LPV-150-12 150W Single Output Switching Power Supply
Product Information
| Model | DC Voltage | Rated Current | Rated Power | Line Regulation | Load Regulation | Efficiency | Input Voltage Range | Frequency Range | Dimensions | Weight | More Information |
|---|---|---|---|---|---|---|---|---|---|---|---|
| LPV-150-12 | 12V | 10A (0 ~ 10A) | 120W | 200mVp-p | 500ms, 50ms / 230VAC 500ms, 50ms / 277VAC; | 87% | 180 ~ 305VAC 254 ~ 431VDC | 47 ~ 63Hz | 191mm x 63mm x 37.5mm (L x W x H) | 0.74Kg | Product Manual |
| LPV-150-15 | 15V | 8A (0 ~ 8A) | 120W | 200mVp-p | 500ms, 50ms / 230VAC 500ms, 50ms / 277VAC; | 88% | 180 ~ 305VAC 254 ~ 431VDC | 47 ~ 63Hz | 191mm x 63mm x 37.5mm (L x W x H) | 0.74Kg | Product Manual |
| LPV-150-24 | 24V | 6.3A (0 ~ 6.3A) | 151.2W | 200mVp-p | 500ms, 50ms / 230VAC 500ms, 50ms / 277VAC; | 89% | 180 ~ 305VAC 254 ~ 431VDC | 47 ~ 63Hz | 191mm x 63mm x 37.5mm (L x W x H) | 0.74Kg | Product Manual |
| LPV-150-36 | 36V | 4.2A (0 ~ 4.2A) | 151.2W | 200mVp-p | 500ms, 50ms / 230VAC 500ms, 50ms / 277VAC; | 89% | 180 ~ 305VAC 254 ~ 431VDC | 47 ~ 63Hz | 191mm x 63mm x 37.5mm (L x W x H) | 0.74Kg | Product Manual |
Product Usage Instructions
To use the LPV-150 series single output switching power supply,
follow these instructions:
- Ensure that the input voltage is within the specified range of
180 ~ 305VAC or 254 ~ 431VDC. - Connect the power supply to the desired load using appropriate
wiring. - Make sure the load does not exceed the rated current for the
specific model of LPV-150 power supply. - Turn on the input power source.
- The power supply will provide a stable DC voltage output
according to the selected model. - Monitor the load and ensure it remains within the specified
range to prevent overload. - If an overload occurs, the power supply will enter hiccup mode
and automatically recover once the fault condition is removed. - In case of an overvoltage or over-temperature condition, the
power supply will shut down the output voltage. Once the condition
is resolved, the power supply will automatically recover. - Ensure that the working temperature is within the range of
-25°C to +65°C. Refer to the derating curve for temperature
adjustment guidelines. - Keep the power supply in a well-ventilated environment with a
working humidity range of 20% to 90% RH non-condensing. - Store the power supply in a dry and cool place with a
temperature range of -40°C to +80°C and a humidity range of 10% to
95% RH.
150W Single Output Switching Power Supply
LPV-150 series
User’s Manual
IP67
IS 15885(Part 2/Sec13)
THOMAS SAMUEL
THOMAS SAMUEL
R-41027766 (for LPV-150-12,24 only)
File Name:LPV,LPVL-150-SPEC 2023-04-14
Downloaded from Arrow.com.
150W Single Output Switching Power Supply
LPV-150 series
SPECIFICATION
MODEL
LPV -150-12
LPV-150-15
LPV -150-24
LPV-150-36
DC VOLTAGE
12V
15V
24V
36V
RATED CURRENT CURRENT RANGE
10A 0 ~ 10A
8A 0 ~ 8A
6.3A 0 ~ 6.3A
4.2A 0 ~ 4.2A
RATED POWER
120W
120W
151.2W
151.2W
OUTPUT
RIPPLE & NOISE (max.) Note.2 200mVp-p VOLTAGE TOLERANCE Note.3 ±5.0%
200mVp-p
200mVp-p
200mVp-p
LINE REGULATION LOAD REGULATION
±1.0% ±2.0%
SETUP, RISE TIME Note.6 LPV-150: 500ms, 50ms / 230VAC 500ms, 50ms / 277VAC;
LPVL-150: 1500ms, 50ms / 115VAC
HOLD UP TIME (Typ.)
LPV-150: 18ms/230VAC 20ms/277VAC at full load;
LPVL-150: 10ms/115VAC at full load
VOLTAGE RANGE Note.4 LPV-150: 180 ~ 305VAC 254 ~ 431VDC;
LPVL-150: 90~132VAC
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
87%
88%
89%
89%
INPUT
AC CURRENT
LPV-150: 1.7A/230VAC 1.5A/277VAC;
LPVL-150: 3.0A/115VAC
INRUSH CURRENT Blank type COLD START 60A(twidth=900s measured at 50% Ipeak) at 230VAC
(Typ.)
L type COLD START 75A(twidth=900s measured at 50% Ipeak) at 115VAC
LPV-150-48 48V 3.2A 0 ~ 3.2A 153.6W 200mVp-p
90%
MAX. No. of PSUs Blank type
on 16A CIRCUIT
BREAKER
L type
2 units (circuit breaker of type B) / 3 units (circuit breaker of type C) at 230VAC 1 units (circuit breaker of type B) / 2 units (circuit breaker of type C) at 115VAC
LEAKAGE CURRENT
LPV-150: 0.25mA / 240VAC
LPVL-150:0.25mA / 120VAC
OVERLOAD
PROTECTION OVER VOLTAGE
OVER TEMPERATURE WORKING TEMP. WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION
110 ~ 150% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
13.5 ~ 18V
17 ~ 25V
27 ~ 35V
40 ~ 49V
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
-25 ~ +65 (Refer to “Derating Curve”)
20 ~ 90% RH non-condensing
-40 ~ +80, 10 ~ 95% RH
±0.03%/ (0 ~ 40 for LPV-150-12,15 and LPVL-150-12,24;0~50 for LPV-150-24,36,48)
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
52 ~ 63V
SAFETY STANDARDS
Blank type
UL8750,CSA C22.2 No 250.13-12,UL879,CSA C22.2 No.207-M89,BIS IS15885(for LPV-150-12,24 only),EAC TP TC 004, IP67, IEC62368-1, BS EN/EN62368-1 approved
L type UL8750(type”HL”),CSA C22.2 No 250.13-12,UL879,CSA C22.2 No.207-M89,IP67 approved
SAFETY & EMC
OTHERS NOTE
WITHSTAND VOLTAGE
I/P-O/P:3KVAC
ISOLATION RESISTANCE I/P-O/P:>100M Ohms / 500VDC / 25/ 70% RH
EMC EMISSION
Blank type Compliance to BS EN/EN55032 (CISPR32) Class B, BS EN/EN61000-3-2 Class A(80% load), BS EN/EN61000-3-3, EAC TP TC 020 L type Compliance to FCC part 15
EMC IMMUNITY
Blank type Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11; BS EN/EN55035, light industry level, EAC TP TC 020 L type Design refer to IEC61000-4-2,3,4,5,6,8,11; light industry level
MTBF
3361.2K hrs min. Telcordia SR-332 (Bellcore) ; 391.9Khrs min. MIL-HDBK-217F (25)
DIMENSION
191*63*37.5mm (L*W*H)
PACKING
LPV-150: 0.74Kg;20pcs/15.8Kg/0.95CUFT; LPVL-150: 0.85Kg;20pcs/17Kg/0.95CUFT
https://www.meanwell.com/Upload/PDF/LED_EN.pdf
, https://www.meanwell.com/serviceDisclaimer.aspx
Downloaded from Arrow.com.
File Name:LPV,LPVL-150-SPEC 2023-04-14
150W Single Output Switching Power Supply
Mechanical Specification
25 AC/N(Blue) AC/L(Brown)
300±20 SJTW 18AWG
5
191 5
63 26
2-4.5
T case
tc
96
5
tc : Max. Case Temperature
5
LPV-150 series
Case No. LPC-150 Unit:mm
300±20 SJTW 14AWG
25
+V(Red) -V(Black)
37.5
3
Recommend Mounting Direction
Block Diagram
EMI FILTER
I/P
&
RECTIFIERS
O.L.P.
POWER SWITCHING
PWM CONTROL
RECTIFIERS &
FILTER
PWM fosc : 6457KHz
+V -V
DETECTION CIRCUIT O.V.P.
Derating Curve
Static Characteristics
100
LPV-150-24,36,48
80
60
LPV-150-12,15
40
LPVL-150 20
-25 -15
0
15
30
40
50
60
65 (HORIZONTAL)
AMBIENT TEMPERATURE ()
100 90 80 70 60 50 40
180 190 200 210 220 230 240 250 260 270 280 305 (Blank type)
90
100
105
120
130 132 (L type)
INPUT VOLTAGE (V) 60Hz
LOAD (%) LOAD (%)
Downloaded from Arrow.com.
File Name:LPV,LPVL-150-SPEC 2023-04-14