Installer Friendly Series Single Phase Simplex
Product Information
The Three Phase Duplex is a pump control and system monitoring
system that can be operated in either Demand Dose or Timed Dose
mode. It is equipped with a Float or C-LevelTM Sensor for pump
control and continuous level monitoring. The panel features a touch
pad with various features for easy operation and monitoring.
C-LevelTM Sensor
The panel can utilize the C-LevelTM sensor for continuous level
monitoring. It senses the level in the tank and sends a signal to
the panel. Pump activation levels can be adjusted using the panel
touch pad. The C-LevelTM CL40 sensor has an operating range of
3-39.9 inches (7.6-101.3 cm), while the C-LevelTM CL100 sensor has
an operating range of 3-99.5 inches (7.6-252.7 cm).
Touch Pad Features
- A. Level Status indicators illuminate when floats or set points
are activated; alarm will activate if a float operates out of
sequence - B. HOA (Hand-Off-Automatic) buttons control pump mode with
indication; Hand mode defaults to Automatic when stop level or
redundant off level is reached - C. Pump Run indicators will illuminate when pumps are called to
run - D. Lead/Lag selector toggles pump operation (alternate 1-2 and
2-1) - E. LED display shows system information including: level in
inches or centimeters (C-LevelTM only), mode, pumps elapsed time
(hh:mm), events (cycles), alarm counter, float error count, timed
dose override counter (timed dose only), and ON/OFF times (timed
dose only) - F. NEXT push button toggles display
- G. UP and SET push buttons set pump ON/OFF times (timed dose
only) and activation levels (C-LevelTM only)
Components
- 1. Enclosure base measures 16 x 14 x 6 inches (40.64 x 35.56 x
15.24 cm); NEMA 4X (ultraviolet stabilized thermoplastic with
removable mounting feet for outdoor or indoor use) - 3. Exterior Alarm Test/Normal/Silence switch allows horn and
light to be tested and horn to be silenced in an alarm condition;
alarm automatically resets once alarm condition is cleared - 4. Motor protective switches provide adjustable overload,
branch circuit protection, and pump disconnect - 5. IEC motor contactors control pumps by switching electrical
lines - 6. Multi-tap transformer (208/240/480 VAC primary) provides 120
VAC control alarm voltage or 600 VAC primary transformer - 7. Float connection terminal block
- 8. Control Power indicator/fuse indicator light illuminates if
control power is present in the panel; alarm will activate if
control fuse is blown - 9. Alarm Power indicator/fuse indicator light illuminates if
alarm power is present in the panel - 10. Large incoming power connection terminal block
- 11. Terminal block float wiring label
- 12. Ground lugs
- 13. Alarm horn provides audio warning of alarm condition (83 to
85 decibel rating) (Not shown)
Note:
Options, voltage, and amp range selected may change enclosure
size and component layout.
Schematic/Wiring Diagram and Pump Specification Label are
located inside the panel.
Pricing Worksheet
- IFS CONTROL PANEL 6 MODEL TYPE 1
- ALARM PACKAGE W
- ENCLOSURE RATING PUMP FULL LOAD AMPS
- FLOAT SWITCH APPLICATION
- CONTROL PANEL 3 IFS MODEL TYPE 3 6 Three Phase Duplex (includes
Option 8AC as standard) - ALARM PACKAGE 3 1 Alarm Package (includes test/normal/silence
switch, fuse, red light, & horn) - ENCLOSURE RATING 3 W Weatherproof, NEMA 4X (engineered
thermoplastic)
Regulatory Information
Reg. Cdn Pat. & TM Off C-LevelTM Sensor US Patent No.
8,336,385; 8,567,242; 8,650,949
Additional Information
Panel layout may vary with options.
Product Usage Instructions
- Connect the Three Phase Duplex panel to the power source using
the large incoming power connection terminal block. - If using the C-LevelTM sensor for continuous level monitoring,
connect it to the float connection terminal block. - Adjust the pump activation levels by using the touch pad and
the UP and SET push buttons. - To control the pump mode, use the HOA (Hand-Off-Automatic)
buttons on the touch pad. The Hand mode will default to Automatic
when the stop level or redundant off level is reached. - Monitor the system information displayed on the LED display,
including the level in inches or centimeters (C-LevelTM only),
mode, pumps elapsed time, events, alarm counter, float error count,
timed dose override counter (timed dose only), and ON/OFF times
(timed dose only). - Toggle the pump operation between Lead and Lag by using the
Lead/Lag selector on the touch pad. - If an alarm condition occurs, use the Exterior Alarm
Test/Normal/Silence switch to test the horn and light or to silence
the horn. The alarm will automatically reset once the alarm
condition is cleared. - Refer to the Schematic/Wiring Diagram and Pump Specification
Label located inside the panel for further information.
INSTALLER FRIENDLY SERIES® (IFS)
THREE PHASE DUPLEX
Demand Dose or Timed Dose, Float or C-LevelTM Sensor Controlled System for Pump Control and System Monitoring
AEC
3
6
2 1
4
B
9
5
F 10
Installer Friendly Series®
D
G
The IFS duplex control panel utilizes an innovative circuit board design to control two alternating 208/240/480 VAC three phase pumps in water and sewage applications. IFS panels feature an easy-to-use touch pad on inner door for programming and system monitoring. The alternating action equalizes pump wear. In addition, this system provides override control should either pump fail. The panel configuration can be easily converted in the field to either a timed dose or demand dose. Available with the EZconnex® float system.
The panel can utilize the C-LevelTM sensor for continuous level monitoring. It senses the level in the tank and sends a signal to the panel. Pump activation levels can be adjusted by using the panel touch pad. C-LevelTM CL40 sensor operating range is 3-39.9 inches (7.6-101.3 cm). C-LevelTM CL100 operating range is 3-99.5 inches (7.6-252.7 cm).
TOUCH PAD FEATURES
A. Level Status indicators illuminate when floats or set points are activated; alarm will activate if a float operates out of sequence
B. HOA (Hand-Off-Automatic) buttons control pump mode with indication; Hand mode defaults to Automatic when stop level or redundant off level is reached
C. Pump Run indicators will illuminate when pumps are called to run
D. Lead/Lag selector toggles pump operation (alternate 1-2 and 2-1)
E. LED display shows system information including: level in inches or centimeters (C-LevelTM only), mode, pumps elapsed time (hh:mm), events (cycles), alarm counter, float error count, timed dose override counter (timed dose only), and ON/OFF times (timed dose only)
F. NEXT push button toggles display
G. UP and SET push buttons set pump ON/OFF times (timed dose only) and activation levels (C-LevelTM only)
7 11
8
12
Panel layout may vary with options. Reg. Cdn Pat. & TM Off C-LevelTM Sensor US Patent No. 8,336,385; 8,567,242; 8,650,949
COMPONENTS
1. Enclosure base measures 16 x 14 x 6 inches (40.64 x 35.56 x 15.24 cm); NEMA 4X (ultraviolet stabilized thermoplastic with removable mounting feet for outdoor or indoor use)
2. Red LED beacon provides 360° visual check of alarm condition
3. Exterior Alarm Test/Normal/Silence switch allows horn and light to be tested and horn to be silenced in an alarm condition; alarm automatically resets once alarm condition is cleared
4. Motor protective switches provide adjustable overload, branch circuit protection and pump disconnect
5. IEC motor contactors control pumps by switching electrical lines
6. Multi-tap transformer (208/240/480 VAC primary) provides 120 VAC control alarm voltage or 600 VAC primary transformer
7. Float connection terminal block
8. Control Power indicator/fuse indicator light illuminates if control power is present in panel; alarm will activate if control fuse is blown
9. Alarm Power indicator/fuse indicator light illuminates if alarm power is present in panel
10. Large incoming power connection terminal block
11. Terminal block float wiring label
12. Ground lugs
13. Alarm horn provides audio warning of alarm condition (83 to 85 decibel rating) (Not shown)
Note: Options, voltage, and amp range selected may change enclosure size and component layout.
Note: Schematic/Wiring Diagram and Pump Specification Label are located inside the panel.
9500056L Rev 01/23 © 2020 SJE, Inc. All Rights Reserved. SJE Rhombus is a trademark of SJE, Inc.
www.sjerhombus.com · Toll Free 888-342-5753
B.17
Installer Friendly Series®
PRICING WORKSHEET
INSTALLER FRIENDLY SERIES® THREE PHASE DUPLEX – Demand or timed dose float controlled system for pump control and system monitoring.
IFS
CONTROL PANEL
6
MODEL TYPE
1
ALARM PACKAGE
W
ENCLOSURE RATING
PUMP FULL LOAD AMPS
FLOAT SWITCH APPLICATION
CONTROL PANEL 3 IFS
MODEL TYPE
3 6 Three Phase Duplex (includes Option 8AC as standard)
ALARM PACKAGE 3 1 Alarm Package (includes test/normal/silence switch, fuse, red light, & horn)
ENCLOSURE RATING 3 W Weatherproof, NEMA 4X (engineered thermoplastic)
208/240/480V
600V
001 1.0 – 1.6 FLA
005 1.0 – 1.6 FLA
101 1.6 – 2.5 FLA
105 1.6 – 2.5 FLA
201 2.5 – 4.0 FLA
205 2.5 – 4.0 FLA
PUMP FULL LOAD AMPS
301 4.0 – 6.3 FLA 401 6.0 – 10.0 FLA
305 4.0 – 6.3 FLA 405 6.0 – 10.0 FLA
511 9.0 – 14.0 FLA
515 9.0 – 14.0 FLA
611 13.0 – 18.0 FLA
615 13.0 – 18.0 FLA
621 17.0 – 23.0 FLA
625 17.0 – 23.0 FLA
701 20.0 – 25.0 FLA
705 20.0 – 25.0 FLA
H Floats – Pump Down (select Option 17 below)
FLOAT SWITCH APPLICATION
E EZconnex® Float Switch System (select Option 34 or 35 below)
X No Floats
C
C-LevelTM Sensor (select Option 24 or 29) Select Option 3E and/or 4A & 4D for high water alarm and/or redundant off floats
8AC
OPTIONS (LISTED BELOW)
IFS Three Phase Duplex Base Price
Alarm Package Enclosure Rating Pump Full Load Amps Float Switch Application
Total Options Enclosure Upsize TOTAL LIST PRICE
NOTE: Pump down applications only. Industry practices suggest that a secondary device, such as a float switch, be used for redundant activation of the high level alarm and pump shut off when using the C-LevelTM sensor.
ENCLOSURE UPSIZE: If you selected one or more of the options, add a one-time charge for enclosure upsize.
OPTIONS 3A Alarm Flasher 3B Manual Alarm Reset
DESCRIPTION
3E
High Water Alarm Float (must also select Option 17) Only Available with Float Switch Application = C
4A Redundant Off (must also select Option 4D if floats are required) 4D Redundant Off Float (must also select Option 4A and Option 17)
5A
Thermal Cutout/Heat Sensor Auto Reset (for pumps with thermal switch leads)
5E Seal Failure Circuit and Red Indicator (2 Wire) 6A Auxiliary Alarm Contact, Form C
3
8AC
Display Board – Includes: ETM Counter, Events (Cycles) Counter, Alarm Counter and Lead/Lag Selector (included as standard)
10E Lockable Latch – NEMA 4X 10G Lightning Arrestor 10K Anti-condensation Heater 11C Additional NEMA 1 Remote Alarm Panel (must also select Option 6A) 11D Additional NEMA 4X Remote Alarm Panel (must also select Option 6A) 16A 10′ Cord in Lieu of 20′ Cord (per Float) 16B 15′ Cord in Lieu of 20′ Cord (per Float) 16C 30′ Cord in Lieu of 20′ Cord (per Float) 16D 40′ Cord in Lieu of 20′ Cord (per Float)
OPTIONS 17C 17D 17G 17H 17J 19F 24E 24F 24G 24H 24X 29A 29B 29X
34D 34E 34G 34H 35D 35E 35G 35H
DESCRIPTION Sensor Float® / Internally Weighted (per Float) – Mercury Sensor Float® / Externally Weighted (per Float) – Mercury SJE MilliAmpMasterTM / Pipe Clamp (per Float) – Mechanical SJE MilliAmpMasterTM / Externally Weighted (per Float) – Mechanical Sensor Float® / Pipe Clamp (per Float) – Mercury Fourth Float to Separate Alarm Function from Lag C-LevelTM CL40 Sensor with 4′ Vent Tube and 20′ Cord C-LevelTM CL40 Sensor with 4′ Vent Tube and 40′ Cord C-LevelTM CL40 Sensor with 8′ Vent Tube and 20′ Cord C-LevelTM CL40 Sensor with 8′ Vent Tube and 40′ Cord No C-LevelTM CL40 Sensor C-LevelTM CL100 Sensor with 10′ Vent Tube and 20′ Cord C-LevelTM CL100 Sensor with 10′ Vent Tube and 40′ Cord No C-LevelTM CL100 Sensor EZconnex® 4-Port, 25′, with 10′ Floats (3) / Pipe Clamp, Sealing Plug EZconnex® 4-Port, 50′, with 10′ Floats (3) / Pipe Clamp, Sealing Plug EZconnex® 4-Port, 25′, with 20′ Floats (3) / Pipe Clamp, Sealing Plug EZconnex® 4-Port, 50′, with 20′ Floats (3) / Pipe Clamp, Sealing Plug EZconnex® 4-Port, 25′, with 10′ Floats (4) / Pipe Clamp EZconnex® 4-Port, 50′, with 10′ Floats (4) / Pipe Clamp EZconnex® 4-Port, 25′, with 20′ Floats (4) / Pipe Clamp EZconnex® 4-Port, 50′, with 20′ Floats (4) / Pipe Clamp
EZconnex® mechanically-activated, narrow angle float switches with quick release connections
B.18
www.sjerhombus.com · email: [email protected] SEE PRICE BOOK FOR PRICING.