Greystone Tlflf24x01 Flying Lead Low Limit Thermostat Instruction Manual

TLFLF24X01 Flying Lead Low Limit Thermostat

Product Information: Flying Lead Low Limit Thermostat

The Flying Lead Low Limit Thermostat (TLFL Series) is a
temperature sensor that is designed for single point temperature
monitoring in various applications. It can be used in air ducts or
to measure pipe temperature. The thermostat comes with a hinged
enclosure with a latch for protection.

Key Features:

  • Flying lead sensor for easy installation
  • Suitable for air duct or pipe temperature monitoring
  • Can be used with thermal compound for improved heat
    transfer
  • Includes a hinged enclosure with latch for added
    protection
  • Wiring connections are illustrated on page 2 of the manual

Warnings and Limitations:

  • Do not use the thermostat in an explosive or hazardous
    environment
  • Avoid using it with combustible or flammable gases
  • Do not exceed the device ratings
  • Failure to follow the instructions may result in product
    damage

Typical Applications:

The Flying Lead Low Limit Thermostat can be used in the
following applications:

  • Air duct temperature monitoring
  • Pipe temperature monitoring

Product Usage Instructions:

Mounting the Thermostat in an Air Duct:

  1. Select a suitable installation area in the middle of the air
    duct.
  2. Drill a 3/8″ hole in the top of the duct.
  3. Slide the probe through the hole.
  4. Mount a length of flexible duct hanger from top to bottom of
    the duct.
  5. Secure the probe to the duct hanger using a tube clamp or wire
    tie.

Refer to Figure 1 in the manual for a visual representation of
the mounting process.

Measuring Pipe Temperature:

  1. Select a suitable spot along the pipe.
  2. If insulation is present, remove a small section and set it
    aside.
  3. Apply thermal compound on the pipe to improve heat
    transfer.
  4. Lay the probe in the thermal compound and secure it to the pipe
    using a worm gear clamp (not included).
  5. For added protection, wrap the probe cable around the pipe 1-2
    times.

Re-install the insulation if necessary, allowing the sensor
cable to protrude. See Figure 2 in the manual for a visual
representation of the process.

Enclosure Installation:

  1. Open the hinged cover of the enclosure by pulling slightly on
    the latch on the right side.
  2. If needed, screw the EMT connector or cable gland connector
    into the provided 1/2″ NPT threaded connection hole at the bottom
    of the enclosure.
  3. Make wiring connections as per the wiring illustrations on page
    2 of the manual.
  4. Close the enclosure’s swing door until securely latched. For
    added security, use the provided screws on the integrated screw
    tabs.

Refer to Figures 3, 4, and 5 in the manual for visual
representations of the enclosure installation process.

For detailed wiring instructions, refer to Figures 6, 7, 8, 9,
and 10 in the manual.

Flying Lead Low Limit Thermostat
TLFL Series – Installation Instructions

INTRODUCTION
The single point flying lead low limit thermostat incorporates a precision thermistor temperature sensor and provides a Form C relay output (NO/NC) with an adjustable setpoint. The sensor is encapsulated in a 6 mm (0.236″) OD X 50 mm (2″), 304 series stainless steal probe. Standard wire length is 3.05m (10′). All probes are constructed to provide excellent heat transfer, fast response and are potted to resist moisture penetration. A hinged and gasketed Polycarbonate enclosure is provided for ease of installation.

BEFORE INSTALLATION

Read these instructions carefully before installing and commissioning the temperature

sensor. Failure to follow these instructions may result in product damage. Do not use

in an explosive or hazardous environment, with combustible or flammable gases, as

a safety or emergency stop device or in any other application where failure of the

MOUNTING

product could result in personal injury. Do not exceed the device ratings.

The flying lead sensor can be used in several different types of applications where single point temperature monitoring is required.

Listed below are some typical applications

The flying lead sensor can be installed directly into any air duct. Select a suitable installation area in the middle of the duct. To achieve the best reading, do not place in an area where air stratification may be present. Avoid areas where the sensor is exposed to vibrations or rapid temperature changes.

Once a suitable spot is selected, drill a 3/8″ hole in the top of the duct and slide the probe through, mount a length of flexible duct hanger from top to bottom of the duct. Mount the probe to the duct hanger using a tube clamp or wire tie. See Figure 1.

Figure 1

The flying lead could also be used to measure pipe temperature. Select a suitable spot along the pipe, remove a small section of insulation if present and set aside. It is recommended that thermal compound be used to improve heat transfer. Spread a liberal amount on the pipe. Lay probe in thermal compound and secure sensor to pipe using a worm gear clamp (not included).

For added protection it is recommended to wrap the probe cable around the pipe 1-2 times. Re-install insulation if present, allowing sensor cable to protrude. See Figure 2.

The enclosure has a hinged cover with latch. Open cover by pulling slightly on the latch on the right side of the enclosure. At the same time pulling on the cover, as shown in Figure 3.

Figure 2

A 1/2″ NPT threated connection hole is provided in the bottom of the enclosure. Screw the EMT connector or cable gland connector in until tight. See Figure 4. It is recommended that weatherproof conduit or cable gland fittings be used. An optional 1/2″ NPT to M16 thread adapter and cable gland fitting is available.

Make wiring connections as per the “Wiring” illustrations on Page 2.

Swing door closed until securely latched. For added security, 2 screws are provided that may be installed in the integrated screw tabs. See Figure 5.

Figure 3

Figure 4

Figure 5

Thread adapter and cable gland fitting

IN-GE-TLFLXXX-003

EMT Connector Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com

Page 1

WIRING
· Deactivate the 24 Vac/dc power supply until all connections are made to the device to prevent electrical shock or equipment damage. · Use 14-22 AWG shielded wiring for all connections and do not locate the device wires in the same conduit with wiring used to supply inductive loads such as
motors. Make all connections in accordance with national and local codes. · The temperature thermostat comes with the temperature sensor pre-wired to the PCB. If removal is required for installation then it may be re-wired as shown
in Figure 6. · Pull at least six inches of control wire into the enclosure, then complete the wiring connection according to the wire diagram for the applicable power supply
as shown in Figure 7. · Connect the DC positive or the AC voltage hot side to the PWR terminal. The supply common is connected to the COM terminal. See Figure 7. · The relay has both Normally Open (NO) and Normally Closed (NC) contacts available. The relay output is available on the NO/COM/NC terminal. Make
connections before applying power as shown in Figure 8. · The setpoint differential has 3 jumper selectable settings (Low/Mid/High). Set jumper to desired differential as shown in Figure 9. · To set the switching setpoint, turn the setpoint potentiometer to the desired temperature setting as shown in Figure 10. · Once all connections settings are made and checked, power can be applied.

Figure 6 Temperature sensor wiring to PCB (Factory Wiring)
No Polarity

Figure 8

Relay Output Wiring

DIFFERENTIA L
HIGH MID LOW

NO COM NC

TEMP COM PWR

Figure 9 Setpoint Differential Setting

DIFFERENTIAL
HIGH MID LOW

HIGH = 5.6°C/10°F MID = 2.8°C/5°F LOW = 1.1°C/2°F

Figure 7

NO

+24 Vdc Digital

Power Supply Wiring

COM

DI

INPUT

NC

Controller

Temperature Sensor

COM PWR

COMMON +24 Vdc

24 Vdc Power Supply

NO

+24 Vdc

COM

COMMON

Figure 10

Setpoint Adjustment

NC

24 Vdc Power Supply

3C/38F

COMMON

1C/33F

5C/42F

COM

COMMON

DI

-2C/29F

8C/46F

PWR

24 Vac

Controller

-4C/25F SETPOINT 10C/50F

24 Vac Transformer

SPECIFICATIONS:
Power Supply:…………………………………..12 to 28 Vac/dc Consumption:…………………………………..50 mA max Relay Contacts:…………………………………SPDT, Form C contacts (N.O. and N.C.)
5 Amps @ 30 Vac/250 Vac resistive 1.5 Amps @ 30 Vdc/250 Vac inductive Relay Action:……………………………………..Activates on temperature fall – Auto reset Setpoint Operation:………………………..Single-turn knob-pot on PCB Adjustable Setpoint:……………………….-4 to 10°C (25 to 50°F) Temperature Differential:………………Low: 1.1°C (2°F) Mid: 2.8°C (5°F) High: 5.6°C (10°F) Jumper selectable Temperature Sensor:………………………10K ohm curve matched precision thermistor Sensor Accuracy:……………………………..±0.2°C, 0 to 70°C (±0.36°F, 32 to 158°F) Probe Sensing Range:…………………….-40 to 60°C (-40 to 140°F) Probe Material: …………………………………304 Series Stainless Steel Probe Diameter:……………………………….6 mm (0.236″) Wire Material: ……………………………………FT-6 Plenum-rated cable Wire Length: ……………………………………..3.05m (10′) Operating Conditions:……………………-10 to 50°C (14 to 122°F), 5 to 95% RH, non-condensing Storage Conditions: ………………………..-30 to 70°C (-22 to 158°F), 5 to 95% RH, non-condensing Wiring Connections:……………………….Screw terminal block (14 to 22 AWG) Enclosure:…………………………………………..Grey Polycarbonate UL94-V0, IP65 (NEMA 4X) Optional thread adapter (1/2″ NPT to M16) and cable gland fitting Country of Origin:……………………………Canada

DIMENSIONS
112.5 mm 4.43″
99.7 mm 3.93″
53.7 mm 2.11″
0.5″ NPT

116.5 mm 4.58″

3.05 m 10.00′

FT-6 Rated Plenum Cable, 22 AWG

50 mm 2″

6.0 mm 0.236″

304 Series S/S Probe

PRINTED IN CANADA

IN-GE-TLFLXXX-003

Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com

Page 2

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals