Senseair Se-0115 Asense Rl Co2 And Temperature Transmitters Installation Guide

Senseair Se-0115 Asense Rl Co2 And Temperature Transmitters Installation Guide

Senseair - logoSE-0115 aSENSE RL CO2 and Temperature Transmitters
Installation Guide

Senseair SE 0115 aSENSE RL CO2 and Temperature Transmitters

1 top part
2 lid
3 front part
4 wall plate
5 screw
6 label with settings inside the top part

Dismounting the sensor

Senseair SE 0115 aSENSE RL CO2 and Temperature Transmitters - Dismounting the sensorSenseair SE 0115 aSENSE RL CO2 and Temperature Transmitters - Dismounting the sensor 2Senseair SE 0115 aSENSE RL CO2 and Temperature Transmitters - Dismounting the sensor 3
Pull the top part upwardsPush the front part with the lid upwards while keeping the wall plate steadyFold the front part with the lid forwards and lose it from the hooks (#1)

Mounting the sensor

Senseair SE 0115 aSENSE RL CO2 and Temperature Transmitters - Mounting the sensor 2Senseair SE 0115 aSENSE RL CO2 and Temperature Transmitters - Mounting the sensor 3
Screw head diameter: max 7.5mm
(0.295 inches) Screw head height: max 2.5mm
(0.1 inches)
A) Put the top tabs of the front part
into the top holes of the wall plate.
(B) Press the lower edge of the case on to the wall plate to latch
The top part is pushed under the locking hooks of the wall plate and is secured with a screw.

If the connection cables are drawn through a conduit the conduit must be sealed.
The air of different temperatures may otherwise disturb the temperature measurements.

If possible keep the sensor powered up after mounting. Connect the analog output before measuring (see Electrical connections).

Senseair SE 0115 aSENSE RL CO2 and Temperature Transmitters - iconIf for some reason, the PCB must be removed, care must be taken to protect from electrostatic discharge! Normally, removing the PCB is NOT required.

Senseair SE 0115 aSENSE RL CO2 and Temperature Transmitters - Mounting the sensor 4

Terminals and jumpers under the top part on a sense RL. The darker positions are default settings.

Electrical connections

The power supply has to be connected to Senseair SE 0115 aSENSE RL CO2 and Temperature Transmitters - icon 2 and Senseair SE 0115 aSENSE RL CO2 and Temperature Transmitters - icon 3.Senseair SE 0115 aSENSE RL CO2 and Temperature Transmitters - icon 3 is considered as system ground. If the analog output is connected to a controller the same ground reference has to be used for the aSENSE RL unit and for the control system! Unless different transformers are used, special precautions need to be taken.

Connection
Terminal
FunctionElectrical DataRemarks
Senseair SE 0115 aSENSE RL CO2 and Temperature Transmitters - icon 4Power (+)
Power ground (-)
24 VAC/DC+ (+-20%), 3W
24 VAC/DC-
2W without output load
See note 1!
Out(1)
CO2
Out(2)
Temp
Analogue Output 1 (+) 0-2000 ppm
See label for non-standard
Analog Output 2 (+)
0-50 °C ppm
See label for non-standard
0-10 VDC or 0-20 mA,
2-10 VDC or 4-20 mA,
Same as Output 1
According to positions of Out(1) and start point jumpers.
See note 2!
According to positions of Out(2) and start point jumpers.
See notes 2 and 3!
5
6
7
Normally closed relay Relay COM
Normally open relay
Contact-free relay
minimum load 1mA/5V rated load 0,5A/125VAC; 1A/24VDC
Triggered by register
Out(3)
Standard relay ON/OFF 1000/900 ppm CO2
See label for non-standard
8Not used

Table I. Electrical terminal connections for aSENSE RL

Note 1: The ground terminal is used as negative power supply DC input or AC phase ground Senseair SE 0115 aSENSE RL CO2 and Temperature Transmitters - icon 3 (halfwave rectifier). A single transformer may be used for the entire system.

Note 2: aSENSE RL can deliver a voltage or a current loop for Out(1)/ Out(2). To change between voltage and current output mode the hardware jumpers are used. There is one jumper for Out(1) and one for Out(2), so that one output can be a voltage output and the other a current output. Both, voltage output and current output can have start points O % (0-1 O VDC or 0-20mA) or 20 % (2-10 VDC or 4-20mA). The same starting point is used for both outputs. See the function manual.

Note 3: Please use voltage outputs for temperature measurements. The accuracy of temperature measurements is valid only for units configured in voltage outputs mode.

Senseair SE 0115 aSENSE RL CO2 and Temperature Transmitters - Dimensions and holes

Senseair® AB (headquarter)
Stationsgatan 12
Phone: +46-(0)653-71 77 70
Box 96
E-mail; [email protected]
824 08 Delsbo
SWEDEN Web site: www.senseair.com

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals