Roth Minishunt Plus Wireless Regulation Installation Guide

Roth Minishunt Plus Wireless Regulation Installation Guide

Roth logoRoth Mini shunt Plus
Installation

Roth Minishunt Plus Wireless RegulationLiving full of energy

Description

Roth Mini shunt Plus is intended  for supplying and connecting small floor  heating system to existing radiator heating systems. Two underfloor hes ting circuits can be connected with the dual coupling. The room tempera- ture is controlled via a thermostat with capillary sensor or a wireless room thermostat and actuator (fixed-value  temperature contra) Can be used on both 1- and 2-string systems and has a built-in temperature limit of 45°C.
Roth Mini shunt Plus:

1. Valve for thermostat or actuator7. Flow, secondary
2. Circulation pump8. Regulation valve for water volume
3. Air vent9. Bypass valve for 1- or 2-string systems
4. Flow, primary10. Analog thermometer
5. Return, primary11 Insulation Box
6. Return, secondary

Roth Minishunt Plus Wireless Regulation - Description

Pipe dimensionsNumber of loopsMay. pipe length
10,5 mm170m
10,5 mm22x70m
16 mm190m
16 mm22x90m
20 mm1120m
20 mm22x120m

Secure an equal length when installing 2 loops.

Assembly requirements

  • The Roth Mini shunt Plus must be mounted in horizontal position as shown in picture 1
  • It must be ensured there is a differential pressure of Min. 15 kPa and Max. 50 kPa
  • The water temperature on the installation side should be min. 15°C higher than the underfloor circuit.
  • Always flush the installation before attaching the Roth Mini shunt Plus.

Roth Minishunt Plus Wireless Regulation - Assembly requirements

 Assembly

  • Attach the Mini shunt Plus to a suitable wall. The pump will not cause  noise due to the dense shunt body.
  • Vent and perform pressure testing according to industry rules. Water filing, flushing and venting is optimized by combining  the design of the  shunt body with the air vent.
  • Set between 1- and 2-string systems see page 6.
  • Mount the thermostat or the actuator (wireless control only) on the  valve
  • Sensor or thermostat is placed approx. 1.7 m above the floor on an inner wall in a representative place.
  • Set the pump to constant pressure. Normally. a setting as shown in image 2€ will be sufficient to achieve optimal comfort with minimum noise.

Indicator lights (LEDs)
(2A)
> Signal display
> LED is lit up in green in normal operation
> LED lights up/flashes  in case of a fault
(2B)
> Display of selected control mode AP-v, AP-c and constant speed
(2C)
> Display  of selected pump curve ( I, I I,  I I) within the control mode
(2D)
> LED indicator combinations during the pump venting function, manual restart and key lock
>No light  in LED = No power

Roth Minishunt Plus Wireless Regulation - Indicator lights (LEDs)

Setting of Mini shunt for 1- or 2-string system, picture 3+ 4
(The factory setting is 2-string)

  • 2-string system 2.5 mm Allen screw must be completely at the bottom,  see picture 3.
  • L-string system, 2.5 mm Allen screw must be set in relation  to the desired  bypass water volume. Figure 4 shows the percentage of water that is  passed through the bypass screw at the various settings.

Roth Minishunt Plus Wireless Regulation - Setting

Roth Minishunt Plus Wireless Regulation - Bypass valve,Bypass valve, turns open

Technical data

ApplicationUnderfloor heating system
Roth Mini shunt Plus with capillary sensorHVAC no. 7466210141
Roth Mini shunt Plus with basic wireless thermostatHVAC no. 7466210310
Roth Minishunt Plus with advanced wireless  thermostat and heating elementHVAC no. 7466210351
Max operating pressure6 bar
Max operating temperatureMax. 80°C on primary side
Max operating temperatureMax. 45°C on secondary side
PumpWilo PARA MS/ 6-43/ SC-12
Thread primary sideEURO 4″ EXL/MT
Thread secondary sideELIXIR 34″ Ext./MT
MaterialBrass CW614
Electrical connection230V, 50 Hz with earthing
Pump output3-45W
AntifreezeWater mixed with max. 50%Glycol

Accessories

Roth Duo CC T Connection – 10,5 mmHVAC no. 7401974830
Roth Duo Splitter Set 4″ 12 – 20 mmHVAC no. 7046296220
Roth adapter 16 mm x 34″ EUROHVAC no. 7046217546
Roth adapter 20 mm x34* EUROHVAC no. 7046217550
Roth marigold coupler 10.5 mm x 3% EUROHVAC no. 7401974810
Roth marigold coupler 12 mm x %” EUROHVAC no. 7401974812
Roth marigold coupler 15 mm x %4 EURDHVAC no. 7401974815
Roth marigold coupler 16 mm x 4 EURDHVAC no. 7401974816*
Roth marigold coupler 17 mm x %4 EUROHVAC no. 7401974817
Roth marigold coupler 18 mm x %” EUROHVAC no. 7401974818
Roth marigold coupler 20 mm x %” EUROHVAC no. 7401974820*
Roth marigold cabinet Roth Mini shunt PlusHVAC no. 7046219540

Roth Minishunt Plus Wireless Regulation - qr codeRoth Mini shunt Plus QR
https://roth.support/minishunt

Roth logo

ROTH DANMARK A/S
Centervej 5
3600 Frederikssund
Tl +45 4738 0121
E-mail: servicemroth-danmark.dk
roth-danmark.dk
ROTH SVERIGE AB
Hujdrodergatan 22
212 39 Malmo
Tel. +46 40534090
Fax +46 40534099
E-mail: [email protected]
roth-sverige.se
ROTH NORGE AS
Billingstadsletta 19
1396 Billingstad
Tel. +47 67 57 54 00
E-mall: [email protected]
facebook.com/RothNorge
ROTH FINLAND OY
Sysimiehenkatu 12
10300 Karjaa
Puh. +358 (0)19 440 330
S-posti: [email protected]
facebook.com/RothFinland

ROTH UK Ltd
1a Berkeley Business Park
Wainwright Road
Worcester
WR4 9FA
Phone +44 (0) 1905 453424
E-Mail [email protected]
[email protected]
[email protected]
[email protected]
roth-uk.com

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals