
UPS will auto‐restart when  the mains recover.
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 24
Bypass ModeThe bypass amber LED is on.
The UPS is in bypass.
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 25
ECO ModeThe bypass amber LED is on.
When ECO enabled and the AC mains is in range, the UPS will work on ECO Mode.
If the AC mains is out of range the UPS will transfer to ONLINE mode.
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 25
Fault ModeThe warning red LED is on and the alarm beeps.The UPS is in fault mode.
• NOTE: please refer to alarm or fault reference code.
ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 26

3-5 Operational Status and Mode(s) 

item Content Displayed 
2Standby Mode
3No Output
4Bypass Mode
5Utility Mode
6Battery Mode
7Battery Self‐diagnostics
8Inverter is starting up
9ECO Mode
10EPO Mode
11Maintenance Bypass Mode
12Fault Mode

3-6 Alarm or Fault reference codes 

Event logUPS Alarm Warning Buzzer LED 
2Inverter fault (Including Inverter bridg is shorted)Beep continuouslyFault LED lit
9Fan faultBeep continuouslyFault LED lit
12Self‐test faultBeep continuouslyFault LED lit
13Battery Charger faultBeep continuouslyFault LED lit
15DC Bus over voltageBeep continuouslyFault LED lit
16DC Bus below voltageBeep continuouslyFault LED lit
17DC bus unbalanceBeep continuouslyFault LED lit
18Soft start failedBeep continuouslyFault LED lit
19UPS Inside Over TemperatureTwice per secondFault LED lit
20Heat sink Over TemperatureTwice per secondFault LED lit
26Battery over voltageOnce per secondFault LED blinking
29Output Short‐circuitOnce per secondFault LED blinking
30Input current limitOnce per secondFault LED blinking
31Bypass over currentOnce per secondBPS LED blinking
32OverloadOnce per secondINV or BPS LED blinking
33No batteryOnce per secondBattery LED blinking
34Battery under voltageOnce per secondBattery LED blinking
35Battery low pre‐warningOnce per secondBattery LED blinking
36Overload time outOnce per 2 secondsFault LED blinking
37DC component over limit.Once per 2 secondsINV LED blinking
39Main’s volt. AbnormalOnce per 2 secondsBattery LED lit
40Mains freq. abnormalOnce per 2 secondsBattery LED lit
41Bypass Not AvailableBPS LED blinking

Troubleshooting

If the UPS system does not operate correctly, please solve the problem by using the table below.

SymptomPossible causeRemedy
No indication and alarm even though the mains is normal.The AC input power isnot connected well.Check if input power cord firmly connected to the mains.
The AC input is connected to the UPS output.Plug AC input power cordto AC input correctly.
Alarm code is shown as”33″and battery led blinking.The external or internal batten/ is
incorrectly connected.
Check if all batteries are connected well.
Alarm code is shown as “26”and battery led blinking.voltage Is too Battery high or the charger is fault.Contact your dealer.
Alarm code is shown as “34”and  battery led blinkingBattery voltage is toolow or the charger is fault.Contact your dealer.
Alarm code is shown as “3 2″and INV or BYPASS led blinking.UPS is overloadRemove excess loads fromUPS output.
Alarm code is shown as ” 29″and FAULT led light.The UPS shut down automatically because short circuit occurs on
the UPS output.
Check output wiring and if connected devices are in short circuit status.
Alarm code is shown as “9”and FAULT led light.Fan fault.Contact your dealer.
Alarm code is shown as 01,02, 15,16,17,18″A UPS internal faulthas occurred.Contact your dealer.
Battery backup time is shorterthan nominal valueBatteries are not fully chargedCharge the batteries for atleast 5 hours and then check capacity. If the problem still persists, consult with your dealer.
Batteries defectContact your dealer to replace the battery.

Storage and Maintenance

Operation 
The UPS system contains no user‐serviceable parts. If the battery service life (3~5 years at 25°C  mbient temperature) has been  exceeded, the batteries must be replaced. In this case, please contact your dealer.
Storage 
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table:

Storage TemperatureRecharge FrequencyCharging Duration
‐25°C ‐ 40°CEvery 3 months1‐2 hours
40°C ‐ 45°CEvery 2 months1‐2  hours

ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 27

  • Loosen the 2 torque screws (on each side of the card).
  • Carefully insert the SNMP / Relay card into the slot and lock the screws

SW006 SNMP 

SW011 Relay Card 

1Common
2UPS ActiveOpen when UPS Active2 & 1 open
3Mains FailOpen when Mains Fails3 & 1 open
4Close when Mains Fails4 & 1 close
5Battery LowOpen when Battery Low7 & 1 open
6Close when Battery Low8 & 1 close
7General AlarmOpen when UPS Alarm7 & 1 open
8Close when UPS Alarm8 & 1 close
9Bypass ActiveOpen when Bypass Active9 & 1 open
10Close when Bypass Active10 & 1 close
11UPS FaultOpen when UPS Fault11 & 1 open
12Close when UPS Fault12 & 1 close

Contacts & Links

7-1 Warranty Registration 
Please register your warranty with the serial number provided on the below link.
http://www.pssdistributors.com.au/ups‐warranty‐registration/ 
7-2 PSS Repair/RMA Form
 https://pssdistributors.com.au/repair‐rma/ 
7-3 Service Enquiries 
Email: [email protected] 
Contact: 1300 882 447

Specification

ModelEN 1000EN 2000EN 3000
Capacity1kVA/900W2kVA/1800W3kVAl2700W
Input
Voltage range230V +/- 20%
Frequency range45Hz – 65Hz
PhaseSingle phase
Power factor.?- 0.98
Breaker6A10A15A
Input socketIEC C14 10AIEC C14 10AIEC C20 16A
Output
Voltage range230VAC+/-2%
Frequency ( battery mode)50Hz +/- 0.1Hz
Power factor0.9
Current crest ratio3:01
THDc3%(linear Load); -05% (non-linear oad)
WaveformPure Sinewave
Output sockets2x AU 3 Pin sockets
( 1 critical I 1 non-critical)
3x AU 3 Pin sockets
( 2 critical / 1 non-critical)
3x AU 3 Pin sockets
( 2 critical! 1 non-critical)
Efficiency?.. 89% normal mode, up to 97% ECO mode
Overload capacity30s at 100-150%: 300ms at >150%
Battery
TypeSeated lead acid, maintenance free
Configuration (standard run)3x 12V / 9Ah6x 12V /9Ah6x 12V / 9Ah
Rated battery voltage36V72V72V
Charge current (Max)12A
Recharge time to 90%5 Hrs
Charge modeIntelligent 3-stage charging
Comma & Management
SoftwareWindows 95198/NT/2000/XPNistaf7, Windows Server 2003/2008
Linux Deblan, Redhat, Fedora, Suss, Ubuntu, Cent0S. Novell. Mac, FreeBSD
PortsUSB and RS-232 standard
OptionalSNMP & relay (trigger voltage free contacts)
LED/LCO displayLoad, battery, input, output, operating
Audible alarmBattery mode, low battery, overload, fault
Protection
Surge protection2200 Joules/ 60,000 Amps
Input protectionCompliance with IEEE 587
Short circuitResettable circuit breaker
EPOShuts down UPS immediately
EMCEN50091-2, C Tick/RCM
NetworkRJ45, fulltime network protection
Characteristics
Temperature0-40  °C
Humidity0 – 95% (non-condensing)
Noise level<50dB at 1m
Dimensions (WxDxH) /weight440x430x86.5 (2RUy15.1kg440x600x86.5mm (2RU)126.3kg440x600x86.5mm (2RU)/26.8kg
Shipping dimensions (WxDxli)/weight560x560x210mm/17.9kg560x730x210mrs129.6kg560x730x210mm129.9kg
EBM dimensions (WxOxH) 1 weight440x430x86.5mm(2RU)120kg440x710x86.5mm(2RU)/33kg440x710x86.5mm(2RU)133kg
EOM shipping dimensions(VhdixH)fweigN560x560x210mm124.1kg560440x210mm./42.6kg560x810x210mm142.6kg

ENDURO logowww.pssdistributors.com.au
Email: [email protected]
Phone: 1300 882 447

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals