Ako D14212 Thermostat Electronic Controller Instruction Manual

Ako D14212 Thermostat Electronic Controller Instruction Manual

LOGO

AKO D14212 Thermostat Electronic Controller Instruction

AKO-D14212-Thermostat-Electronic-Controller-Instruction-PRODACT-IMG

Configurable electronic thermostats with 2 relays and up to 2 probes

The two probe inputs can be interrelated with the two relay outputs for the thermometer, thermostat and the timing functions in cold and heat applications.
CONFIGURATION allows that some parameters are ADJUSTABLE or not by the USER so that he or she has the exclusive information and adjustment that the device’s use requires. The functions of the front part keys as well as the display of temperatures can be modified, while the configuration with a password can be blocked.
Warnings
The use of the unit different to the manufacturer’s instructions voids the safety qualification. To ensure correct operation of the apparatus, only NTC type probes supplied by AKO should be used. Between -40 ºC and +20 ºC, when the probe is extended up to 1.000m with

minimum 0,5mm cable, deviation will be less than 0.25 ºC (probe extension cable ref. AKO-15586)
Versions and references

MODELAKO-14722AKO-14723AKO-15223
FASTENING UNITPanel mountingPanel mountingDIN raíl
POWER SUPPLY 50/60 Hz12 V ~_ ± 20%230 V~ ±10%230 V~ ±10%

Installation

The controller must be installed in a place protected from vibrations, water and corrosive gases, and where the ambient temperature does not surpass the values specified in the technical data.
In order for the panel mounting units to be suitable having IP65 protection, the gasket should be installed properly between the apparatus and the perimeter of the panel cut-out where it is to be fitted. In order to give a correct reading, the probe has to be installed in a max. place without heat influences other than the temperature that is 18 mm to be measured or controlled.
Fastening units for panel mounting

To fix the unit, place the fasteners 1 over the sliders 2 as shown in the figure. Move the fasteners in the direction of the arrow. By pressing tab 3 the fasteners may be moved in the opposite direction of the arrow.AKO-D14212-Thermostat-Electronic-Controller-Instruction-FIG-1

Fastening units for DIN rail mountingAKO-D14212-Thermostat-Electronic-Controller-Instruction-FIG-2

Connection
See diagram in the unit rating plate. The probe and its lead shoud NEVER be installed in ducting along with power, control or power supply wiring. The power supply circuit should be connected with a minimum 2A, 230V, switch located close to the unit. 2 2 The cables should be of the type H05VV-F 2×0,5mm or H05V-K 1×0,5mm . Section of connecting wires for relays contacts must be between 1mm2 and 2,5mm

Front panel functionsAKO-D14212-Thermostat-Electronic-Controller-Instruction-FIG-3

AKO-D14212-Thermostat-Electronic-Controller-Instruction-FIG-4N UP key: By pressing this key, the temperature in probe 2 is displayed. By pressing it during 5 seconds, the R2 SET POINT is displayed. In programming, it increases the value being displayed. By default, the configuration of this key is factory-set for the preceding actions. However, it can be configured according to the options of parameters 42,

  •  DOWN key: AKO-D14212-Thermostat-Electronic-Controller-Instruction-FIG-5By pressing this key during 5 seconds, the R1 SET POINT is displayed.
  • In programming, it decreases the value being displayed.
  • By default, the configuration of this key is factory-set for the preceding functions. However, it can be configured according to the options of parameters 44, 45.
    UP + DOWN keys (panel mounting) or SET key (DIN rail)
  • Pressing these keys during 10 seconds accesses to the configuration of the controller parameters.
  • Pressing these keys once accesses to the adjustment of the user’s parameters.
  • By default, the configuration of these keys is factory-set for the preceding function, however, they can be configured according to the options of parameter 46.
    LEDs
  • ºC: Permanent: Temperature display in ºC. Flashing, parameters programming phase.
  • ºF: Temperature display in ºF.
  • R1/R2: Relay R1/R2 activated.
    Configuration and adjustment
  • It should only be programmed or modified by personnel who are fully conversant with the operation and possibilities of the equipment.
    Level 1, Parameters
  • Press the CONFIGURE OR ADJUST keys for 10 seconds. The LED “ºC” will be flashing to indicate programming phase and the first parameter “01” will appear on the
  • display. Pressing the AKO-D14212-Thermostat-Electronic-Controller-Instruction-FIG-6 key accesses the next parameter and the Q key will produce a return to the previous one.
  • Pressing DISPLAY VALUE key in the last display EP the controller will return to the current temperature display status and the LED “ºC” will stop flashing.
    Level 2 Values
  • In order to display the current value of any parameter, select the desired parameter and press the DISPLAY VALUE keys. Once it is displayed, it can be modified by
  • pressing the AKO-D14212-Thermostat-Electronic-Controller-Instruction-FIG-4 keys.
  • Pressing the ACCEPT THE NEW keys sets the new value. When this operation is performed, the programming returns to Level 1 (parameters).

AKO-D14212-Thermostat-Electronic-Controller-Instruction-FIG-7

ADJUSTMENT: Pressing once the CONFIGURE OR ADJUST keys accesses the user’s parameters adjustment. The proceeding is the same as for the configuration and access is only possible to the parameters defined as adjustable by the user in the configuration. In order to access the parameters the parameter 39 parameter should be configured. REMARK: If no key is pressed for 25 seconds in any of the previous steps, the controller will automatically return to the current temperature display status without modifying any of the parameters values.
REMARK: When the time parameters are modified, the new values are applied once the current cycle is completed. In order for it to have an immediate effect, switch the controller off and then on again.

Description of parameters and messages

Level 1 
 
 
PARAMETERS
DescriptionValuesMin.Def.Max.
01Temperature display mode:                    0 =Whole in ºC 1 = One decimal in ºC

2 =Whole in ºF 3 = One decimal in ºF

 013
02Probe 1, Enable? (S1) 0=No, 1=Yes 011
03Probe 1 calibration (S1)(ºC / ºF)-20.00.020.0
04Parameter 03 adjustable by the user? 0=No, 1=Yes 001
05Probe 2, Enable? (S2) 0=No, 1=Yes 011
06Probe 2 calibration (S2)(ºC / ºF)-20.00.020.0
07Parameter 06 adjustable by the user? 0=No, 1=Yes 001
08Thermostat relay R1, Enable? 0=No, 1=Yes011
09Thermostat relay R1, Probe selection 0=S1-S2, 1=S1, 2=S2 012
10Thermostat relay R1, Operation type 0=Cold, 1=Heat011
11Thermostat relay R1, Set Point(ºC / ºF)-50.00.099.0
12Parameter 11 adjustable by the user? 0=No, 1=Yes 011
13Thermostat relay R1, Differential (Hysteresis)(ºC / ºF)-90.01.090.0
14Parameter 13 adjustable by the user? 0=No, 1=Yes 011
15Thermostat relay R1, connection delay or protection(min)00120
16Parameter 15 adjustable by the user? 0=No, 1=Yes 011
17Thermostat relay R2, Enable? 0=No, 1=Yes011
18Thermostat relay R2, Probe selection 0=S1-S2, 1=S1, 2=S2 012
19Thermostat relay R2, Operation type 0=Cold, 1=Heat011
20Thermostat relay R2, Set Point(ºC / ºF)-50.00.099.0
21Parameter 20 adjustable by the user? 0=No, 1=Yes 011
22Thermostat relay R1, Differential (Hysteresis)(ºC / ºF)-90.01.090.0
23Parameter 22 adjustable by the user? 0=No, 1=Yes 011
24Thermostat relay R2, connection delay or protection(min.)00120
25Parameter 24 adjustable by the user? 0=No, 1=Yes 011
26Timing relay R1, Enable? 0=No, 1=Yes 001
27Timing relay R1, Elapsed time between starts(h.)00120
28Parameter 27 adjustable by the user? 0=No, 1=Yes 011
29Timing relay R1, Duration(min.)00120
30Parameter 29 adjustable by the user? 0=No, 1=Yes 011
31Timing relay R1, Relay status during P29 0=OFF, 1=ON 001
32Timing relay R2, Enable? 0=No, 1=Yes 001
33Timing relay R2, Elapsed time between starts(h.)00120
34Parameter 33 adjustable by the user? 0=No, 1=Yes 011
35Timing relay R2, Duration(min.)00120
36Parameter 35 adjustable by the user? 0=No, 1=Yes 011
37Timing relay R1, Relay status during P35 0=OFF, 1=ON 001
38Parameters transfer 0=disabled,1=send, 2=receive 002
39Password to modify the configuration 00126
40Program version (information)    
41Display without pressing any key 114
42Function by pressing UP key 027
43Function by pressing UP key during 5” 047
44Function by pressing DOWN key 007
45Function by pressing DOWN key during 5” 037
46Function by pressing UP + DOWN keys in panel mounting models Function by pressing SET key in DIN rail models 077

options for parameters 41 to 46

0Key disabled4R2 Set Point display
1Display Probe 1 of input (S1)5Start R1 timing
2Display Probe 2 of input (S2)6Start R2 timing
3R1 Set Point display7Accessible parameters adjustment
Messages
Probe S1 and Probe S2 disabled
E1Probe S1 damaged (open, crossed circuit, temp. > 110ºC or temp. <-55ºC). Assigned relay OFF.
E2Probe S2 damaged (open, crossed circuit, temp. > 110ºC or temp. <-55ºC). Assigned relay OFF.
E1+E2Flashing: Probes S1+S2 damaged (open, crossed circuit, temp. > 110ºC or temp. <-

55ºC). Relays R1 and R2 OFF.

EEMemory error

Relays R1 and R2 operation and control

Thermostat relay R1 Thermostat relay R2AKO-D14212-Thermostat-Electronic-Controller-Instruction-FIG-8AKO-D14212-Thermostat-Electronic-Controller-Instruction-FIG-9

Parameters transfer

AKO-14916
Tabletop server which is connected by means of the AKO-80018, 230/12V, to the power supply. Permit to transfer parameters previously recorded in one server AKO-14918, to other panel mounting controllers without these having to be powered.AKO-D14212-Thermostat-Electronic-Controller-Instruction-FIG-10

AKO-14918
A portable server without supply to which the parameters programmed in powered AKO controllers can be copied. The parameters may then be transferred from the server to other identical powered units.AKO-D14212-Thermostat-Electronic-Controller-Instruction-FIG-11

Technical data

  • Temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -50 to 99 ºC (-58 to 211 ºF)
  • NTC probe inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AKO-149xx
  • Controller accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 1 ºC
  • Probe tolerance at 25ºC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 0.4 ºC
  • Relay R1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 (4) A*, 250 V, cos j=1, SPST
  • Relay R2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 A*, 250 V, cos j=1, SPDT
  • Maximum input power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 VA
  • Working ambient temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 to 40 ºC
  • Storage ambient temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -30 to 70 ºC
  • Installation category. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . II según norma CEI 664
  • 3 digits and an optional decimal point when programmed . . . . . . . . . . . . . . . . . . . . . . . .
  • Double insulation between the power supply, the secondary circuit and the relay output.
  • * The current specified for each relay is its individual maximum. When more than one relay
  • is connected, the total current cannot surpass 17,5A (EN61010) or 13A (EN60730

AKO ELECTROMECÁNICA , S.A.L. Avda. Roquetes, 30-38 08812 • Sant Pere de Ribes. Barcelona • Spain. www.ako.com

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals