Accurex Model Xrv Dedicated Outdoor Air Systems User Guide

Accurex Model Xrv Dedicated Outdoor Air Systems User Guide

ACCUREX logo

Model XRV Dedicated Outdoor Air Systems
User Guide

BACnet Quick Start Guide

ACCUREX Model XRV Dedicated Outdoor Air Systems

3 – Command Unit Operation

  1. Enable Unit
  2. Control Occupancy
  3. Reset Alarms
  4. Global Alarm Notification
  5. Control Temperature Setpoint (optional)
ObjectObject NameObject DescriptionActive TextInactive Text
Variable Type
BV-2System_EnableMaster system enable/disable point.EnabledDisabled
BV-3BMS_Occupancy_CommandOccupancy CommandUnoccupiedOccupied
BV-4Reset_All_AlarmsAlarm Reset CommandResetNormal
BV-23Global_AlarmAlarm Notification (any alarm by default)AlarmNormal
AV-1Temperature_SetpointSets the active temperature set-point based on mode of operation (space setpoint, return setpoint or supply setpoint). Not applicable for outside reset.Default = 72°F
Min = 50°F; Max = 100°F

Document 485940
BACnet Integration Guide for
Dedicated Outdoor Air Systems

Reference Guide for BACnet Integration
Please read and save these instructions for future reference. The information in this guide assumes the controller was already configured with BACnet based on the original sales configuration. If the controller does not have BACnet enabled, please contact the equipment representative to get the necessary licensing and configuration files to allow BACnet communication to be used.

DOAS_08.000 Rev 2
Document Date: 01/2023

Basic Unit Integration

Below are the basic integration functions available on all equipment regardless of control mode. Some features are unit configuration dependent (heating type, cooling type, etc.). The controller’s BMS points list is static regardless of configuration to accommodate field configuration changes, however, not all points are applicable to every unit. Once the required sensors are installed in the equipment, the only mandatory requirements to make the unit operational are to enable the unit, if it hasn’t been enabled manually at the controller, and to command occupancy as desired.

ObjectVariableDescriptionActive TextInactive Text
Unit Enable/Disable Operation
If desired, the unit can be enabled and disabled by the BMS system. In disabled mode, certain safety sequences may operate to protect the building and/or equipment but general heating, cooling and ventilation operation will not function.
BV-2System_EnableMaster system enable/disable commandEnabledDisabled
Unit Occupancy Control
By default, the unit occupancy is expected to be commanded by the BMS occupancy point. Alternatively, the unit occupancy can be controlled by an internal schedule, set to always unoccupied, always occupied or controlled by a digital input by changing the occupancy mode selection at the controller.
If the controller is configured for warm-up/cool-down mode, after the occupancy command is received the unit will run in unoccupied recirculation mode until reaching the occupied temperature setpoint or the warm-up/cool down time expires (default 30 minutes) at which point the controller will enter normal occupied mode operation.
BV-3BMS_Occupancy_CommandBuilding Occupancy CommandUnoccupiedOccupied
Alarms
The following points allow the notification of any alarm and the last alarm triggered to be read, as well as active alarms that to be manually reset remotely. See the unit’s full BMS points list if specific alarm monitoring or trending is desired.
BV-4Reset_All_AlarmsAlarm Reset CommandResetNormal
BV-23Global_AlarmGlobal AlarmAlarmNormal
IV-5LatestAlmMost recent active alarmSee Alarm Table (0 = No Active Alarm)
Monitoring Unit Operation
Unit status
AV-40Unit_Status_ModeUnit Operation Mode/StateSee Status Mode Table
Fans and Dampers
BI-1Exhaust_Fan_1_Status_Digital_InputExhaust Fan 1 StatusActiveInactive
BI-2Supply_Fan_1_Status_Digital_InputSupply Fan 1 StatusActiveInactive
AV-73Exhaust_Fan_Speed_Analog_OutputExhaust Fan Speed Analog OutputReal (%)
AV-78Outside_Air_Damper_Analog_OutputOutside Air Damper Analog OutputReal (%)
AV-79Supply_Fan_Speed_Analog_OutputSupply Fan Speed Analog OutputReal (%)
Cooling
IV-11*
(Bit 20)
Cooling_is_OnIndicates that the unit is coolingActiveInactive
AV-42Cooling_1_Ramp_CapacityCooling Ramp 1 Status ValueReal (%)
Heating
IV-11*
(Bit 21)
Heating_is_OnIndicates that the unit is heatingActiveInactive
AV-51Heating_CapacityHeating RampReal (%)
Filters
IV-10*
(Bit 13)
Filter_Alarm_Digital_InputFilter Alarm Digital Input StatusAlarmNormal
ObjectVariableDescriptionActive TextInactive Text
Energy Recovery
IV-10*
(Bit 0)
Heat_Wheel_Enable_Digital_OutputHeat Wheel Enable Digital OutputActiveInactive
IV-10*
(Bit 18)
Wheel_Rotation_AlarmHeat Wheel Rotation AlarmAlarmNormal
AV-72Energy_Recovery_Analog_OutputEnergy Recovery Analog OutputReal (%)
Refrigeration Systems
IV-6*
(Bit 0)
Compressor_1_Enable_Digital_OutputCompressor 1 Enable Digital OutputActiveInactive
IV-6*
(Bit 1)
Compressor_2_Enable_Digital_OutputCompressor 2 Enable Digital OutputActiveInactive
IV-6*
(Bit 2)
Compressor_3_Enable_Digital_OutputCompressor 3 Enable Digital OutputActiveInactive
IV-6*
(Bit 3)
Compressor_4_Enable_Digital_OutputCompressor 4 Enable Digital OutputActiveInactive
AV-50HP_Ramp_CapacityHeat Pump Heating RampReal (%)
AV-53Hot_Gas_Reheat_RampHot Gas Reheat RampReal (%)
AV-80Modulating_Compressor_Analog_Output_BMSModulating Compressor Analog OutputReal (%)
Chilled Water Systems
AV-68Chilled_Water_1_Valve_Analog_OutputChilled Water 1 Valve Analog OutputReal (%)
Hot Water Systems
AV-74Hot_Water_Valve_1_Analog_OutputHot Water Valve 1 Analog OutputReal (%)
IG Furnaces
IV-6* (Bit 16)Furnace_1_Stage_1_Digital_OutputFurnace 1 Stage 1 Digital OutputActiveInactive
IV-6*
(Bit 17)
Furnace_2_Stage_1_Digital_OutputFurnace 2 Stage 1 Digital OutputActiveInactive
AV-76Mod_Gas_Furnace_1_Analog_OutputMod Gas Furnace 1 Analog OutputReal (%)
Electric Post-Heat
AV-70Electric_Heater_1_Analog_OutputElectric Heater 1 Analog OutputReal (%)
Electric Pre-Heat
IV-10*
(Bit 1)
PreHeat_Enable_Digital_OutputPreHeat Enable Digital OutputActiveInactive
Sensor Values (when equipped)
AI-1Space_Temp_Analog_InputSpace Air TemperatureReal (°F)
AI-2Supply_Temp_Analog_InputSupply(discharge) Air TemperatureReal (°F)
AI-3Outside_Air_Temp_Analog_InputOutside Air TemperatureReal (°F)
AI-4Mixed_Temp_Analog_InputMixed Air TemperatureReal (°F)
AI-5Cold_Coil_1_Temp_Analog_InputCold Coil 1 Leaving Air TemperatureReal (°F)
AI-7Return_Temp_Analog_InputReturn Air TemperatureReal (°F)
AI-8Exhaust_Temp_Analog_InputExhaust Air TemperatureReal (°F)
AI-9Space_RH_Analog_InputSpace Air Relative HumidityReal (% RH)
AI-10Outside_RH_Analog_InputOutside Air Relative HumidityReal (% RH)
AI-11Return_RH_Analog_InputReturn Air Relative HumidityReal (% RH)
AI-12Return_Duct_Static_Pressure_Analog_InputReturn Duct Static PressureReal (“wc)
AI-13Space_Static_Pressure_Analog_InputSpace Static PressureReal (“wc)
AI-14Supply_Duct_Static_Pressure_Analog_InputSupply Duct Static PressureReal (“wc)
AI-15Space_CO2_1_Analog_InputSpace 1 CO2 ppmReal (ppm)
AI-17Return_CO2_Analog_InputReturn CO2 ppmReal (ppm)
AV-64Total_Exhaust_Fan_CFM_BMSTotal Exhaust Fan CFMReal (cfm)
AV-65Total_Supply_Fan_CFM_BMSTotal Supply Fan CFMReal (cfm)
AV-66OAD_CFM_BMSOutdoor Air Damper CFMReal (cfm)
Active Setpoints
AV-41Supply_Temperature_Calculated_SetpointActive Supply Temperature SetpointReal (°F)
AV-90Coil_Temperature_Calculated_SetpointCalculated Coil Leaving Set pointReal (°F)

Unpacking Integer Words to Binary Values

Binary values can be combined to create an integer word. By doing this, more information is available to the BMS in a smaller number of points and less network traffic. These integer words need to be “unpacked” once the BMS receives the value.
To unpack the integer word into the binary values, the integer needs to be converted to a binary number. The integers in the program are 32-bit, meaning up to 32 binary values are packed into the integer. Each bit can either be a 0 (Inactive) or a 1 (Active).

The BMS front end may have a solution already intact to pull individual bits from an integer. A “read bit” function looks to return what value a certain bit is in an integer. Bit number are 0-31 in a 32-bit integer with 0 being the lowest bit and the furthest to the right in the binary notation of the number. Bit 31 would be the largest bit and the furthest to the left in binary notation.
If the front end does not have a “read bit” or “bit extract” function, the binary value of individual bits can be determined by continually dividing the quotient of the integer by 2, the remainder of the division is the value of the bit (0 or 1). A function called Modulo or “mod” is commonly used to return the remainder of integer division.

Equation: x = (round down(a/2b ) )mod 2

  • x is Boolean value for bit b, where 0 is inactive and 1 is active.
  • a is the integer word value
  • b is the bit of the binary number used as an exponent
  •  The result of a/2b should round down to a whole number, truncating the decimal. For example, 5/21 is 2.5, however, only the 2 is used.

Example:
If the Device_Offline_Word (IV-8) is a decimal value of 11, the binary value would be 1011. This binary value would mean that Space Thermostats 1, 2, and 4 are offline. The rest of the bits in the binary number would be a Boolean value of 0. (Please see Binary Tables.)

  • Bit 0 = 11/2° mod 2… this results in a Boolean of 1 or Active for bit 0.
  • Bit 1 = 11/2¹ mod 2… this results in a Boolean of 1 or Active for bit 1.
  • Bit 2 = 11/2² mod 2… this results in a Boolean of 0 or Inactive for bit 2.
  • Bit 3 = 11/2³ mod 2… this results in a Boolean of 1 or Active for bit 3.

ACCUREX Model XRV Dedicated Outdoor Air Systems - symbol 1

Modifying Equipment Operation

In addition to commanding unit occupancy, some system level sequences may require feedback from the BMS.
Common BMS adjusted sequences include items like supply air temperature reset control, demand control ventilation for multiple zones, and duct static pressure reset.

HEATING AND COOLING OPERATION SETPOINTS

ObjectVariableDescriptionActive TextInactive Text
Controller Provided Sequences – Unoccupied Mode
When the unoccupied mode of operation is set to night setback temperature, normal operation with unoccupied setpoints, or recirculation with unoccupied setpoints, the following setpoints control unoccupied heating and cooling operation. If night setback is selected as the Unoccupied Mode of operation, the reset mode will not be available to change at the controller and should be set to Space Reset(2).
IV-2Temperature_Reset_Mode_UnoccupiedCommands the reset mode during occupied operation.1 = No Reset, 2 = Space Reset 3 = Return Reset, 4 = Outside Reset
AV-3Temperature_Setpoint_UnoccupiedSets the temperature setpoint based on mode of operation (space setpoint, return setpoint or supply setpoint).
Not applicable for outside reset.
Real, Default = 70°F
*Min = 50°F; Max = 100°F
AV-4Temperature_Heat_Cool_Deadband_UnoccupiedHeat/Cool Setpt Deadband when Space or Return reset control is active. Unooc Clg Setpt = Temp Setpt Unocc + (Deadband Unocc)/2
Unocc Htg Setpt = Temp Setpt Unocc + (Deadband Unocc)/2
 

Real, Default = 20°F
*Min = 0.5°F; Max = 40°F
[Space/Return Heating = 60°F, Space/Return Cooling = 80°F]

BMS Controlled Sequences
BMS control over reset write to temp setpoint and have mode in No reset.

* Typical range for standard configuration unit, please verify at point min and max properties.

DEHUMIDIFICATION OPERATION SETPOINTS

ObjectVariableDescriptionActive TextInactive Text
Dehumidification Setpoints
The unit controller will enter occupied dehumidification mode when the dehumidification trigger(s) is met. During dehumidification mode, the cooling system is controlled to maintain the cooling coil leaving air temperature setpoint while the hot gas reheat system (if installed) reheats the air to maintain the active supply air temperature setpoint. For units with space or return humidity sensors, the controller may also actively reset the cooling coil temperature setpoint between minimum and maximum values to maintain the target space/return dehumidification setpoint (% RH).
Note: By default, unoccupied dehumidification mode is not active unless a trigger to enter the mode is selected at the unit controller since most spaces do not have an unoccupied dehumidification load.
AV-5Cooling_Coil_Setpoint_MinPrimary Cooling Coil Leaving Air SetpointDefault = 50°F
*Min = 46°F; Max = 80°F
AV-6Cooling_Coil_Setpoint_MaxMaximum Coil Leaving Setpoint if cooling coil rest strategy is used.Default = 55°F
*Min = 46°F; Max = 80°F
AV-7Dehumidification_SetpointDehumidification Setpoint. %RH for Space or Return controlDefault = 55% RH
Min = 0%; Max = 100%
AV-11Unoccupied_Dehumidification_SetpointUnoccupied Dehumidification %RH SetpointDefault =60% RH
Min = 0%; Max = 100%

* Typical range for standard configuration unit, please verify at point min and max properties.

AIRFLOW OPERATION SETPOINTS

ObjectVariableDescriptionActive TextInactive Text
Airflow Setpoints
Airflow operation of supply fan, exhaust fan, and mixing dampers may use setpoints from duct pressure, space pressure, CO2 sensors, or airflow measuring stations to properly control airflow in an application. The Outside Air Damper Minimum Setpoint Occupied applies to all units with modulating outside air dampers. The setpoint is used to establish an absolute minimum position for ventilating the space while allowing other control modes to open the damper further as necessary. Outdoor and recirculating air dampers operate inversely using the same signal.
AV-14Supply_Fan_CFM_SetpointSupply Fan CFM SetpointDefault = Job Specified CFM
Min = 0 cfm; Max = 999,999 cfm
AV-15Exhaust_Fan_CFM_SetpointExhaust Fan CFM SetpointDefault = Job Specified CFM Min = 0 cfm; Max = 999,999 cfm
AV-16OAD_CFM_SetpointOAD CFM SetpointDefault = Job Specified CFM
Min = 0 cfm; Max = 999,999 cfm
AV-21Return_Duct_Static_Pressure_SetpointReturn Duct Static Pressure SetpointDefault = -2.0”wc
Min = 0.0”wc; Max = -5.0”wc
AV-22Space_Static_Pressure_SetpointSpace Static Pressure SetpointDefault = 0.05”wc
Min = -0.5”wc; Max = 0.5”wc
AV-23Supply_Duct_Static_Pressure_SetpointSupply Duct Static Pressure SetpointDefault = 1.0”wc

Min = 0.0”wc; Max = 5.0”wc

AV-24Space_CO2_SetpointSpace CO2 SetpointDefault = 1,000 ppm
Min = 0 ppm; Max = 5,000 ppm
AV-25Outside_Air_Damper_Minimum_Setpoint_OccOutside Air Damper Minimum Setpoint OccupiedDefault = 35%
Min = 0%; Max = 100%

BMS Watchdog Enabled Control

BMS WATCHDOG
When directly commanding fans speeds, damper positions, or sending sensor values, the unit controller requires the BMS Watchdog point to be written to on a recurring basis. This tells the unit controller that the BMS is still actively communicating.

ObjectVariableDescriptionActive TextInactive Text
BMS Watchdog
The BMS Watchdog must be written to True (1) regularly to verify communication is established between the unit controller and the BMS headend system. If the BMS Watchdog value remains False(0) for longer than the Timeout Delay (15 minutes, adjustable), an alarm is generated and the controller falls back to local control and sensor values, as applicable, instead of using BMS commanded values.
BV-1BMS_WatchdogBMS Watchdog commandActiveInactive
BV-24BMS_Watchdog_ActiveStatus of the BMS watchdog ping.ActiveInactive

CONTROLLING AIRFLOW DEVICES
If desired, the speeds and positions of airflow devices can be controlled directly using BACnet commandable points. To control the devices via the BMS, the BMS Watchdog requirements must be satisfied.

ObjectVariableDescriptionActive TextInactive Text
Fan Controls
Fan speeds can be controlled directly though BMS points. The binary points enable the BMS to take control and the analog values command the speeds as a percentage between the allowed minimum and maximum values set in the controller.
Supply Fan
BV-17SF_Control_Source_BMSAllows the BMS to control supply fan speedBMSLocal
AV-36SF_Control_Signal_BMSSupply Fan Command SpeedReal (%)
*Min=50%; Max=100%
Exhaust Fan
BV-18EF_Control_Source_BMSAllows the BMS to control exhaust fan speedBMSLocal
AV-37EF_Control_Signal_BMSExhaust Fan Command SpeedReal (%)
Min=25%; Max=100%
Outdoor Air/Recirculation Air Damper Control
The outdoor air damper position can be controlled directly by the BMS to adjust the mixture of outdoor air and recirculation air on units configured for recirculation. Minimum and maximum values for occupied and unoccupied mode set at the unit controller are enforced.
BV-19OAD_Control_Source_BMSAllows the BMS to control OAD positionBMSLocal
AV-38OAD_Control_Signal_BMSOutside Air Damper Control Signal via BMSReal (%)
Min=0%; Max=100%

* Typical range for standard configuration unit, please verify at point min and max properties.

SENDING SENSOR VALUES
Sensor values required for sequence operation can be sent to the controller over dedicated BMS points in place of a sensor wired to the controller (local sensor). When values are communicated to the controller over BMS, the BMS Watchdog must be satisfied. If the watchdog isn’t satisfied, the controller reverts to the local sensor (if installed and
valid) to control the unit or falls back to local control until the BMS watchdog is satisfied.

ObjectVariableDescriptionActive TextInactive Text
BMS Writeable Sensor Values
To write the sensor values over BMS, first command the controller to use the BMS value using the corresponding binary value and then use the corresponding analog value to send the sensor value.
Sensor Sources
BV-7Outside_RH_Source_BMSOutside RH Source SelectionBMSLocal
BV-8Outside_Temp_Source_BMSOutside Temp Source SelectionBMSLocal
BV-9Return_RH_Source_BMSReturn RH Source SelectionBMSLocal
BV-10Return_Temp_Source_BMSReturn Temp Source SelectionBMSLocal
BV-11Space_1_CO2_Source_BMSSpace 1 CO2 Source SelectionBMSLocal
BV-12Space_2_CO2_Source_BMSSpace 2 CO2 Source SelectionBMSLocal
BV-13Return_CO2_Source_BMSReturn CO2 Source SelectionBMSLocal
BV-14Space_RH_Source_BMSSpace RH Source SelectionBMSLocal
BV-15Space_Static_Source_BMSSpace Static Source SelectionBMSLocal
BV-16Space_Temp_Source_BMSSpace Temp Source SelectionBMSLocal
ObjectVariableDescriptionActive Text          Inactive Text
Sensor Values
AV-26Outside_RH_from_BMSOutside RH from BMS.Real (% RH)
AV-27Outside_Temp_from_BMSOutside Temp from BMSReal (°F)
AV-28Return_RH_from_BMSReturn RH from BMSReal (% RH)
AV-29Return_Temp_from_BMSReturn Temp from BMSReal (°F)
AV-30Space_1_CO2_from_BMSSpace 1 CO2 from BMSReal (ppm)
AV-31Space_2_CO2_from_BMSSpace 2 CO2 from BMSReal (ppm)
AV-32Return_CO2_from_BMSReturn CO2 from BMSReal (ppm)
AV-33Space_RH_from_BMSSpace RH from BMSReal (% RH)
AV-34Space_Static_from_BMSSpace Static from BMSReal (“wc)
AV-35Space_Temp_from_BMSSpace Temp from BMSReal (°F)

Advanced BACnet Settings

ACCUREX Model XRV Dedicated Outdoor Air Systems - symbol 2

Additional settings can be accessed in the BACnet Advanced Settings menu including BACnet Broadcast Management Device (BBMD) configuration, relinquish default settings, Change of Value (COV) increments and restoring binary text values.

BBMD CONFIGURATION

ACCUREX Model XRV Dedicated Outdoor Air Systems - symbol 3

To configure the controller to operate with a BACnet Broadcast Management Device (BBMD) on IP networks, go to the advanced BACnet settings menu and enter the IP address of the BBMD, foreign device configuration, and time to live settings.

COV INCREMENTS

ACCUREX Model XRV Dedicated Outdoor Air Systems - symbol 4

BACnet COV is an optional portion of BACnet that supports providing new values/information only after an increase or decrease of the value is at least the listed COV increment. The controller’s COV increments are based on the unit of measure. All variables with the same unit of measure share the same COV increment value. Values can be adjusted on this screen, or by writing to the COV increment property of any BACnet object.

RELINQUISH DEFAULT SETTINGS

ACCUREX Model XRV Dedicated Outdoor Air Systems - symbol 5

When the Return to Default function is enabled, the present value will not overwrite the relinquish default value and on a loss of power the controller will boot with last saved default values instead of last written values. This must also be enabled for the BACnet Comm Loss relinquish default to work.

ACCUREX Model XRV Dedicated Outdoor Air Systems - symbol 6

When the Enable Relinquish Default function is enabled any value in the priority array for binary values or analog values will be cleared if a communication loss is detected.
All commandable points will revert to the relinquish default value.
Communication loss is determined based on the BMS Watchdog. The watchdog function must be enabled. The function will execute 5 minutes after the watchdog status goes inactive.

ACCUREX Model XRV Dedicated Outdoor Air Systems - symbol 7

This may be desired if the BMS is running a reset routine on the setpoints and would like to revert to a default state if communication is lost. It is recommended to be used with return to default enabled, and a known relinquish default is saved.
When this box is checked by a user, the controller will write the present value of variables to the relinquish default for all binary and analog value BACnet objects that are commandable. The function operates in the background and takes approximately 30 seconds to complete.
This is desired to save any Test and Balance settings adjusted locally on the controller to be the BACnet relinquish default values. Alternatively, these values could be read and written to the relinquish default variables by the BMS system.

BINARY TEXT

ACCUREX Model XRV Dedicated Outdoor Air Systems - symbol 8

If for any reason, the state text is missing from binary objects, checking this box will cause the controller to re-write the active and inactive text values.

DOAS Reference Tables

STATUS MODE TABLE
The following analog values can appear in the point to tell the building automation the current mode of operation of the unit. Values may rotate every three seconds.

Status Mode Table (AV-40)
Analog ValueModeAnalog ValueModeAnalog ValueMode
0Off/Standby12System Disabled23Dehumidifying
1Unoccupied Start13Remote Off25Hot Gas Reheat Purging
2Occupied Start14System Shutdown Alarm26Energy Recovery Defrost Active
3Opening Dampers15Pressurization Only29Dehumidifying with Heat
5Dampers Open16Exhaust Only30Manual Overrides Active
6Fan Start Delay17Fan Only Purge31Expansion Board Offline
7Exhaust Fan Start18Case Heat Active33Energy Recovery Active
8Supply Fan Start19Fans Only34Hot Gas Reheat Active
9Heat/Cool Startup Delay20Economizing35Morning Occupancy Sequence
10System On21Cooling36Heat Pump Defrost Active
11Soft Shutdown22Heating

ALARM TABLE
This table displays the latest alarm that is active in the unit controller.

Alarm Table – Latest Alarm (IV-5)
0No Active Alarms94Sens S1 EVD 1 – Sensor Value Not Valid
1Supply Fan 1 Run – Status Not Proven95Sens S2 EVD 1 – Sensor Value Not Valid
2Freeze Protection – Thermostat Tripped96Sens S3 EVD 1 – Sensor Value Not Valid
3High Supply Duct – Static Pressure97Sens S4 EVD 1 – Sensor Value Not Valid
4Low Return Duct – Static Pressure98EVD 1 EEPROM Damaged – Call Tech Support
5Outside Air Temp – Sensor Value Not Valid99Incomplete Closing – EVD 1
6Supply Air Temperature – Sensor Value Not Valid100Emergency Closing – EVD 1
7Cold Coil 1 Temp – Sensor Value Not Valid101EVD 1 Battery –
9Exhaust Air Temp – Sensor Value Not Valid102FW Incompatibility – EVD 1
10Mixed Air Temperature – Sensor Value Not Valid103EVD 1 Config Error –
11Return Air Temperature – Sensor Value Not Valid104EVD 1 Comm – EVD 1 is Offline
12Space Temperature – Sensor Value Not Valid105High Discharge Temp – First Inverter
13Return Air RH – Sensor Value Not Valid106Low Discharge Pressure – First Inverter
14Space RH – Sensor Value Not Valid107High Suction Pressure – First Inverter
15Outside RH – Sensor Value Not Valid108Low Suction Pressure – First Inverter
16Low Pressure Switch – Circuit A109High Current – First Inverter
17Low Pressure Switch – Circuit B110High Pressure Ratio – First Inverter
20High Pressure Switch – Circuit A111Low Pressure Ratio – First Inverter
21High Pressure Switch – Circuit B112Low Delta P – First Inverter
24Damper End Switch Fail – Dampers are not open113High Discharge Press – First Inverter
25Exhaust Fan 1 Run – Status Not Proven114Compressor Staging – Order Skipped
26Filters are Dirty – Replace Filters115Heat Pump Heating – Locked Out
27Cond Drain Pan Full – Check Drain116EVD 1 Error – Unexpected Position
28Exp Board 1 Status – Board is Offline117High SDT Lockout – Circuit A
29Exp Board 2 Status – Board is Offline118High SDT Lockout – Circuit B
31Exp Board 4 Status – Board is Offline121Inverter 1 Alarm –
32Non-Volatile Memory Er – Contact Tech Support123Inverter 1 Lockout – Cycle Power to Unit
33Space 1 CO2  – Sensor Value Not Valid125Inverter 1 Foldback – Output Current
34Space Static Pressure – Sensor Value Not Valid126Inverter 1 Foldback – Input Current
35Supply Duct Stat Press – Sensor Value Not Valid127Inverter 1 Foldback – Inverter Temp
36Return Duct Stat Press – Sensor Value Not Valid131Inverter 1 Comms Lost – Compressor Offline
37Supply Fan AFMS – Sensor Value Not Valid133Space Thermostat 1 – Sensor Offline
38Exhaust Fan AFMS – Sensor Value Not Valid134Space Thermostat 2 – Sensor Offline
39Outside Damper AFMS – Sensor Value Not Valid135Space Thermostat 3 – Sensor Offline
40Space Setpt Adj Slider – Sensor Value Not Valid136Space Thermostat 4 – Sensor Offline
41Space 2 CO2 – Sensor Value Not Valid137IG Furnace 1. No flame – after 3 tries
42Return CO2 – Sensor Value Not Valid138IG Furnace 1 Large – no flame after 3 tries
43Discharge Press Ckt A – Sensor Value Not Valid139IG Furnace 1 combust – fan high pressure switch
44Discharge Press Ckt B – Sensor Value Not Valid140IG Furnace 1 Ignition – controller alarm
47Suction Press Ckt A – Sensor Value Not Valid141IG Furnace 1 pressure – switch fault alarm
48Suction Press Ckt B – Sensor Value Not Valid142IG Furnace 1 combust – fan proving alarm
51Discharge Temp Ckt A – Sensor Value Not Valid143IG Furnace 1 – Max Retries
52Discharge Temp Ckt B – Sensor Value Not Valid144IG Furnace 1 – High Limit Trip
55Suction Temp Ckt A – Sensor Value Not Valid145IG Furnace – pCOe 1 Offline
56Suction Temp Ckt B – Sensor Value Not Valid146IG Furnace 1 IC fault – Check Furnace Wiring
59Ckt A High Saturated – Discharge Temperature147IG Furnace 2 No flame – after 3 tries
60Ckt B High Saturated – Discharge Temperature148IG Furnace 2 Large – no flame after 3 tries
63Supply Air Temperature – Low Limit Shutdown149IG Furnace 2 combust – fan high pressure switch
64Heat Wheel Rotation – Not Detected150IG Furnace 2 Ignition – controller alarm
65Slave Unit 1 Offline –151IG Furnace 2 pressure – switch fault alarm
66Slave Unit 2 Offline –152IG Furnace 2 combust – fan proving alarm
67Slave Unit 3 Offline –153IG Furnace 2 – Max retries
68Slave Unit 4 Offline –154IG Furnace 2 – High Limit Trip
69Master Unit Offline –155IG Furnace – pCOe 2 Offline
70Heat Pump Defrost – Mode is Active156IG Furnace 2 IC fault – Check Furnace Wiring
71Multi Devices per Ch – Contact Tech Support157Outside Air GreenTrol  – Offline or Flow Error
74Shutdown Contact – In Alarm Position158Exhaust Air GreenTrol – Offline or Flow Error
75Comp Maintenance Alarm – Run Hours Setpt Reached159Supply Air GreenTrol – Offline or Flow Error
76Supply Air Temperature – High Limit Shutdown169ER Wheel High – Differential Pressure
77Space High Static Pres – Shutdown170OA Damper Fault – Not Econ and should be
78Internal Board Temp – Exceeds -40F or 158F171OA Damper Fault – Econ and shouldn’t be
79BMS Offline – Watchdog is FALSE172OAD Fault – Damper not Modulating
80Cooling Coil Setpt Input – Value is not valid173OAD Fault – Excess Outdoor Air
81Sup Air Setpt Input – Value is not valid174IG Furnace 1 – Combustion Fan Alarm
82BACnet License – Not Installed175IG Furnace 2 – Combustion Fan Alarm
83Low Suction SH ExV A – EVD 1 Alarm176Supply Fan – VFD Offline
84Low Suction SH ExV B – EVD 1 Alarm177Exhaust Fan – VFD Offline
85LOP A EVD 1 – Low Operating Pressure178Return Fan – VFD Offline
87MOP A EVD 1 – Max Operating Pressure179Energy Recovery – VFD Offline
89EEV A EVD 1 – Motor Alarm180Embedded EVD Error
91Low Suction A EVD 1 – Refrigerant Temp181SF VFD Alarm – Check VFD
93High Condensing Temp – EVD 1

BIT-PACKED INTEGER WORD TABLES
The following tables are used to unpack integer words into Boolean values.

Device Enable DO Word Table (IV-6)
BitDevice_Enable_DO_WordBitDevice_Enable_DO_WordBitDevice_Enable_DO_Word
0Compressor 1 Start1122
1Compressor 2 Start12Condenser Fan Ramp 2 Stage 1 Start23
2Compressor 3 Start13Condenser Fan Ramp 2 Stage 2 Start24
3Compressor 4 Start14Condenser Fan Ramp 2 Stage 3 Start25
41526
516Furnace 1 Start27
617Furnace 2 Start28
71829
8Condenser Fan Ramp 1 Stage 1 Start1930
9Condenser Fan Ramp 1 Stage 2 Start20Supply Fan Start31
10Condenser Fan Ramp 1 Stage 3 Start21Exhaust Fan Start
Refrigeration Circuit Word Table (IV-7)
BitRef_Ckt_PressTemp_Alarm_WordBitRef_Ckt_PressTemp_Alarm_WordBitRef_Ckt_PressTemp_Alarm_Word
0Circuit A Discharge Pressure Sensor Alarm11Circuit B Low-Pressure Switch Alarm22
1Circuit A Discharge Temp Sensor Alarm12Circuit A High Sat Discharge Temp Alarm23
2Circuit A Suction Pressure Sensor Alarm13Circuit B High Sat Discharge Temp Alarm24
3Circuit A Suction Temp Sensor Alarm1425
4Circuit B Discharge Pressure Sensor Alarm1526
5Circuit B Discharge Temp Sensor Alarm1627
6Circuit B Suction Pressure Sensor Alarm1728
7Circuit B Suction Temp Sensor Alarm1829
8Circuit A High-Pressure Switch Alarm1930
9Circuit A Low-Pressure Switch Alarm2031
10Circuit B High-Pressure Switch Alarm21
Device Offline Word Table (IV-8)
BitDevice_Offline_WordBitDevice_Offline_WordBitDevice_Offline_Word
0Space T-Stat 1 Offline11Expansion Board 4 Alarm22
1Space T-Stat 2 Offline1223
2Space T-Stat 3 Offline1324
3Space T-Stat 4 Offline1425
4VFD Offline Supply Fan1526
51627Master Unit Offline Alarm
61728Slave Unit 1 Offline Alarm
71829Slave Unit 2 Offline Alarm
8Expansion Board 1 Alarm1930Slave Unit 3 Offline Alarm
9Expansion Board 2 Alarm2031Slave Unit 4 Offline Alarm
10Expansion Board 3 Alarm21
Device Alarm Word Table (IV-9)
BitDevice_Alarm_WordBitDevice_Alarm_WordBitDevice_Alarm_Word
0Cold Coil Temperature Sensor Alarm11GreenTrol OAD AFMS Alarm22Inverter Scroll 1 Alarm
112Return CO2 Sensor Alarm23
2Mixed Temperature Sensor Alarm13Return Duct Static Pressure Sensor Alarm24EVD Valve A Alarm
3Supply Duct Static Pressure Sensor Alarm14Return Temperature Sensor Alarm25
4Supply Fan AFMS Alarm15Return RH Sensor Alarm26SF VFD Alarm
5Supply Air Temp Sensor Alarm16Space CO2 Sensor Alarm27
6Exhaust Fan AFMS Alarm17Space RH Sensor Alarm28
7Exhaust Temperature Sensor Alarm18Space Static Pressure Sensor Alarm29
8Outside Air Temp Sensor Alarm19Space Temperature Sensor Alarm30
9Outside RH Sensor Alarm20IG Furnace Alarm31
10OAD AMD Alarm21
System Word Table (IV-10)
BitSystem_WordBitSystem_WordBitSystem_Word
0Heat Wheel Enable11Drain Pan Alarm22BMS Offline Alarm
1Preheat Enable12Freeze Stat Alarm23
2Reversing Valve (Cooling (0)/Heating(1))13Filter Alarm24
314Space High Static Alarm25
415Return Low Static Alarm26
516Shutdown Input Alarm27
6Supply Temp Low Limit Alarm17Energy Recovery Wheel High Diff Pressure28Heat-Cool Only – Dehumidification Request Active
7Supply Temp High Limit Alarm18Energy Recovery Wheel Rotation Alarm29Heat-Cool Only – Heating Request Active
8Supply High Duct Static Alarm1930Heat-Cool Only – Coil Setpoint Alarm Active
9Supply Fan 1 Alarm20Heat Pump Heating Lock Out Alarm31Heat-Cool Only – Supply Setpoint Alarm
Active
10Exhaust Fan 1 Alarm21Permanent Memory – Too Many Writes
Unit Status Word Table (IV-11)
BitUnit_Status_WordBitUnit_Status_WordBitUnit_Status_Word
0Off/Standby11Remote Off22Dehumidifying
1Unoccupied Start12System Shutdown Alarm23Hot Gas Reheat Active
2Occupied Start13Supply Fan Only24HGRH Purging
3Opening Dampers14Exhaust Fan Only25Dehum w/Heat
4Dampers Open15Purge Mode (Supply and Exhaust Only)26Energy Recovery Defrost Active
5Fan Start Delay16Case Heat Active27Heat Pump Defrost Active
6Exhaust Fan On17Fans Only28Morning Warm Up/Cool Down Active
7Supply Fan On18Economizing29Winter Ramp Active
8System On19Energy Recovery Active30
9Soft Shutdown20Cooling31Overrides Active
10System Disabled21Heating

ACCUREX logo

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals