CL40 Installer Friendly Series Site Single Phase Simplex
Product Information
The Single Phase Duplex is a pump control system that can be
used for demand dose or timed dose applications. It is equipped
with a Float or C-LevelTM sensor for pump control, system
monitoring, event logging, and reporting.
The panel features the C-LevelTM sensor, which allows for
continuous level monitoring in the tank. The sensor detects the
level and sends a signal to the panel. Pump activation levels can
be adjusted using the panel touch pad. The operating range for the
C-LevelTM CL40 sensor is 3-39.9 inches (7.6-101.3 cm), while the
CL100 sensor has an operating range of 3-99.5 inches (7.6-252.7
cm).
The touch pad on the panel offers various features:
- A. Level Status indicators illuminate when floats or set points
are activated. An alarm will activate if a float operates out of
sequence. - B. HOA (Hand-Off-Automatic) buttons with indication control
pump mode. Hand mode defaults to Automatic when stop level or
redundant off level is reached. - C. Pump Run indicators will illuminate when pumps are called to
run. - D. LED display provides system information including level in
inches or centimeters (C-LevelTM only), mode, pump elapsed time,
events (cycles), alarm counter, float error count, timed dose
override counter (timed dose only), pump ON/OFF times (timed dose
only), and sequence ON/OFF times (timed dose only). - E. NEXT push button toggles display.
- F. UP and SET Push Buttons are used to set pump ON/OFF times
(timed dose only), pump operation (alternate 1-2 and 2-1), date and
hour, and activation levels (C-LevelTM only).
The panel components include an enclosure base measuring 16 x 14
x 6 inches (40.64 x 35.56 x 15.24 cm) made of NEMA 4X ultraviolet
stabilized thermoplastic. It is suitable for outdoor or indoor use
and features removable mounting feet. Other components include
circuit breakers (optional), power relays, float connection
terminal block, control power indicator/fuse indicator light, alarm
power indicator/fuse indicator light, ground lugs, RF filter, power
supply, control fuse, alarm fuse, USB port for flash drive, and a
manual report switch.
Note: The panel layout may vary with options selected. Options,
voltage, and amp range chosen may affect enclosure size and
component layout.
Note: The schematic/wiring diagram and pump specification label
can be found inside the panel.
Product Usage Instructions
- Install the Single Phase Duplex panel in a suitable location
near the pump and tank. - Connect the C-LevelTM sensor to the tank to enable continuous
level monitoring. Adjust the pump activation levels using the panel
touch pad. - If using timed dose mode, use the UP and SET Push Buttons on
the touch pad to set the desired pump ON/OFF times. - Ensure that the control power and alarm power are present in
the panel by checking the corresponding indicator lights. - If an alarm condition occurs, use the Exterior Alarm
Test/Normal/Silence switch to test the horn and light. The horn can
be silenced by switching to the Silence position. - If necessary, reset the alarm once the alarm condition is
cleared. - To download time-stamped system events, insert a flash drive
into the USB port. - Use the Manual Report switch to date and time stamp service
calls. - Refer to the schematic/wiring diagram and pump specification
label inside the panel for additional information and
guidance.
INSTALLER FRIENDLY SERIES® (IFS) IN-SITE®
SINGLE PHASE DUPLEX
Demand Dose or Timed Dose, Float or C-LevelTM Sensor Controlled System for Pump Control, System Monitoring, Event Logging and Reporting
A
15 D 16 17
3
62
14
1
5
C B
9
18 13
Installer Friendly Series®
EF
The IFS In-Site® duplex control panel utilizes an innovative circuit board design to control two alternating 120/208/240V single phase pumps in water and sewage applications. IFS panels feature an easy-to-use touch pad on inner door for programming and system monitoring. The alternating action equalizes pump wear. In addition, this system provides override control should either pump fail. Quick retrieval of all system events can be done by downloading panel information onto a USB flash drive. The panel configuration can be easily converted in the field to either a timed dose or demand dose. Available with the EZconnex® float system.
Monitor system events including pump run times, pump cycles, alarm conditions, power outages, service calls and more! Quick, convenient reports make diagnosing system conditions easy! Plug the flash drive into the USB port located on the inner door of the IFS In-Site® panel to download system events which occurred. No computer is needed at the site! Use the flash drive (included with panel) with any computer to download system information and reports. The pre-loaded software on the flash drive formulates system data for you, creating reports quickly in an easy-to-read format so system conditions can be easily identified and corrected. In addition to monitoring system events, the IFS In-Site® panel logs any service calls and changes made to system settings, which helps protect service providers.
The panel can utilize the C-LevelTM sensor for continuous level monitoring. It senses the level in the tank and sends a signal to the panel. Pump activation levels can be adjusted by using the panel touch pad. C-LevelTM CL40 sensor operating range is 3-39.9 inches (7.6-101.3 cm). C-LevelTM CL100 operating range is 3-99.5 inches (7.6-252.7 cm).
TOUCH PAD FEATURES
A. Level Status indicators illuminate when floats or set points are activated; alarm will activate if a float operates out of sequence
B. HOA (Hand-Off-Automatic) buttons with indication control pump mode; Hand mode defaults to Automatic when stop level or redundant off level is reached
C. Pump Run indicators will illuminate when pumps are called to run D. LED display for system information including: level in inches or centimeters
(C-LevelTM only), mode, pumps elapsed time (hh:mm), events (cycles), alarm counter, float error count, timed dose override counter (timed dose only), pump ON/OFF times (timed dose only), and sequence ON/OFF times (timed dose only) E. NEXT push button toggles display F. UP and SET Push Buttons used to set pump ON/OFF times (timed dose only), pump operation (alternate 1-2 and 2-1), date and hour, activation levels (C-LevelTM only)
4
7 8 12
11
Panel layout may vary with options. Reg. Cdn Pat. & TM Off C-LevelTM Sensor US Patent No. 8,336,385; 8,567,242; 8,650,949
COMPONENTS
1. Enclosure base measures 16 x 14 x 6 inches (40.64 x 35.56 x 15.24 cm); NEMA 4X (ultraviolet stabilized thermoplastic with removable mounting feet for outdoor or indoor use)
2. Red LED beacon provides 360° visual check of alarm condition
3. Exterior Alarm Test/Normal/Silence switch allows horn and light to be tested and horn to be silenced in an alarm condition; alarm automatically resets once alarm condition is cleared
4. Alarm horn provides audio warning of alarm condition (83 to 85 decibel rating)
5. Circuit breakers (optional) provide pump disconnect and branch circuit protection
6. Power relays control pump by switching electrical lines; definite purpose contactors used when pump full load amps are above 15
7. Float connection terminal block 8. Incoming Control/Alarm Terminal Block
9. Control Power indicator/fuse indicator light illuminates if control power is present in panel; alarm activates if control fuse is blown
10. Alarm Power indicator/fuse indicator light illuminates if alarm power is present in panel (Not shown)
11. Ground lugs
12. Incoming pump power connections
13. RF filter
14. Power supply
15. Control fuse
16. Alarm fuse
17. USB port for flash drive to download time-stamped system events
18. Manual report switch date and time stamps service calls
Note: Options, voltage, and amp range selected may change enclosure size and component layout.
Note: Schematic/Wiring Diagram and Pump Specification Label are located inside the panel.
9500060J Rev 01/23 © 2020 SJE, Inc. All Rights Reserved. SJE Rhombus is a trademark of SJE, Inc.
www.sjerhombus.com · Toll Free 888-342-5753
B.25
Installer Friendly Series®
PRICING WORKSHEET
INSTALLER FRIENDLY SERIES® IN-SITE® SINGLE PHASE DUPLEX – Demand or timed dose float controlled system for pump control, system monitoring, event logging and reporting.
IFI
CONTROL PANEL
MODEL TYPE
1
ALARM PACKAGE
W
ENCLOSURE RATING
STARTING DEVICE
PUMP FULL LOAD AMPS
PUMP
FLOAT SWITCH
DISCONNECTS APPLICATION
8AC
OPTIONS (LISTED BELOW)
CONTROL PANEL 3 IFI
MODEL TYPE
3 Duplex Timed Dose (includes Option 8AC as standard) 4 Duplex Demand Dose (includes Option 8AC as standard)
ALARM PACKAGE 3 1 Alarm Package (includes test/normal/silence switch, fuse, red light, & horn)
ENCLOSURE RATING 3 W Weatherproof, NEMA 4X (engineered thermoplastic)
STARTING DEVICE
1 120/208/240V 9 120V only
PUMP FULL LOAD AMPS
0 0 – 7 FLA 1 7 – 15 FLA 2 15 – 20 FLA
0 No Pump Disconnect
PUMP DISCONNECTS
4 Circuit Breaker(s) 120V (select STARTING DEVICE Option 9 above) Circuit Breaker(s) 120/208/240V (select STARTING DEVICE Option 1 above)
H
Floats – Pump Down (select Option 17 below) Timed dose = timer enable and alarm / Demand dose = stop, start, and alarm
FLOAT SWITCH APPLICATION
E
EZconnex® Float Switch System (select Option 34 or 35 below)
X No Floats
Timed Dose Demand Dose Timed Dose Demand Dose
C
C-LevelTM Sensor (select Option 24 or 29) Select Option 3E and/ Timed Dose
or 4A & 4D for high water alarm and/or redundant off floats
Demand Dose
NOTE: Pump down applications only. Industry practices suggest that a secondary device, such as a float switch, be used for redundant activation of the high level alarm and pump shut off when using the C-LevelTM sensor.
IFI Duplex Base Price Alarm Package
Enclosure Rating Starting Device
Pump Full Load Amps Pump Disconnects
Float Switch Application Total Options
TOTAL LIST PRICE
OPTIONS 1J 3A 3B
Duo Alarm Inputs Alarm Flasher Manual Alarm Reset
DESCRIPTION
3E
High Water Alarm Float (must also select Option 17) Only Available with Float Switch Application = C
4A
Redundant Off
Timed Dose
(must also select Option 4D if floats are required) Demand Dose
4D Redundant Off Float (must also select Option 4A and Option 17)
6A Auxiliary Alarm Contact, Form C
Display Board – Includes: ETM Counter, Events (Cycles) Counter, 3 8AC Alarm Counter, Override Counter (Timed Dose Only), and Lead/
Lag Selector (Demand Dose Only) (included as standard)
10E Lockable Latch – NEMA 4X
10F
Lightning Arrestor (select pump circuit breakers, control and alarm power combined)
10K
Anti-condensation Heater (must select if operating temperature is colder than 0 degrees F or -18 degrees C)
11C Additional NEMA 1 Remote Alarm Panel (must also select Option 6A) 11D Additional NEMA 4X Remote Alarm Panel (must also select Option 6A) 15A Control/Alarm Circuit Breaker 16A 10′ Cord in Lieu of 20′ Cord (per Float) 16B 15′ Cord in Lieu of 20′ Cord (per Float) 16C 30′ Cord in Lieu of 20′ Cord (per Float) 16D 40′ Cord in Lieu of 20′ Cord (per Float)
OPTIONS
DESCRIPTION
17C Sensor Float® / Internally Weighted (per Float) – Mercury
17D Sensor Float® / Externally Weighted (per Float) – Mercury
17G SJE MilliAmpMasterTM / Pipe Clamp (per Float) – Mechanical
17H SJE MilliAmpMasterTM / Externally Weighted (per Float) – Mechanical
17J Sensor Float® / Pipe Clamp (per Float) – Mercury
18A Timer Override Float (Timed Dose Float Panel Only)
19F
Fourth Float to Separate Alarm Function from Lag (Demand Dose Float Panel Only)
24E 24F 24G 24H 24X 29A 29B 29X 34D 34E 34G 34H 35D 35E 35G 35H
C-LevelTM CL40 Sensor with 4′ Vent Tube and 20′ Cord C-LevelTM CL40 Sensor with 4′ Vent Tube and 40′ Cord C-LevelTM CL40 Sensor with 8′ Vent Tube and 20′ Cord C-LevelTM CL40 Sensor with 8′ Vent Tube and 40′ Cord No C-LevelTM CL40 Sensor C-LevelTM CL100 Sensor with 10′ Vent Tube and 20′ Cord C-LevelTM CL100 Sensor with 10′ Vent Tube and 40′ Cord No C-LevelTM CL100 Sensor EZconnex® 4-Port, 25′, with 10′ Floats (3) / Pipe Clamp, Sealing Plug EZconnex® 4-Port, 50′, with 10′ Floats (3) / Pipe Clamp, Sealing Plug EZconnex® 4-Port, 25′, with 20′ Floats (3) / Pipe Clamp, Sealing Plug EZconnex® 4-Port, 50′, with 20′ Floats (3) / Pipe Clamp, Sealing Plug EZconnex® 4-Port, 25′, with 10′ Floats (4) / Pipe Clamp EZconnex® 4-Port, 50′, with 10′ Floats (4) / Pipe Clamp EZconnex® 4-Port, 25′, with 20′ Floats (4) / Pipe Clamp EZconnex® 4-Port, 50′, with 20′ Floats (4) / Pipe Clamp
EZconnex® mechanically-activated, narrow angle float switches with quick release connections
B.26