Thorn Altis G4 Floodlight Instruction Manual

Thorn Altis G4 Floodlight Instruction Manual

THORN logoALTIS G4 Floodlight
Instruction ManualTHORN ALTIS G4 Floodlight

ALTIS G4 Floodlight

TYPE: ALG4 432L
IP66 / IK08
THORN ALTIS G4 Floodlight - icon 1 =30.9 kg
THORN ALTIS G4 Floodlight - icon 2 The luminaire with clear optic should be positioned so that prolonged staring into the luminaire at a distance <2m is not expected
THORN ALTIS G4 Floodlight - icon 3 Caution, risk of electric shock
Extreme caution: Do not connect any LED CONNECTION wire (high voltage) inside NTC connector !! It could result in a critical failure and damage irreversibly the ALTIS luminaire
The light source contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person.THORN ALTIS G4 Floodlight - icon 4

GEAR BOX : ALG4 GB LE 432L

THORN ALTIS G4 Floodlight - Figure 1THORN ALTIS G4 Floodlight - icon 5TaMIN = -40°C / TaMAX = +50°C
(up to 50°C with driving current derating)
IP66 / IK08
corrosion environment from C1 to C3 according to standard ISO9223
ALG4 GB 432LTHORN ALTIS G4 Floodlight - Figure 2TaMIN = -40°C / TaMAX = +55°C
(up to 55°C with driving current derating)
IP66 / IK08

DIMENSIONS

THORN ALTIS G4 Floodlight - Figure 3

 ScXO° *ScX15′ *ScX45° *SX65′ *ScX90° *
ALG4432L0.140.260.480.550.57

THORN ALTIS G4 Floodlight - Figure 4* These data refer to the worst case at indicated angle
ALG4 GB LE 432LTHORN ALTIS G4 Floodlight - Figure 5THORN ALTIS G4 Floodlight - Figure 6

  1. 1xM20 with extra large washer (not provided)
    or
  2. 2xM20 with extra large washer (not provided)

For installation higher >3m
Secure product with retaining cable attached to the frame (not included in the delivery).
Please refer to local installation norms/regulations.THORN ALTIS G4 Floodlight - Figure 7THORN ALTIS G4 Floodlight - Figure 8THORN ALTIS G4 Floodlight - Figure 9THORN ALTIS G4 Floodlight - Figure 10

CONNECTION BOX

THORN ALTIS G4 Floodlight - Figure 11

ELECTRICAL CONNECTION

THORN ALTIS G4 Floodlight - Figure 12Extreme caution :
Do not connect any LED CONNECTION wire (high voltage) inside NTC connector !! It could result in a critical failure and damage irreversibly the ALTIS luminaire (7*)  Optionnal : NTC connection (thermal monitoring).
Cable 9x cores or above is recommended (ex : H07 RN-F 9G1,5mm²)

PINOUT
NumberLabelDescription
1+1LED1+Connection (TOP Brick
2-1LED1-Connection (TOP Brick
3+3LED3+Connection (BOT Brick
4-3LED3-Connection (BOT Brick
5+2LED2+Connection (MID Brick
6-2LED2-Connection (MID Brick
7NTC optionThermal Measure INPUT
GNDPROTECTIVE EARTH
GNDPROTECTIVE EARTH

THORN ALTIS G4 Floodlight - Figure 13Recommended:
H07 RN-F 9G1,5 mm² with NTC connected or H07 RN-F 7G1,5 mm² if NTC not connected THORN ALTIS G4 Floodlight - Figure 14Recommended:
H07 RN-F 7G1,5 mm² ( Without NTC )

ALG4 GB 432L / ELECTRICAL CONNECTION / DALI

THORN ALTIS G4 Floodlight - Figure 15

Extreme caution: Do not connect any LED CONNECTION wire (high voltage) inside NTC connector !! It could result in a critical failure and damage irreversibly the ALTIS luminaire

PINOUT
NumberLabelDescription
L1AC LINE 1 INPUT
L2AC LINE 2 INPUT
THORN ALTIS G4 Floodlight - icon 8PROTECTIVE EARTH
DA+DALI INPUT
DA+DALI RE-LAUNCH
DA-DALI INPUT
DA-DALI RE-LAUNCH
THORN ALTIS G4 Floodlight - icon 9PROTECTIVE EARTH FOR LED MODULE
7NTCTHERMAL MEASURE INPUT
11LED1+CONNECTION (TOP Brick)
2-1LED1-CONNECTION (TOP Brick)
52LED2+CONNECTION (MID Brick)
6-2LED2-CONNECTION (MID Brick)
33LED3+CONNECTION (BOT Brick)
4-3LED3-CONNECTION (BOT Brick)

THORN ALTIS G4 Floodlight - Figure 16

SIGNALLING LED INDICATIONS ON THE GEAR BOX
PERIODPULSESFAULT DESCRIPTIONPRIORITY
The encoded faults are based on pulses emitted every 4 seconds1One or more CCR module enabled by config are not communicating with logic boardMaximum
THORN ALTIS G4 Floodlight - icon 6Minimum
5Firmware version of one or more CCR module is not compatible with logic board firmware version
2One or more CCR’s output is short-circuited
3Load failure on one or more CCR’s output
4Thermal derating active (output current reduction)

CABLE GLAND

TYPEØMinØMax
M165 mm10 mm
M2510 mm17 mm
M3213 mm21 mm

ALG4 GB 432L / ELECTRICAL CONNECTION / RDM-DMX

THORN ALTIS G4 Floodlight - Figure 17Extreme caution: Do not connect any LED CONNECTION wire (high voltage) inside NTC connector !! It could result in a critical failure and damage irreversibly the ALTIS luminaire

PINOUT
NumberLabelDescription
L1AC LINE 1 INPUT
L2AC LINE 2 INPUT
THORN ALTIS G4 Floodlight - icon 8PROTECTIVE EARTH
ADMX INPUT DATA+
ADMX-RE-LAUNCH DATA+
BDMX INPUT DATA-
BDMX-RE-LAUNCH DATA
SDMX COMMON / SHIELD
SDMX COMMON / SHIELD
THORN ALTIS G4 Floodlight - icon 9PROTECTIVE EARTH FOR LED MODULE
7NTCTHERMAL MEASURE INPUT
1-1LED1+CONNECTION (TOP Brick)
21LED1-CONNECTION (TOP Brick)
52LED2+CONNECTION (MID Brick)
6-2LED2-CONNECTION (MID Brick)
33LED3+CONNECTION (BOT Brick)
4-3LED3-CONNECTION (BOT Brick)

THORN ALTIS G4 Floodlight - Figure 18

SIGNALLING LED INDICATIONS ON THE GEAR BOX
PERIODPULSESFAULT DESCRIPTIONPRIORITY
The encoded faults are based on pulses emitted every 4 seconds1One or more CCR module enabled by config are not communicating with logic boardMaximum
THORN ALTIS G4 Floodlight - icon 6 Minimum
5Firmware version of one or more CCR module is not compatible with logic board firmware version
2One or more CCR’s output is short-circuited
3Load failure on one or more CCR’s output
4Thermal derating active (output current reduction)

CABLE GLAND

TYPEØMinØMax
M165 mm10 mm
M2510 mm17 mm
M3213 mm21 mm

ALG4 GB 432L MOUNTING

THORN ALTIS G4 Floodlight - Figure 19

ALG4 GB 432L / 200-250 Vac – ALG4 GB 432L/250-440 Vac

CIRCUIT BREAKER recommendation
It should mentioned in the notice that calculation has been done with a Circuit Breaker Load Factor of 100%.

V in
Nominal
Inrush Current Data# Drivers for each Circuit Breaker
I peak
(A)
Half Value
Time (ps)
Type B
10A
Type B
16A
Type B
20A
Type B
25A
Type C
10A
Type C
16A
Type C
20A
Type C
25A
Type D
10A
Type D
16A
Type D
20A
Type D
25A
230Vac402500011201120112
400Vac682000011111221123

GUIDELINE FOR INTEGRATION OF GEAR BOXTHORN ALTIS G4 Floodlight - Figure 20If you cannot follow instructions included in previous section regarding gear box integration, you have to measure Tc reference point taking into consideration that measures must be down to Tc_max

Tc Reference at Max Ambient
PositionHorizontalVerticalSide
THORN ALTIS G4 Floodlight - Figure 21
230Vac81°C80°C82°C (Ref.)
400Vac69°C68°C70°C (Ref.)
Ambient Max55°C55°C55°C (Ref.)

ALG4 GB LE 432L / ELECTRICAL CONNECTION

THORN ALTIS G4 Floodlight - Figure 22

PINOUT

NumberLabelDescription
LAC INPUT
NAC INPUT
PEPROTECTIVE EARTH
PEPE FOR LED MODULE
NTCTHERMAL PROTECTION FOR LED FIXTURE
3V3+OUTPUT CHANNEL 3+ (BOT Brick)
1V3-OUTPUT CHANNEL 3- (BOT Brick)
2V2+OUTPUT CHANNEL 2+ (MID Brick)
4V2-OUTPUT CHANNEL 2- (MID Brick)
5V1+OUTPUT CHANNEL 1+ (TOP Brick)
6V1-OUTPUT CHANNEL 1- (TOP Brick)

THORN ALTIS G4 Floodlight - Figure 23 The wiring should be strictly followed by the marking label instruction, Otherwise the product could be damaged or the fonctions could be affected.
Each set of + or – are not potential identical, cross connection is prohibited.

CABLE GLAND
TYPEØMinØMax
M206.3 mm11.3 mm
M2510 mm16.3 mm

ALG4 GB LE 432L MOUNTING

THORN ALTIS G4 Floodlight - Figure 24

ALG4 GB LE 432L / 200-250 Vac – ALG4 GB LE 432L/250-440 Vac

Drivers for each circuit breaker
Referring to the circuit breakers available on the market, the maximum number on the driver connectable for each circuit breaker is as the following table.

Circuit Breaker TypeMCB B/C 10AMCB B/C 16AMCB B/C 20AMCB B/C 25AMCB B/C 32A
Input: 220~240Vac11223
Input: 380~400Vac12234

GUIDELINE FOR INTEGRATION OF GEAR BOXTHORN ALTIS G4 Floodlight - Figure 25If you cannot follow instructions included in previous section regarding gear box integration, you have to measure Tc reference point taking into consideration that measures must be down to Tc_max

Tc Reference at Max Ambient
PositionHorizontalVerticalSide
THORN ALTIS G4 Floodlight - Figure 26
220Vac85°C84°C85°C (Ref.)
400Vac80°C77°C80°C (Ref.)
Ambient Max50°C50°C50°C (Ref.)

Aiming Device

ALTIS LED AIMING DEVICE
Installation instructionsTHORN ALTIS G4 Floodlight - Figure 27

96671487ALTIS G5 AIMING DEVICE WITH VISOR
96671488ALTIS G5 AIMING DEVICE BRACKET

THORN ALTIS G4 Floodlight - Figure 28Louvres / Bird Deterrent
ALTIS LED
Installation instructions
TYPE: ALTIS LED G4/G5 ACCESSORIESTHORN ALTIS G4 Floodlight - Figure 29THORN ALTIS G4 Floodlight - Figure 30

96671492ALTIS G5 1 BRICK LOUVRE A4
96671493ALTIS G5 1 BRICK LOUVRE A5
96671494ALTIS G5 1 BRICK LOUVRE A6/A6I
96671496ALTIS G5 1 BRICK LOUVRE MB
96671495ALTIS G5 1 BRICK LOUVRE NB/EB
96671497ALTIS G5 1 BRICK LOUVRE WB

96671489 ALTIS G5 BIRD DETERRENT
Visor
ALTIS LED
Installation instructions
TYPE: ALTIS G4/G5 ACCESSORIES
THORN ALTIS G4 Floodlight - Figure 3196671498 ALTIS G5 1 BRICK AJ VISORTHORN ALTIS G4 Floodlight - Figure 32Power supply support
ALTIS LED
Installation instructions
TYPE: ALTIS G4/G5 ACCESSORIESTHORN ALTIS G4 Floodlight - Figure 3396671490 ALTIS G5 GB BRACKET 3 BRICK STIRRUPTHORN ALTIS G4 Floodlight - Figure 34

  • Replace any cracked protective shield.
  • Class II luminaires must be installed so that exposed metal work of the luminaire is not in contact with any part of the electrical installation connected to a protective conductor.
    WARNING: Class I luminaires must be earthed.
  • This luminaire operates at mains voltage which must be switched off before intervention in control gear.
  • Any modification to this luminaire is forbidden.
  • Lighted objects nearer than the minimal distance in the is forbidden.

THORN ALTIS G4 Floodlight - icon 7

Thorn Lighting is constantly developing and improving its products. The right is reserved to change specifications without prior notification or public announcement.

© Thorn Lighting

  • To ensure maintaining the best system performances, we advice to switch on the system “At least one night hour per month”.
  • corrosion environment from C1 to C5 according to standard ISO9223 except gear box ALG4 GB LE 432L corrosion environment from C1 to C3

 

 

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals