Accurex Xdgx Make Up Air Direct Gas User Guide

Accurex Xdgx Make Up Air Direct Gas User Guide

ACCUREX XDGX Make up Air Direct Gas User Guide
ACCUREX XDGX Make up Air Direct Gas

Wire Network Connection

Network Connection

Ethernet Port Lights
Ethernet Port Lights

Adjust BACnet Network Settings
Network Settings

Command Unit Operation
  1. Enable Unit
    Control Occupancy
  2. Reset Alarms
  3. Global Alarm Notification
  4. Control Temperature Setpoint (optional)
ObjectObject NameObject DescriptionActive TextInactive Text
Variable Type
BV-2System_EnableMaster system enable/disable point.EnabledDisabled
BV-3BMS_Occupancy_CommandOccupancy CommandUnoccupiedOccupied
BV-4Reset_All_AlarmsAlarm Reset CommandResetNormal
BV-19Global_AlarmAlarm Notification (any alarm by default)AlarmNormal
AV-1Temperature_SetpointSets the active temperature set-point based on mode of operation (space setpoint, return setpoint or supplysetpoint). Not applicable for outside reset.Default = 72°FMin = 50°F; Max = 100°F

Reference Guide for BACnet Integration
Please read and save these instructions for future reference. The information in this guide assumes the controller was already configured with BACnet based on the original sales configuration. If the controller does not have BACnet enabled, please contact the equipment representative to get the neces sary licensing and configuration files to allow BACnet communicationto be used.

MUA_01.001 Rev 2
Document Date: 01/2023

Basic Unit Integration

Below are the basic integration functions available on all equipment regardless of control mode. Some features are unit configuration dependent (heating type, cooling type, etc.). The controller’s BMS points list is static regardless of configuration to accommodate field configuration changes, however, not all points are applicable every unit. Once the required sensors are installed in the equipment, the only mandatory requirements to make the unit operational are to enable the unit, if it hasn’t been enabled manually at the controller, and to command occupancy as desired.

 ObjectVariableDescriptionActive TextInactive Text
Unit Enable/Disable Operation
If desired, the unit can be enabled and disabled by the BMS system. In disabled mode, certain safety sequences may operate to protect thebuilding and/or equipment but general heating, cooling and ventilation operation will not function.
BV-2System_EnableMaster system enable/disable commandEnabledDisabled
Unit Occupancy Control
By default, the unit occupancy is expected to be commanded by the BMS occupancy point. Alternatively, the unit occupancy can be controlled by an internal schedule, set to always unoccupied, always occupied or controlled by a digital input by changing the occupancy mode selection at the controller. If the controller is configured for warm-up/cool-down mode, after the occupancy command is received the unit will run in unoccupied recirculation mode until reaching the occupied temperature setpoint or the warm-up/cool down time expires (default 30 minutes)at which point the controller will enter normal occupied mode operation.
BV-3BMS_Occupancy_CommandBuilding Occupancy CommandUnoccupiedOccupied
Alarms
The following points allow the notification of any alarm and the last alarm triggered to be read, as well as active alarms that to be manuallyreset remotely. See the unit’s full BMS points list if specific alarm monitoring or trending is desired.
BV-4Reset_All_AlarmsAlarm Reset CommandResetNormal
BV-19Global_AlarmGlobal AlarmAlarmNormal
IV-9LatestAlmMost recent active alarmSee Alarm Table(0 = No Active Alarm)
Monitoring Unit Operation
Unit status
AV-41Unit_Status_ModeUnit Operation Mode/StateSee Status Mode Table
Fans and Dampers
BI-1Exhaust_Fan_1_Status_Digital_InputExhaust Fan 1 StatusActiveInactive
BI-2Supply_Fan_1_Status_Digital_InputSupply Fan 1 StatusActiveInactive
AV-62Outside_Airflow_MaskPercentage of Outside AirflowReal (%)
AV-63Supply_Fan_Speed_Analog_OutputSupply Fan Speed Analog OutputReal (%)
Cooling
IV-15*(Bit 20)Cooling_is_OnIndicates that the unit is coolingActiveInactive
AV-43Cooling_1_Ramp_CapacityCooling Ramp 1 Status ValueReal (%)
Heating
IV-15*(Bit 21)Heating_is_OnIndicates that the unit is heatingActiveInactive
AV-46Heating_CapacityHeating RampReal (%)
Filters
IV-13*(Bit 3)Filter_Alarm_Digital_InputFilter Alarm Digital Input StatusAlarmNormal
Refrigeration Systems
IV-10*(Bit 3)Compressor_1_Enable_Digital_OutputCompressor 1 Enable Digital OutputActiveInactive
IV-10*(Bit 4)Compressor_2_Enable_Digital_OutputCompressor 2 Enable Digital OutputActiveInactive
AV-64Modulating_Compressor_Analog_Output_BMSModulating Compressor Analog OutputReal (%)
ObjectVariableDescriptionActive TextInactive Text
Chilled Water Systems
AV-58Chilled_Water_1_Valve_Analog_OutputChilled Water 1 Valve Analog OutputReal (%)
Evaporative Cooling Systems
IV-10*(Bit 16)Evap_Valve_Enable_Digit_OutputEvaporative Cooling Valve EnableActiveInactive
IV-10*(Bit 17)Evap_Pump_Enable_Digit_OutputEvaporative Cooling Pump EnableActiveInactive
Hot Water Systems
AV-60Hot_Water_Valve_1_Analog_OutputHot Water Valve 1 Analog OutputReal (%)
IG Furnaces
IV-10*(Bit 7)Furnace_1_Stage_1_Digital_OutputFurnace 1 Stage 1 Digital OutputActiveInactive
IV-10*(Bit 8)Furnace_1_Stage_2_Digital_OutputFurnace 1 Stage 2 Digital OutputActiveInactive
IV-10*(Bit 9)Furnace_2_Stage_1_Digital_OutputFurnace 2 Stage 1 Digital OutputActiveInactive
IV-10*(Bit 10)Furnace_2_Stage_2_Digital_OutputFurnace 2 Stage 2 Digital OutputActiveInactive
IV-10* (Bit 11)Furnace_3_Stage_1_Digital_OutputFurnace 3 Stage 1 Digital OutputActiveInactive
AV-61Mod_Gas_Furnace_1_Analog_OutputMod Gas Furnace 1 Analog OutputReal (%)
Electric Post-Heat
IV-10* (Bit 15)Electric_Heater_Start_Stop_Digital_OutputElectric Heater Digital Output
AV-59Electric_Heater_1_Analog_OutputElectric Heater 1 Analog OutputReal (%)
Direct Gas Burner
IV-10* (Bit 14)Direct_Gas_Heating_Enable_Digital_OutputDirect Gas Enable Digital OutputActiveInactive
Sensor Values (when equipped)
AI-1Space_Temp_Analog_InputSpace Air TemperatureReal (°F)
AI-2Supply_Temp_Analog_InputSupply(discharge) Air TemperatureReal (°F)
AI-3Outside_Air_Temp_Analog_InputOutside Air TemperatureReal (°F)
AI-9Space_Static_Pressure_Analog_InputSpace Static PressureReal (“wc)
AI-10Supply_Duct_Static_Pressure_Analog_InputSupply Duct Static PressureReal (“wc)
AI-11Space_CO2_1_Analog_InputSpace 1 CO2 ppmReal (ppm)
AI-12Return_CO2_Analog_InputReturn CO2 ppmReal (ppm)
AV-56OAD_CFM_BMSOutdoor Air Damper CFMReal (cfm)
Active Setpoints
AV-42Supply_Temperature_Calculated_SetpointActive Supply Temperature SetpointReal (°F) 

Unpacking Integer Words to Binary Values

Binary values can be combined to create an integer word. By doing this, more information is available to the BMS in a smaller number of points and less network traffic. These integer words need to be “unpacked” once the BMS receives the value.

Object                                 Variable                                                           Description                                              Reference Table
Packed Integer Words
IV-10Digital_Output_WordDigital Output EnablesBit Packed Word – See Binary Tables
IV-11Cooling_Alarm_WordCooling Device AlarmsBit Packed Word – See Binary Tables
IV-12Device_Offline_WordDevice Communication AlarmsBit Packed Word – See Binary Tables
IV-13Device_Alarm_WordDevice AlarmsBit Packed Word – See Binary Tables
IV-14Heating_Alarm_WordHeating Device AlarmsBit Packed Word – See Binary Tables
IV-15Unit_Status_WordUnit Status WordBit Packed Word – See Binary Tables

To unpack the integer word into the binary values, the integer needs to be converted to a binary number. The integers in the program are 32-bit, meaning up to 32 binary values are packed into the integer. Each bit can either be a 0 (Inactive) or a 1 (Active).

The BMS front end may have a solution already intact to pull individual bits from an integer. A “read bit” function looks to return what value a certain bit is in an integer. Bit number are 0-31 in a 32-bit integer with 0 being the lowest bit and the furthest to the right in the binary notation of the number. Bit 31 would be the largest bit and the furthest to the left in binary notation.

If the front end does not have a “read bit” or “bit extract” function, the binary value of individual bits can be determined by continually dividing the quotient of the integer by 2, the remainder of the division is the value of the bit (0 or 1). A function called Modulo or “mod” and is commonly used to return the remainder of integer division.

Equation: x = (round down(a/2b ) )mod 2

  • x is Boolean value for bit b, where 0 is inactive and 1 is active.
  • a is the integer word value
  • b is the bit of the binary number used as an exponent
  • The result of a/2b should round down to a whole number, truncating the decimal. For example, 5/21 is 2.5, however, only the 2 is used.

Example:
If the Device_Offline_Word (IV-12) is a decimal value of 11, the binary value would be 1011. This binary value would mean that Space Thermostats 1, 2, and 4 are offline. The rest of the bits in the binary number would be a Boolean value of 0. (Please see Binary Tables.)

  • Bit 0 = 11/20 mod 2… this results in a Boolean of 1 or Active for bit 0.
  • Bit 1 = 11/21 mod 2… this results in a Boolean of 1 or Active for bit 1.
  • Bit 2 = 11/22 mod 2… this results in a Boolean of 0 or Inactive for bit 2.
  • Bit 3 = 11/23 mod 2… this results in a Boolean of 1 or Active for bit 3.
Bit313029282726252423222120191817161514131211109876543210
Val00000000000000000000000000001011

Modifying Equipment Operation

In addition to commanding unit occupancy, some system level sequences may require feedback from the BMS. Common BMS adjusted sequences include items like supply air temperature reset control, demand control ventilation for multiple zones, and duct static pressure reset.

HEATING AND COOLING OPERATION SETPOINTS
 ObjectVariableDescriptionActive TextInactive Text
Adjusting Temperature Setpoints
Controller Provided Sequences – Occupied Mode
The controller has several stand-alone supply air temperature control modes with setpoints that can be modified by the BMS. These modes include a static supply air temperature setpoint (no-reset) or allows for the supply air temperature setpoint to be reset based on outside air temperature, spacetemperature, or return air temperature.
IV-1Temperature_Reset_ModeCommands the reset mode during occupiedoperation.1 = No Reset, 2 = Space Reset3 = Return Reset, 4 = Outside Reset
 AV-1 Temperature_SetpointSets the temperature setpoint based on mode of operation (space setpoint, return setpoint or supply setpoint).Not applicable for outside reset. Real, Default = 72°F*Min = 50°F; Max = 120°F
 AV-2 Temperature_Heat_Cool_DeadbandHeat/Cool Setpt Deadband when Space or Return reset control is active.Htg Setpt = Temp Setpt – Deadband /2 Clg Setpt = Temp Setpt – Deadband /2Real, Default = 4°F Min = 0.1°F; Max = 20°F[Space/Return Heating = 70°F, Space/Return Cooling = 74°F]
Controller Provided Sequences – Unoccupied Mode
When the unoccupied mode of operation is set to night setback temperature, normal operation with unoccupied setpoints, or recirculation withunoccupied setpoints, the following setpoints control unoccupied heating and cooling operation. If night setback is selected as the Unoccupied Mode of operation, the reset mode will not be available to change at the controller and should be set to Space Reset(2).
IV-2Temperature_Reset_Mode_UnoccupiedCommands the reset mode during occupiedoperation.1 = No Reset, 2 = Space Reset3 = Return Reset, 4 = Outside Reset
 AV-3 Temperature_Setpoint_UnoccupiedSets the temperature setpoint based on mode of operation (space setpoint, return setpoint or supply setpoint).Not applicable for outside reset. Real, Default = 72.5°F*Min = 50°F; Max = 120°F
ObjectVariableDescriptionActive Text Inactive Text
 AV-4 Temperature_Heat_Cool_Deadband_UnoccupiedHeat/Cool Setpt Deadband when Space or Return reset control is active.Unooc Clg Setpt = Deadband /2 + Temp Setpt Unocc Htg Setpt = Deadband /2 – Temp SetptReal, Default = 15°F Min = 0.1°F; Max = 40°F[Space/Return Heating = 65°F, Space/Return Cooling = 80°F]
BMS Controlled Sequences
BMS control over reset write to temp setpoint and have mode in No reset. 

AIRFLOW OPERATION SETPOINTS

ObjectVariableDescriptionActive TextInactive Text
Airflow Setpoints
Airflow operation of supply fan, exhaust fan, and mixing dampers may use setpoints from duct pressure, space pressure, CO2 sensors, or airflow measuring stations to properly control airflow in an application. The Outside Air Damper Minimum Setpoint Occupied applies to all units withmodulating outside air dampers. The setpoint is used to establish an absolute minimum position for ventilating the space while allowing other control modes to open the damper further as necessary. Outdoor and recirculating air dampers operate inversely using the same signal.
AV-16Space_Static_Pressure_SetpointSpace Static Pressure SetpointDefault = 0.05”wcMin = -0.5”wc; Max = 0.5”wc
AV-17Supply_Duct_Static_Pressure_SetpointSupply Duct Static Pressure SetpointDefault = 1.0”wcMin = 0”wc; Max = 5”wc
AV-18Space_CO2_SetpointSpace CO2 SetpointDefault = 1,000 ppmMin = 0 ppm; Max = 5,000 ppm
AV-19Outside_Air_Damper_Minimum_Setpoint_OccOutside Air Damper Minimum Setpoint OccupiedDefault = 35%Min = 0%; Max = 100%

BMS Watchdog Enabled Control

BMS WATCHDOG
When directly commanding fans speeds, damper positions, or sending sensor values, the unit controller requires the BMS Watchdog point to be written to on a recurring basis. This tells the unit controller that the BMS is still actively communicating.

ObjectVariableDescriptionActive TextInactive Text
BMS Watchdog
The BMS Watchdog must be written to True (1) regularly to verify communication is established between the unit controller and the BMS headend system. If the BMS Watchdog value remains False(0) for longer than the Timeout Delay (15 minutes, adjustable), an alarm is generated and thecontroller falls back to local control and sensor values, as applicable, instead of using BMS commanded values.
BV-1BMS_WatchdogBMS Watchdog commandActiveInactive
BV-20BMS_Watchdog_ActiveStatus of the BMS watchdog ping.ActiveInactive
CONTROLLING AIRFLOW DEVICES

If desired, the speeds and positions of airflow devices can be controlled directly using BACnet commandable points. To control the devices via the BMS, the BMS Watchdog requirements must be satisfi.

ObjectVariableDescriptionActive TextInactive Text
Fan Controls
Fan speeds can be controlled directly though BMS points. The binary points enable the BMS to take control and the analog values command thespeeds as a percentage between the allowed minimum and maximum values set in the controller.
Supply Fan
BV-14SF_Control_Source_BMSAllows the BMS to control supply fan speedBMSLocal
AV-38SF_Control_Signal_BMSSupply Fan Command SpeedReal (%)*Min=50%; Max=100%
Outdoor Air/Recirculation Air Damper Control
The outdoor air damper position can be controlled directly by the BMS to adjust the mixture of outdoor air and recirculation air on units configured forrecirculation. Minimum and maximum values for occupied and unoccupied mode set at the unit controller are enforced.
BV-15OAD_Control_Source_BMSAllows the BMS to control OAD positionBMSLocal
AV-39OAD_Control_Signal_BMSOutside Air Damper Control Signal via BMSReal (%)Min=0%; Max=100%

SENDING SENSOR VALUES
Sensor values required for sequence operation can be sent to the controller over dedicated BMS points in place of a sensor wired to the controller (local sensor). When values are communicated to the controller over BMS, the BMS Watchdog must be satisfied. If the watchdog isn’t satisfied, the controller reverts to the local sensor (if installed and valid) to control the unit or falls back to local control until the BMS watchdog is satisfied.

ObjectVariableDescriptionActive TextInactive Text
BMS Writeable Sensor Values
To write the sensor values over BMS, first command the controller to use the BMS value using the corresponding binary value and then use thecorresponding analog value to send the sensor value.
Sensor Sources
BV-6Outside_Temp_Source_BMSOutside Temp Source SelectionBMSLocal
BV-9Space_1_CO2_Source_BMSSpace 1 CO2 Source SelectionBMSLocal
BV-10Return_CO2_Source_BMSReturn CO2 Source SelectionBMSLocal
BV-12Space_Static_Source_BMSSpace Static Source SelectionBMSLocal
BV-13Space_Temp_Source_BMSSpace Temp Source SelectionBMSLocal
Sensor Values
AV-30Outside_Temp_from_BMSOutside Temp from BMSReal (°F)
AV-33Space_1_CO2_from_BMSSpace 1 CO2 from BMSReal (ppm)
AV-34Return_CO2_from_BMSReturn CO2 from BMSReal (ppm)
AV-36Space_Static_from_BMSSpace Static from BMSReal (“wc)
AV-37Space_Temp_from_BMSSpace Temp from BMSReal (°F)

Advanced BACnet Settings

Additional settings can be accessed in the BACnet Advanced Settings menu includingBACnet Broadcast Management Device (BBMD) configuration, relinquish default settings, Change of Value (COV) increments and restoring binary text value
Menu Structure Reference

BBMD CONFIGURATION
To configure the controller to operate with a BACnet Broadcast Management Device (BBMD) on IP networks, go to the advanced BACnet settings menu and enter the IP
address of the BBMD, foreign device configuration, and time to live setting.
BBMD CONFIGURATION

COV INCREMENTS
BACnet COV is an optional portion of BACnet that supports providing new
values/information only after an increase or decrease of the value is at least the listed
COV increment. The controller’s COV increments are based on the unit of measure. All variables with the same unit of measure share the same COV increment value.  Valuescan be adjusted on this screen, or by writing to the COV increment property of any BACnet object.
COV INCREMENTS

RELINQUISH DEFAULT SETTINGS
When the Return to Default function is enabled, the present value will not overwrite
the relinquish default value and on a loss of power the controller will boot with last
saved default values instead of last written values. This must also be enabled for the BACnet Comm Loss relinquish default to work.
When the Enable Relinquish Default function is enabled any value in the priority array
for binary values or analog values will be cleared if a communication loss is detected. All commandable points will revert to the relinquish default value.
RELINQUISH DEFAULT SETT

Communication loss is determined based on the BMS Watchdog. The watchdog function must be enabled. The function will execute 5 minutes after the watchdog status goes inactiv
RELINQUISH DEFAULT SETT

This may be desired if the BMS is running a reset routine on the setpoints and would
like to revert to a default state if communication is lost. It is recommended to be used
with return to default enabled, and a known relinquish default is saved. When this box is checked by a user, the controller will write the present value of variables to the relinquish default for all binary and analog value BACnet objects that are commandable. The function operates in the background and takes approximately30 seconds to complete.

This is desired to save any Test and Balance settings adjusted locally on the controller to be the BACnet relinquish default values. Alternatively, these values could be read and written to the relinquish default variables by the BMS system.
RELINQUISH DEFAULT SETT
BINARY TEXT
If for any reason, the state text is missing from binary objects, checking this box will cause the controller to re-write the active and inactive text values.

MUA Reference Table

STATUS MODE TABLE
The following analog values can appear in the point to tell the building automation the current mode of operation of the unit. Values may rotate every three seconds.

Status Mode Table (AV-41)
Analog ValueModeAnalog ValueModeAnalog ValueMode
0Off/Standby10System On21Cooling
1Unoccupied Start11Soft Shutdown22Heating
2Occupied Start12System Disabled30Overrides
3Opening Dampers13Remote Off31Expansion Offline
5Dampers Open14System Shutdown Alarm32Occupancy Overridden
6Fan Start Delay18Unit Off Flow Active33Max Vent Sequence Active
7Exhaust Fan Start19Fans Only35Morning Sequence Active
8Supply Fan Start20Economizing36Winter Ramp Active
9Startup Delay

ALARM TABLE
This table displays the latest alarm that is active in the unit controller.

Alarm Table – Latest Alarm (IV-9)
0No Active Alarms27IG Furnace 1 Combust Fan High Pressure Switch
1Supply Fan Run Status Not Proven28IG Furnace 1 Ignition Controller Alarm
2Exhaust Fan Run Status Not Proven29IG Furnace 1 Pressure Switch Fault Alarm
3Filters are Dirty Replace Filters30IG Furnace 1 Combust Fan Proving Alarm
4Cond Drain Pan Full Check Drain31IG Furnace 1 Max Retries
5High Supply Duct Static Pressure32IG Furnace 1 High Limit Trip
6Outside Air Temp Sensor Value Not Valid33IG Furnace pCOe 1 Offline
7Space Temperature Sensor Value Not Valid34IG Furnace 1 IC Fault Check IC->pCOe Wiring
8Supply Air Temperature Sensor Value Not Valid35IG Furnace 1 Combustion Fan Alarm
9Outside Air GreenTrol Offline or Flow Error36IG Furnace pCOe 2 Offline
10Hi/Low Pressure Switch Circuit A37IG Furnace 2-No Flame Alarm After 3 Tries
11Hi/Low Pressure Switch Circuit B38IG Furnace 2 Max Retries
12Space CO2 Sensor Value Not Valid39IG Furnace 2 Ignition Controller Alarm
13Return CO2 Sensor Value Not Valid40IG Furnace 3-No Flame Alarm After 3 Tries
14Space Static Pressure Sensor Value Not Valid41IG Furnace 3 Max Retries
15Supply Duct Stat Press Sensor Value Not Valid42IG Furnace 3 Ignition Controller Alarm
16Supply Air Temperature Low Limit Shutdown43DG Flame Safeguard General Reference
17Supply Air Temperature High Limit Shutdown44DG Flame Safeguard Manual Reset at FSG
18Space High Static Pres Shutdown45DG Pilot Flame Alarm Did Not Prove
19BMS Offline Watchdog is FALSE46DG Heating Safety Check Circuit
20BACnet License Not Installed47DG Flame Safeguard Check Functionality
21Space Thermostat 1 Sensor Offline48DG Burner Differential Check Pressure
22Space Thermostat 2 Sensor Offline51Multi Devices per Ch Contact Tech Support
23Space Thermostat 3 Sensor Offline52Comp Maintenance Alarm Run Hours Setpoint Reached
24Space Thermostat 4 Sensor Offline54Non-Volatile Memory Er Contact Tech Support
25IG Furnace 1-No Flame Alarm After 3 Tries55Cooling Exp Board pCOe 3 Offline
26IG Furnace 1 – Large No Flame After 3 Tries59Exp Board 4 Status Board is Offline

BIT-PACKED INTEGER WORD TABLES
The following tables are used to unpack integer words into Boolean values.

Digital Output Table (IV-10)
BitDigital_Output_WordBitDigital_Output_WordBitDigital_Output_Word
0Supply Fan Start11Furnace 3 Start22
1Exhaust Fan Start1223
2Exhaust Relief Enable13Damper Actuator Power Enable24
3Compressor 1 Start14Direct Gas Start25
4Compressor 2 Start15Electric Heat Start26
5Condenser Fan Start16Evaporative Cooling Valve Enable27
617Evaporative Cooling Pump Enable28
7Furnace 1 Start1829
8Furnace 1 Stage 2 Start1930
9Furnace 2 Start2031
10Furnace 2 Stage 2 Start21
Cooling Alarm Table (IV-11)
BitCooling_Alarm_WordBitCooling_Alarm_WordBitCooling_Alarm_Word
0Circuit A High/Low Pressure Switch Alarm1122
1Circuit B High/Low Pressure Switch Alarm1223
21324
31425
41526
51627
61728
71829
81930
92031
1021
Device Offline Table (IV-12)
BitDevice_Offline_WordBitDevice_Offline_WordBitDevice_Offline_Word
0Space T-Stat 1 Offline1122
1Space T-Stat 2 Offline1223
2Space T-Stat 3 Offline1324
3Space T-Stat 4 Offline1425
4IG Furnace Controller 1 Offline1526
5IG Furnace Controller 2 Offline1627
6Cooling Controller Offline1728
7GreenTrol Outside Air Offline1829
8BMS Offline Alarm1930
9Permanent Memory – Too Many Writes2031
1021
Device Alarms Table (IV-13)
BitDevice_Alarm_WordBitDevice_Alarm_WordBitDevice_Alarm_Word
0Supply Fan Alarm11Supply High Duct Static Alarm22
1Exhaust Fan Alarm12Supply Duct Static Sensor Alarm23
2Drain Pan Alarm13Space Static Pressure Sensor Alarm24
3Filter Alarm14Space High Static Alarm25
4GreenTrol OAD AFMS Alarm15Return CO2 Sensor Alarm26
5Outside Air Temp Sensor Alarm1627
6Space CO2 Sensor Alarm17Shutdown Input Alarm28
7Supply Air Temp Sensor Alarm1829
8Space Temperature Sensor Alarm1930
9Supply Temp Low Limit Alarm2031
10Supply Temp High Limit Alarm21
Heating Alarm Table (IV-14)
BitHeating_Alarm_WordBitHeating_Alarm_WordBitHeating_Alarm_Word
0DG Flame Safeguard General Reference11IG Furnace 1 Pressure Switch Fault Alarm22IG Furnace 3 Ignition Controller Alarm
1DG Flame Safeguard Manual Reset at FSG12IG Furnace 1 Combust Fan Proving Alarm23
2DG Pilot Flame Alarm Did Not Prove13IG Furnace 1 Max Retries24
3DG Heating Safety Check Circuit14IG Furnace 1 High Limit Trip25
4DG Flame Safeguard Check Functionality15IG Furnace 1 IC fault Check Furnace Wiring26
5DG Burner Differential Check Pressure16IG Furnace 1 Combustion Fan Alarm27
6General IG Furnace Alarm17IG Furnace 2-No Flame Alarm After 3 Tries28
7IG Furnace 1 No flame Alarm After 3 Tries18IG Furnace 2 Max Retries29
8IG Furnace 1 Large No Flame After 3 Tries19IG Furnace 2 Ignition Controller Alarm30
9IG Furnace 1 Combust Fan High PressureSwitch20IG Furnace 3-No Flame Alarm After 3 Tries31
10IG Furnace 1 Ignition Controller Alarm21IG Furnace 3 Max Retries
Unit Status Word Table (IV-11)
BitUnit_Status_WordBitUnit_Status_WordBitUnit_Status_Word
0Off/Standby11Remote Off22Dehumidifying
1Unoccupied Start12System Shutdown Alarm23Hot Gas Reheat Active
2Occupied Start13Supply Fan Only24HGRH Purging
3Opening Dampers14Exhaust Fan Only25Dehum w/Heat
4Dampers Open15Purge Mode (Supply and Exhaust Only)26Energy Recovery Defrost Active
5Fan Start Delay16Case Heat Active27Heat Pump Defrost Active
6Exhaust Fan On17Fans Only28Morning Warm Up/Cool Down Active
7Supply Fan On18Economizing29Winter Ramp Active
8System On19Energy Recovery Active30
9Soft Shutdown20Cooling31Overrides Active
10System Disabled21Heating

 

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals