Resideo Fk09s Braukmann Filter Combination Installation Guide

Resideo Fk09s Braukmann Filter Combination Installation Guide

resideo FK09S Braukmann Filter Combination Installation Guide
resideo FK09S Braukmann Filter Combination

Safety Guidelines

  1. Follow the installation instructions.
  2. Use the appliance
    • according to its intended use
    • in good condition
    • with due regard to safety and risk of danger.
  3. Note that the appliance is exclusively for use in the applications detailed in these installation instructions (see 2 Technical Data). Any other use will not be considered to comply with requirements and would invalidate the warranty.
  4. Please take note that any assembly, commissioning, servicing and adjustment work may only be carried out by authorized persons.
  5.  Immediately rectify any malfunctions which may influence safety

Technical Data

Media 
Medium:Drinking water
Connections/Sizes
Connection sizes:1/2″ – 2″
Pressure values
Min. operating pressure:1.5 bar (dynamic pressure)
Max. inlet pressure with clear filter bowl:16 bar
Outlet pressure:1.5 – 6 bar
Operating temperatures
Max. operating temperature medium accord. to EN 1567:30 °C
Specifications
Installation position:Horizontal with filter bowl downwards

Options

For Options visit homecomfort.resideo.com/europe

Assembly

Installation Guidelines

Install in horizontal pipework with filter bowl downwards

  • This position ensures optimum filter efficiency
  • Install shut-off valves
  • Ensure good access
    •  Pressure gauge can be read off easily
    •  Degree of contamination can be easily seen with clear filter bowl
    •  Simplifies maintenance and inspection
  • The installation location should be protected against frost
  • Related to the EN 806-2 it is recommended to install the filter immediately after the water meter
  • In order to avoid flooding, it is recommended to arrange a permanent, professionally dimensioned wastewater connection
Assembly instructions

Assembly

  1. Thoroughly flush pipework
  2.  Fit filter combination
    • Note flow direction
    • Install without tension or bending stresses
  3.  Seal in pressure gauges
  4.  Set outlet pressure
Discharge of reverse rinsing water

Assembly

The reverse rinsing water must be routed to the drain channel in such a way that no backwater can occur. To do this there are 3 options:

  1. Direct connection:
    • Connector DN 50/70 as well as the necessary pipes and siphon (3 elbows 90°) in DN 70.
  2.  Discharge into floor drain
  3. Drain into open container.

Filter size: Reverse rinsing volume*
1/2″ and 3/4″:12 Liter
1″ and 1 1/4″:  15 Liter
1 1/2″ and 2″ : 18 litres
at 4 bar inlet pressure and 3 x 3 seconds reverse rinsing duration

Start-up

Setting outlet pressure

Setting outlet pressure

Set outlet pressure min. 1 bar under inlet pressure.

  1. Close shut-off valve on inlet
  2. Release pressure on outlet side (e.g. through water tap)
  3. Close shut-off valve on outlet
  4. Loosen slotted screw
    • Do not remove slotted screw
  5. Slacken tension in compression spring
    • Turn adjustment handle counter clockwise (-) until it does not move any more
  6. Slowly open shut-off valve on inlet
  7. Turn control handle until the setting scale shows the desired value
  8. Retighten slotted screw
  9. Slowly open shut-off valve on outlet

Reverse rinsing

During reverse rinsing, an inlet (dynamic) pressure of at least 1.5 bar is required. The reverse rinsing interval depends on the degree of dirt in the water. At the latest every 6 months, reverse rinsing should be carried out according to EN 806-5. Our recommendation at least every 2 months! To ensure convenient and regular adherence to the reverse rinsing interval, we recommend installing an automated reverse rinsing system Z11S.
Filtered water can also be tapped during reverse rinsing.

Manual reverse rinsing

Reverse rinsing

If reverse rinsing water is not to be discharged via a direct connection, a collecting container must be positioned beneath before reverse rinsing.

  1. Open ball valve by turning the reverse rinsing button to the stop point
    • Select bar must be upright
    • The patented reverse rinsing system starts
  2. Close ball valve again after approx. 3 seconds.
    Repeat procedure three times
    • If the filter is extremely dirty, the procedure may have to be repeated additional time
      With aid of the memory ring, the next deadline for manual reverse rinsing can be booked.
Automatic reverse rinsing with the Z11S

Automatic reverse rinsing with the Z11S

The automated reverse rinsing system Z11S is available as an accessory. The automated system reliably takes over reverse rinsing of the filter at intervals which can be set between 4 minutes and 3 months.

Maintenance

In order to comply with EN 806-5, water fixtures must be inspected and serviced on an annual basis. As all maintenance work must be carried out by an installation company, it is recommended that a servicing contract should be taken out.

In accordance with EN 806-5, the following measures must be taken:

Inspection

Pressure reducing valve
  1. Close shut-off valve on outlet
  2.  Check outlet pressure using a pressure meter when there is zero through-flow
    • If the pressure is increasing slowly, the valve may be dirty or defective. In this instance, carry out servicing and cleaning (See 6.2 Maintenance)
  3. Slowly open shut-off valve on outlet
Filter
  • The filter must be cleaned by reverse rinsing regularly, at least every 6 months. (acc. to EN 806-5) Our recommendation at least every 2 months!
  • Non-compliance can lead to the filter becoming blocked This results in a drop in pressure and decreased water flow
  • The filter meshes are made of stainless steel. A red coating as a consequence of rust from the pipelines has no influence on function or the way the filter works

CAUTION! Do not forget to do a visual check of the ball valve. Replace if it is dripping!

Maintenance

If necessary, the outside surface of the filter combination can be cleaned. Use only cold, clear drinking water to clean the surfaces! Any other cleansers cause damage to the plastic components!

Pressure reducing valve

Pressure reducing valve

  1. Close shut-off valve on inlet
  2. Release pressure on outlet side (e.g. through water tap)
  3. Close shut-off valve on outlet
  4. Loosen slotted screw
    • Do not remove slotted screw
      CAUTION
      There is a spring in the spring bonnet. It may cause injuries if the spring is derailing.
    • Make sure tension in compression spring is slackened!
  5. Slacken tension in compression spring
    • Turn adjustment handle counter clockwise (-) until it does not move any more
    • Do not turn in too far!
  6. Unscrew spring bonnet
    • Use double ring wrench ZR10K
  7. Remove slip ring
  8. Remove valve insert with a pair of pliers
  9. Unscrew filter bowl and guide piece
    • Use double ring wrench ZR10K
  10. Remove old filter insert and replace by a new one!
  11. Remove slotted ring
  12. Place O-ring onto filter bowl
  13. Screw in filter bowl hand-tight (without tools)
  14. Check that sealing ring, edge of nozzle and slotted ring are in good condition, and if necessary replace the entire valve insert
  15. Reassemble in reverse order
    Press in diaphragm with finger before inserting slip ring Screw in filter bowl hand-tight (without tools)
  16. Set outlet pressure and adjust setting scale
  17. Slowly open shut-off valve on inlet
  18. Slowly open shut-off valve on outlet.
Filter
  • Non-compliance can lead to the filter becoming blocked This results in a drop in pressure and decreased water flow
  • The filter meshes are made of stainless steel. A red coating as a consequence of rust from the pipelines has no influence on function or the way the filter works

CAUTION! Do not forget to do a visual check of the ball valve. Replace if it is dripping!

Adjusting the setting scale

f the adjustment knob is removed, this setting is lost. A new setting can be achieved using a pressure gauge.

  1. Close shut-off valve on inlet
  2. Release pressure on outlet side (e.g. through water tap)
  3. Close shut-off valve on outlet
  4. Loosen slotted screw
    • Do not remove slotted screw
  5. Slowly open shut-off valve on inlet
  6. Set desired outlet pressure (e.g. 4 bar)
  7. Align scale (e.g. 4) in middle of viewing window
  8. Retighten slotted screw
  9. Slowly open shut-off valve on outlet

Disposal

Observe the local requirements regarding correct waste recycling/disposal!

Troubleshooting

ProblemCauseRemedy
Water is escaping from the spring bonnetDiaphragm in valve insert is faultyReplace valve insert
Too little or no water pressureShut-off valves up- or downstream of the pressure reducing valve are not fully openOpen the shut-off valves fully
Pressure reducing valve is not set to the desired outlet pressureSet outlet pressure
Filter mesh dirtyReverse rinsing
Not fitted in flow directionFit filter in flow direction (note direction of arrow on housing)
The outlet pressure set does not remain constantFilter mesh dirtyReverse rinsing
Valve insert, sealing ring or edge of nozzle is contaminated or wornReplace valve insert
Rising pressure on outlet (e.g. in boiler)Check check valve, safety group etc

Spare Parts

For Spare Parts visit homecomfort.resideo.com/europe

Accessories

For Accessories visit homecomfort.resideo.com/europe

 

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals