Solax Power X3 Three-phase Eps Box Installation Guide

X3 Three-Phase EPS Box

Product Information

The Three-Phase EPS Box is a power steering unit that integrates
two contactors. It simplifies the operation and improves security
for users. This product is compatible with Three-phase EPS
change-over application and requires 13 wires to complete the
steering circuit. The EPS Box dimensions are 300mm x 170mm x
220mm.

Mounting Requirements

The installation site should not be exposed to direct sunlight.
The installation process requires four cushion blocks, self-tapping
screws, and a marker pen. The installation process also requires
expansion screws, expansion tubes, cold pressed terminals, silicone
sleeves, diagonal pliers, Philips screwdriver, 6 driller, crimping
plier, manual wrench, and rubber hammer.

Packing List

  • Expansion screws x4
  • Expansion tubes x4
  • Cushion blocks x4
  • Self-tapping screws x4
  • Cold pressed terminals x15
  • Silicone sleeves x15

Product Usage Instructions

Mounting

  1. Install four cushion blocks on Three-phase EPS Box with
    self-tapping screws.
  2. Use Three-phase EPS Box with cushion blocks as a template to
    mark the four holes’ position on the wall with a marker pen.
  3. Drill holes with a 6 driller carefully. Make sure the holes are
    deep enough for installing. Install the expansion tubes through
    cushion blocks into the holes and tighten them.
  4. Install the expansion screws with a screwdriver to fix the
    Three-phase EPS Box.

Wiring Connection

Wires Making

Prepare wires as below. Use the diagonal plier to strip 15mm of
insulation from the side of the wire.

  • L wire x9 pcs
  • N wire x3 pcs
  • GND for EU x1 pcs (or N wire for AU x1 pcs)

If AWG-10 wires are used, pass the wires through the silicone
sleeves to avoid leakage at the insertions.

Grid-Wires Connection

Use the manual wrench to screw off the cap on the cable nut,
then insert Grid-L wires and Grid-N wires into the ports
(L1,L2,L3,L4) of contactor A through the cable nut and tighten them
with a screwdriver.

EPS-Wires Connection

Screw off the cap on the cable nut, then insert EPS-L wires and
EPS-N wires into ports (L1,L2,L3,L4) of contactor B through the
cable nut and tighten them with a screwdriver.

Load-Wires Connection

Screw off the cap on the cable nut, then insert Load-L wires and
Load-N wires into ports (T1, T2, T3, T4) of contactor C through the
cable nut and tighten them with a screwdriver.

Earth-Wire Connection

In EU, insert GND wire into port of contactor (B: L4) through
the cable nut and tighten it with a screwdriver. In AU, insert N
wire into ports of contactor(A: L4&B: L4).

300mm 170mm

Quick Installation Guide
Three-Phase EPS Box
1. Introduction
Three-phase EPS Box integrates two contactors which provide power steering for users. It is compatible with Three-phase EPS change-over application. Configured with Three-phase EPS Box, customers need to connect 13 wires to complete the steering circuit. It can simplify the operation and improve security.
2. Overview 220mm

EPS Box EPS Load

Object 1 2 3

Description EPS Grid Load

4. Mounting
Step 1:
Make sure the installation site does not expose to direct sunlight. Then install the four cushion blocks on Three-phase EPS Box with self-tapping screws.

cushion blocks

self-tapping screws

Step 2:
Use Three-phase EPS Box with cushion blocks as a template to mark the four holes’ position on the wall with marker pen.
mark position

3. Preparation

3.1Packing List Checking
Before installation, make sure that nothing inside the package is damaged. The following items should be inside the package.

1

,

,,

expansion screws expansion tubes

X 4

X 4

cushion blocks X 4

self-tapping screws X 4

cold pressed terminals X15

Silicone sleeves X15

3.2 Tools
Before you start, get the following tools ready.

Diagonal plier

Philips screwdriver

6 driller

Crimping plier

Marker pen

Slotted screwdriver Manual wrench Rubber hammer

01

Step 3:
Drill holes with 6 driller carefully, make sure the holes are deep enough for installing. Install the expansion tubes through cushion blocks into the holes and tighten them.

-Drill holes with 6 drill -Depth : at least 50mm

-ighten the expansion tubes

Step 4:
Install the expansion screws with screwdriver to fix the Three-phase EPS Box.

02

5. Wiring Connection

5.1 Wires making Prepare wires as below. Use the diagonal plier to trip
15mm of insulation from side of the wire.

15mm
L wire X9 pcs

15mm
GND For EU X1 pcs
15mm

, Insert wire into cable gland, then insert the end of wire into cold pressed terminal and tighten it.

N wire X3 pcs

For AU x1 pcs

If AWG-10 wires are used, please pass the wires through the silicone sleeves to aviod leakage at the insertions.

5.2 Grid-Wires Connection
Use the manual wrench to screw off the cap on cable nut, then insert Grid-L wires and Grid-N wires into the ports (L1,L2,L3,L4) of contactor A through the cable nut and tighten them with screwdriver.
cable nut contactor B
cap

Grid wires

contactor A contactor C Top View

Grid-N Grid-L Left View

Please prevent other wires from getting loose during operation.

5.3 EPS-Wires Connection
Screw off the cap on cable nut, then insert EPS-L wires and EPS-N wires into ports (L1,L2,L3,L4) of contactor B through the cable nut and tighten them with screwdriver.
cap contactor B
EPS wires

cable nut contactor A contactor C Top View

EPS-N EPS-L Grid-N Grid-L Left View

5.4 Load-Wires Connection
Screw off the cap on cable nut, then insert Load-L wires and Load-N wires into ports ( T1, T2, T3, T4) of contactor C through the cable nut and tighten them with screwdriver.
contactor B cap

load wires

cable cnounttactor A contactor C Top View
03

Load-N Load-L Right View

5.5 Earth-Wire Connection
In EU, insert GND wire into port of contactor (B: L4) through the cable nut and tighten it with screwdriver. In AU, insert N wire into ports of contactor(A: L4&B: L4) .

For EU

For AU

5.6 Checking
Please make sure all wires are tightened. Wire connection in Three-phase EPS-Box.

to EPS port of inverter to Load to E-BAR to GRID
to EPS port of inverter to Load to GRID

For EU

N wire

For AU

Overview of Three-phase EPS Box

For EU

For AU

6. Technical Parameters

Grid Max.AC input current (A)

3×63

Rated AC voltage (V)

3/N/PE~400/230

Rated AC frequency (Hz)
EPS Max.EPS input current (A) Rated EPS voltage (V) Rated EPS frequency (Hz)

50 / 60
3×63 3/N/PE~400/230
50 / 60

Load Rated output current(A), on grid mode Rated output current(A), EPS mode Rated Grid Voltage( V ) Rated Grid Frequency(Hz)
Genaral Data Operating Temperature range ( ) Dimension (mm) Weight (kg)

3×63* 3×63* 3/N/PE~400/230 50/60
-20~+60 300x220x170
4.85

* : The output current will be reduced when the operating temperature exceeds 40. At 50, the output current drops to 95% . At 60,itdropsto80%.

614.00213.03

04

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals