Siemens Rdg160tu Commercial Thermostat Instruction Manual

Siemens Rdg160tu Commercial Thermostat Instruction Manual

SIEMENS RDG160TU Commercial Thermostat Instruction Manual
SIEMENS RDG160TU Commercial Thermostat

Selecting Location

Install the thermostat about 4 feet (120 cm) above the floor on an inside wall. Ensure that there is free airflow around the thermostat. Do not install the thermostat near windows or doors, in direct or radiant heat of sunlight, on unconditioned outside walls or near heating or cooling duct outlets. Not following these prerequisites will adversely affect the thermostat’s sensed temperature and its control performance. See Figure 1
Warnings
Figure 1. Mounting Location.

Installation

Installation Instruction
Step 1. Loosen retaining screws.

Installation Instruction
Step 2. Remove thermostat from back plate, if attached.

Installation Instruction
Step 3. Mount back plate at desired location and terminate wiring connections. See maximum wire size (above).

Installation Instruction
Step 4. Set application DIP switches. See DIP Switch Settings.

Installation Instruction
Step 5. Pivot thermostat onto back plate.

Installation Instruction
Step 6. Snap into place and tighten mounting screws.

Thermostat Termination Reference

Thermostat Termination Reference

NOTE:
24 Vac power to be supplied by Class 2 rated transformer.

  • G Operating voltage, 24 Vac L
  • G0 Operating voltage, 24 Vac N
  • X1 Input 1 signal (Digital In or 3K Ω NTC)
  • X2 Input 2 signal (Digital In or 3K Ω NTC)
  • M Input 1 and 2 Common
  • D1 Digital input signal (example: occupancy)
  • GND Digital input Common
  • Q1~3 Relays outputs for 2-position valve, Speeds 1 to 3 for 3-speed fan
  • Y50 0 to 10V output for ECM Fan
  • Y10 0 to 10V output for H/C valve (2-pipe) or Heating valve (4-pipe) applications
  • Y20 0 to 10V output for Radiator or Electric heat (2-pipe) or Cooling valve (4-pipe) applications
  • C 24 Vac L for relay outputs

Setting Up Applications

Use the DIP switches to set up Basic Applications.
Use the Control Parameter set up on the front panel to set up additional application customization or special set up can be set up. See Parameter Set Up in Service Level.

If no Applications are set up, the front panel displays NO APP.

Diagnostics Mode

In addition to standard Service level control parameter set up, the RDG160TU also has an Expert Level for the advanced user to perform diagnostics and troubleshooting. SeeTable 3.

DIP Switch Settings Overview

DIP Switch Settings icon

Applications are set up with DIP switches 1 through 3.
DIP Switch 4 selects ECM Fan (OFF) or 3-Speed Fan (ON).
DIP Switch 5 (ON) disables time program functions; time is not displayed.

Following is the set up of the most common applications and any supporting parameters to be set using the Service Menu after installation. For other application settings or detailed control functions, see Room Thermostats with LCD for Wall Mounting RDG100, RDG100T, RDG110, RDG140, RDG160, RDG100T/H Basic Documentation (CE1P3181).

HEAT PUMP(Manual changeover only, no reversing valvesupport)Heat OR Cool Compressor (Q1) OnlyHeat OR Cool Compressor (Q1) with2-Position Electric Heat (Q2)Heat (Q1) ANDCool (Q2) Compressors2-Stage Heat OR Cool(Q1, Q2)
ECM Fan (Y50)DIP Switch Settings icon
P46 = 1
DIP Switch Settings icon
P46 = 1
P47 = 1
DIP Switch Settings icon
P46 = 1P47 = 1
DIP Switch Settings icon
2-PIPE FCU2-Position Valve (Q1)Modulating Valve (Y10)2-PIPE FCU with HEAT2-Position Valve (Q1) with ON-OFF Electric Heat (Q2)Modulating Valve (Y10) with Modulating Electric Heat (Q2)Valve (Y10) with Modulating Electric Heat (Q2) Modulating Valve (Y10) with Modulating Electric Heat (Y20)2-PIPE FCU with RADIATOR2-Position Valve (Q1) with 2-Position Radiator (Q2)Modulating Valve (Y10) with 2-Position Radiator (Q2)Modulating Valve (Y10) with Modulating Radiator (Y20)
ECM Fan (Y50DIP Switch Settings icon
P46 = 1
DIP Switch Settings iconECM Fan (Y50)DIP Switch Settings icon
P46 = 1 P47 = 1
DIP Switch Settings icon
P46 = 2 P47 = 1
DIP Switch Settings iconECM Fan (Y50)DIP Switch Settings icon
P46 = 1 P47 = 1
DIP Switch Settings icon
P46 = 2 P47 = 1
DIP Switch Settings icon
3-Speed Fan (Q1-Q3)DIP Switch Settings icon3-Speed Fan (Q1-Q3)DIP Switch Settings icon3-Speed Fan (Q1-Q3)DIP Switch Settings icon
Chilled / Heated Ceiling/ Heated Ceiling 2-Position Valve (Q1)Modulating Valve (Y10)2-Position valve (Q1) with 2- Position Electric Heater (Q2)Modulating Valve (Y10) with 2-Position Electric Heater (Q2)Modulating Valve (Y10) with Modulating Electric Heater (Y20)2-Position Valve (Q1) with 2-Position Radiator Q2)Modulating Valve (Y10) with 2-Position Radiator (Q2)Modulating Valve (Y10) with Modulating Radiator (Y20)
DIP Switch Settings icon
P46 = 1
DIP Switch Settings iconDIP Switch Settings icon
P46 = 1 P47 = 1
DIP Switch Settings icon
P46 = 2 P47 = 1
DIP Switch Settings iconDIP Switch Settings icon
P46 = 1 P47 – 1
DIP Switch Settings icon
P46 = 2 P47 = 1
DIP Switch Settings icon
4-PIPE FCU2-Position Heating (Q1) and Cooling (Q2) ValvesModulating Heating (Y10) and Cooling (Y20) Valves2-STAGE2-Position Heating (Q1) and Cooling (Q2) ValvesModulating Heating (Y10) and Cooling (Y20) Valves
ECM Fan (Y50DIP Switch Settings icon
P46 = 1
P47 = 1
DIP Switch Settings iconECM Fan (Y50)DIP Switch Settings icon
P46 = 1
P47 = 1
DIP Switch Settings icon
3-Speed Fan (Q1-Q3)DIP Switch Settings icon3-Speed Fan (Q1-Q3)DIP Switch Settings icon

Parameter Set Up in Service Level

Parameter Set Up in Service Level

To change control parameters, do the following:

  1. Press the HEAT/COOL and FAN/OK buttons simultaneously for at least 4 seconds.
  2. Release them and, within 2 seconds, press the HEAT/COOL button again until P01 displays.
  3. Select the required parameter by turning the rotary knob.
  4. Press the FAN/OK button . The selected parameter value blinks. Change the value by turning the rotary knob.
  5. Press the FAN/OK button to confirm the change, or the HEAT/COOL button (Esc) to cancel the change.
  6. Repeat Steps 3 through 5 for more parameters or press HEAT/COOL (Esc) to exit.

To return to the factory-default control parameters, do the following:

  1. Change the value of Parameter P71 to ON.
  2. Press the FAN/OK button to confirm the change. When reloading, the screen displays 8888.

When reloading, the screen displays 8888.

NOTES

  • Use Comfort mode for Occupied settings.
  • Use Economy mode for Unoccupied settings.
  • Use Protection mode for Frost Protection.

Table 1. Service Level Parameters.

Parameter  Name  Factory Setting  Range Dependencies
P01Control sequenceWith 2-pipe/2-stage: 1 = cooling only With 4-pipe:4 = H/C0 = Heating only 1 = Cooling only2 = H/C changeover manual3 = H/C changeover automatic 4 = Heating and cooling
P02Operating mode profile (operating mode button)11 = (Auto) – Comfort – Protection 2 = (Auto) – Comfort – Economy –Protection3 = Comfort – Protection4 = Comfort – Economy – ProtectionP01
P03Fan mode selection00 = Auto – Manual 1 = Manual2 = Auto – Manual – Protection3 = Auto – ProtectionP52
P04Selection of °C or °FAlso set during initial set-up0 = Degrees Celsius (°C)1 = Degrees Fahrenheit (°F)
P05Sensor calibration (internally, externally)0°F (0°C)– 6°F to 6°F (-21°C to -14°C)
P06Standard temperature display00 = Room temperature 1 = Setpoint
P08Comfort setpoint70°F (21°C)41°F to 104°F (5°C to 40°C)
P09Minimum setpoint for Comfort mode41°F (5°C)41°F to 104 °F (5°C to 40°C)
P10Maximum setpoint for Comfort mode95°F (35°C)41°F to 104°F (5°C to 40°C)
P11Economy heating setpoint59°F (15°C)OFF, 41°F to 104°F (5°C to 40°C max.)
P12Economy cooling setpoint86°F (30°C)OFF, 41°F to 104°F; 5°C to 40°C (min.)
P13Electric heater in cooling modeONON = Enabled OFF = DisabledApplication
P14Button lock function00 = Unlocked 1 = Auto lock2 = Manual lock
P15Fan stage in deadband (Comfort mode)00 = Disabled1 = Stage 1 (heating and cooling) 2 = Stage 1 (cooling only)

Diagnostics and Testing using Expert Level

To change control parameters, do the following:

  1. Press the HEAT/COOL and FAN/OK buttons simultaneously for at least 4 seconds.
  2. Release them, and within 2 seconds, press the FAN/OK button again until the temperature does not display.
  3. Turn the rotary knob counterclockwise a minimum 1/2 rotation.
    Pxx displays. Select the required parameter by turning the rotary knob.
  4. Press the FAN/OK button . The current value of the selected parameter blinks and can be changed by turning the rotary knob.
  5. Press the FAN/OK button to confirm the adjusted value or press the HEAT/COOL button (Esc) to cancel the change.
  6. To adjust additional parameters, repeat Steps 3 through 5.
  7. Press the HEAT/COOL button (Esc) to exit the parameter setting mode.

To return to the factory-default control parameters, do the following:

  1. Change the value of Parameter P71 to ON.
  2. Press the FAN/OK button to confirm the change.

When reloading, the screen displays 8888.

NOTES

  • Parameters P46 and P47: Use DIP switches 4 and 5 to set to 2-position or 3 position.
  • Parameter P45 compensates for heat dissipation of the electric heater relay.
  • If no sensors or switches are connected, it is not necessary to disable the inputs (P38, P40 or P42 = no function), the thermostat recognizes if a sensor is connected (but diagnostic displays Err).

Table 2. Expert Level Parameters.

ParameterNameFactory SettRangeDependencies
P30P-band/switching differential in heating mode4°F (-15°C)1°F to 12°F (-17°C to -11°C)
P31P-band/switching differential in cooling mode2°F (-16°C))1°F to 12°F (-17°C to -11°C)
P32P-band/switching differential for radiator4°F (-15°C)1°F to 12°F (-17°C to -11°C)Application
P33Deadband in Comfort mode4°F (-15°C)1°F to 10°F (-17°C to -12°C)Application
P34Setpoint differential (wD)4°F (-15°C)1°F to 10 F (-17°C to -12°C)Application
P35Integral action time45 minutes0 to 120 minutesP46, P47
P36Heating/cooling changeover switching point cooling (X1/X2)61°F (16°C)50°F to 77°F (10°C to 25 C)P38, P40
P37Heating/cooling changeover switching point heating (X1/X2)82°F (27°C)81°F to 104°F (27°C to 40°C)
P38Functionality of X11 = External sensor0 = — (No function)
1 = Room temp ext/ret air temp (AI)
2 = H/C changeover (AI/DI)
3 = Operating mode contact [DI)
4 = Dewpoint sensor (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
9 = Supply air sensor
P39Operating action of X1 if digital inputNONO = Normally open/open
NC = Normally closed/closed
P38
P40Functionality of X22 = H/C changeove0 = — (No function)
1 = Room temp ext/ret air temp (AI)
2 = H/C changeover (AI/DI)
3 = Operating mode contact [DI)
4 = Dewpoint sensor. (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
9 = Supply air sensor
P41Operating action of X2 if digital inputNONO = Normally open/open NC = Normally closed/closedP40
P42Functionality of D13 = Operating mode changeover0 = — (no function)
2 = H/C changeover (DI)
3 = Operating mode contact [DI)
4 = Dewpoint sensor (DI)
5 = Enable electric heater (DI)
P406 = Fault input (DI)
P43Operating action of D1 if digital inputNONO = Normally open/open
NC = Normally closed/closed
P42
P45Power of electric heater on Q2 (for adaptive temperature compensation)0 kW0.0 to 1.2 kW
P46Outputs Y10 (DC) or Q1 (2-pos)DC 0 to 10V (2)1 = On/Off
2 = DC 0 to 10V
Application
P47Outputs Y20 (DC) or Q2 (2.pos)DC 0 to 10V (2)1 = On/Off
2 = DC 0 to 10V
Application
P48Min. output on time 2-position control output1 minute1 to 20 minutesP46
P48Min. output ON time on Q1, Q2 and Q3, Relay function P72, P73, P74 ( =2,3,4,5):1 minute1 to 20 minutesApplication P7x
P49Min. output off time 2-position control output1 minute1 to 20 minutesP47
P49Min. output OFF time on Q1, Q2 and Q3 Relay function P72, P73, P74 ( =2,3,4,5):1 minute1 to 20 minutesApplication P7x
P50Purging function (only when changeover with local sensor is selected)OFFOFF: Not active 1 to 5 min: Active with selected duratio
P51Floor heating limit temperatureOFFOFF, 50°F to 122°F (10°C to 50°C)
P52Fan operation10 = Disabled
1 = Enabled
2 = Heating only 3 = Cooling only
P53Fan speedDC 0 to 10V1 = 1-speed fan 2 = 3-speed fan 3 = DC 0 to 10V (ECM fan)P52 DIP4
P54Fan overrun time (only when electric heater is used)60 seconds0 to 360 secondsP52
P55Switching point fan speed high100%80 to 100%P52
P56Switching point fan speed medium
ECM fan min. output
65%
ECM: 30%
30% to 75%
ECM: 1% to fan max.
P52
P57Switching point fan speed low
ECM: Switching point fan
10%
ECM:10%
1% to 15%
ECM: 1% to 100%
P52
P58Fan start boosterONON: Enabled OFF: DisabledP52
P59Fan min. on time2 minutes1 to .6 minutesP52
P60Fan kick interval in Comfort mode (time until next kick)OFF0 to 89 minutes, OFFP52
P61Fan kick interval in Economy mode (time until next kick)OFF0 to 359 minutes, OFFP52
P62Clean filter reminder running timeOFF (0)OFF, 100 to 9900 hoursP52
P63Minimum supply air temperatureOFF, 32°F to P64 °F (0°C to P64 °C)P38, P40
P64Maximum supply air temperatureOFFOFF, P63 °F to 122°F (P63 °C to 50°C)P38, P40
P65Protection heating setpoint8°COFF, 41°F to 104°F (5°C to 40°C max.)
P66Protection cooling setpointOFFOFF, 41°F to 104°F; 5°C to 40°C (min.)P52, P46, P47
P67Fan start delay0 seconds0 through 360 secondsP02
P68Extension Comfort periodOFF F (0)OFF(0); 15 through 360 minutes
P69Temporary setpoint Comfort mode (see also Comfort setpoint P08)OFFOFF = Disabled ON = Enabled
P70Infrared receiver (Not available)ONOFF = Disabled ON = Enabled
P71Reload factory settingsOFFOFF = Disabled ON = Reload startApplication
P72Output Q1 function00 = No function 1= Switch OFF in Protection
2= Switch ON in H/C demand (2-pipe)
3= Switch ON in H demand (4-pipe)
4= Switch ON in C demand (4-pipe)
5= Status active sequence (H or C)
Application
P73Output Q2 function00 = No function 1= Switch OFF in Protection
2= Switch ON in H/C demand (2-pipe)
3= Switch ON in H demand (4-pipe)
4= Switch ON in C demand (4-pipe) 5= Status active sequence (H or C)
Application
P74Output Q3 function00 = No function 1= Switch OFF in Protection
2= Switch ON in H/C demand (2-pipe)
3= Switch ON in H demand (4-pipe)
4= Switch ON in C demand (4-pipe)
5= Status active sequence (H or C)
Application

Table 3. Diagnostics and Tests.

 Parameter   Name   Factory Setting   Range  Dependencies
d01Application typeDiagnostics0 = (no application) 1 = 2-pipe2 = 2-pipe with electric heater 3 = 2-pipe with radiator4 = 4-pipe5 = 2 stage heating or cooling 6 = 4-pipe with electric heater
d02X1 statusDiagnostics“—” = Function not selected 0 = Not activated (for DI)1 = Activated (DI)32°F to 120°F (0°C to 49°C)= Curr. temp. value (for AI) Err        *)00           = H/C input closed100         = H/C input open
d03X2 statusDiagnostics“—” = Function not selected 0 = Not activated (for DI)1 = Activated (DI)32°F to 120°F (0°C to 49°C)= Curr. temp. value (for AI) Err        *)00           = H/C input closed100         = H/C input open
d04D1 statusDiagnostics“—” = Function not selected 0 = Not activated (for DI)1 = Activated (DI)00           = H/C input closed100         = H/C input open
d07Software versionUx.xx displays
d08Test mode for checking Q1 output“—” = No signal at output Q1OPE = Output Q1 forced opening CLO = Output Q1 forced closingP72,Application
d09Test mode for checking Q2 output“—” = No signal at output Q2OPE = Output Q2 forced opening CLO = Output Q2 forced closingP73,Application
d10Test mode for checking Q3 output“—” = No signal at output Q3OPE = Output Q3 forced opening CLO = Output Q3 forced closingP74,Application

Dimensions

Dimensions
Figure 2. Dimensions in Inches (Millimeters).

Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners. © 2016 Siemens Industry, Inc.

Siemens Industry, Inc.
Building Technologies Division
1000 Deerfield Parkway
Buffalo Grove, IL 60089
USA
Tel. + 1 847-215-1000

Your feedback is important to us. If you have
comments about this document, please send them to
[email protected]

Document No. 129-588
Printed in the USA

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals