Novakon P04 4.3 Inch Hmi Intelligent Iiot Gateway Instruction Manual

Novakon P04 4.3 Inch Hmi Intelligent Iiot Gateway Instruction Manual

NOVAKON logoP04 4.3 Inch HMI Intelligent IIoT Gateway
Instruction ManualNOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway4.3” HMI
Setup Manual

Introduction

The 4.3” HMI comes with a 480 x 272 high-resolution TFT display module and a IP65 waterproof grade. The elegance in its design coupled with the fiexibility of the iFACE editing software meets user satisfaction in any application requirement.
Warning
Please read this manual before continuing with installation or operation of the device.
General Guide

  • Installation and operation of the device must be done by professionally trained staff.
  • Installation of the device must follow the instructions as printed in this manual.
  • If installation of the device occurs outside the suggested storage temperature range of the device, it may cause the LCD to malfunction.
  • If installation of the device occurs outside the suggested storage humidity range of the device, it may cause the touch panel to accumulate moisture which may shorten its
    product lifespan.
  • Installation of the device must be kept away from the risk of any liquid or metal particles getting into the device. Foreign particles may cause internal components to short circuit and thus damage the device or even catch fire.
  • The device must be installed on a stable and flat surface.
  • Installation of the device must be kept away from the risk of corrosion, explosion, or heavy electronic and magnetic fields. It must also be kept away from high humidity and extreme shifts in temperature.
  • The liquid in the LCD screen is very hazardous. If leakage is found, avoid contact with skin. At the chance of accidental contact, please immediately rinse with water. If the material comes in contact with eyes, please use water to rinse out the material and immediately seek medical assistance.
  • Nearby equipment must be installed at a safe and appropriate distance with adequate protection to reduce local interference with the device.

Power Supply

  • The device is designed with an input power of DC 24V. If the supply voltage is outside of the DC 24V +/- 20% range, it may result in damage or malfunction to the device.
  • Therefore, please confirm that the voltage is correct before powering the device on. Please also ensure that the supplied power is stable during device operation.

Installation:

  • Please avoid placing communication lines in the same conduit as the power lines and high voltage lines. Isolated lines are suggested to reduce surrounding noise interference.

Operation

  • The device should not be used as a main control trigger for any emergency override or safety-related operations.
  • Please note that the touch panel on the device is made of standard glass. Do not use forceful pressure or sharp objects to contact or hammer the screen.

Service and Maintenance

  • Please do not allow non-trained staff members to perform the maintenance servicing.
  • Please ensure that the power is switched off before performing any machine cleaning or repairing.
  • When cleaning the front panel, be sure to use a soft cloth and mild detergent to wipe gently, avoiding any forceful pressing or rubbing.
  • Please do not use batteries with poor quality.

Waste and Recycling

  • Please adhere to local regulations when recycling the device.
  • The screen, lithium battery, and capacitors contain hazardous material to individual health and local environment, and must be disposed responsibly.

Grounding

In order to maintain the operational condition and functioning of the HMI hardware components, please ensure proper power grounding.
Please ensure that the cable connecting the FG power terminal to the ground has a cable resistance lower than 100ft.

Installation Parts

NOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - Parts

Housing Type and Cut-Out Dimension

NOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - Dimension

12345678
4.3″127.7089.70118.36.705.0080.81.30119.30

Installing Procedure

  1. Check the device cut-out size first, then proceed to make the proper cut-out on the setting plate. Lodge the device into the cut-out on the setting plate. (Unit = mm).
  2. Fasten the device to the setting plate by tightening the screws on the back of the device. Please tighten all screws evenly instead of tightening each screw one by one. If the screws are not tightened evenly, it may cause distortion damage to the device.NOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - Parts 1

Power Connection

The device requires a power voltage of DC 24V (+/-20%). For a power consumption of 6W on the HMI, a power supply of 8W or above is recommended.
Importance Notice
It is recommended that the power plug must be connected to the device power terminal prior to connecting to the power source.
Power-connecting steps

  1. Remove the power plug from the power terminal of the device.
  2. Loosen the three screws on the power plug.
  3. Strip the cable to expose the copper wire to about 7-8mm.
  4. Insert the exposed copper wire into the three openings on the power plug.
  5. Retighten the three screws on the power plug.
  6. Plug the power plug back into the power terminal of the device.

Note
The power plug is included and already plugged into the power terminal of the device.NOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - Parts 2

Power Line Type Power Line (AWG) Strip Length Torque
Solid28-12About 7-8 mmAbout 4.5 lb-in
Stranded30-12About 7-8 mmAbout 4.5 lb-in

* with copper conduction wire only.

Instructional Diagram

NOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - Diagram

  1. Lock’s Holes
  2. Power Indicator
  3. Dip Switches
  4. Power Terminal
  5. Expansion Slot
  6. COM1 RS232/422/485
  7. Ethernet Port
  8. USB Device
  9. USB Host

Product Specification

TypeP Series
ModelP04
Display Type4.3” TFT
Resolution480×272 pixel
Color16.7M
Backlight TypeLED
Brightness330 cd/m²
Contrast500:01:00
CPUARM Cortex A8 (1 GHz)
Flash Memory512M Bytes
RAM4GB , 8bit eMMC
FRAM (non-volatile)32K Bytes
RTCBuilt-in battery CR2032
COM11 x RS232  1 x RS422/485 , CAN(Option)
COM2N/A
COM3N/A
Ethernet1 x 10/100 Mbit
USB 1 x Host  1x Device
Memory CardN/A
Power Supply24V ± 20 % DC , lsolated Power
Power Consumption6 W
Operation Temperature0 ~ 45 ℃
Storage Temperature-20 ~ 60 ℃
Operation Humidity10 ~ 90RH    No Condensation
Dimension127.7(W) x 89.7(H) x 36.7(D) mm
Cut-out Dimension119.3(W) x 81.3(H) mm
 ( Net ) Weight0.25 kg
 Net weight with Packing box0.42 kg
Touch Panel4-wire Resistive

Power On Test

NOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - Power On Test 1When powered on, the device should automatically perform a system diagnostic test. The diagnostic summary at the end of the test will display NOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - icon 1a if no issues are detected, and aTigo TS4 A F Rapid Shutdown Device - icon2 if an error is detected. Press [Continue] to jump to the System Menu Screen. If there are no errors detected, the “Continue” option will not show.

System Menu Screen
Click [Settings] for all BIOS options which include: [COM Port], [Ethernet], [File Transfer], [Backlight], [Display], [Calibration], [RTC], [Sys. Status], [Misc.] and [USB Device]
NOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - Menu ScreenClick [Run App] to start up any applications downloaded to the device.

Ethernet Setting

Ethernet settings include [IP Address], [Gateway], [Netmask], [Port] and [DHCP]. In order to ensure a smooth and stable connection, communication parameters must correspond with the connected controller. Click the IP address fieldNOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - icon 2 to enter the IP address. The IP address should follow the format: XXX.XXX.XXX.XXX. Each XXX should be less than or equal to “255”. The system will automatically jump to the next set of XXX if values are accepted (if the input value is greater than 255, the system will require users to re-enter values). Press theNOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - icon 3 key to jump to the previous set of XXX values and the key to edit the next set.NOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - Menu Screen 1

File Transfer

Applications and firmware can be downloaded or uploaded via USB or SD card. SelectNOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - icon 5 for the application or firmware to be transferred from the HMI to the memory card. Select NOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - icon 7for the application or firmware to be transferred from the memory card to the HMI. Click [OK] to begin file transfer. NOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - Menu Screen 2Select the file that is going to be transferred. Click [OK] to begin transfer. Click [Cancel] to abort file transfer process.

Backlight (Brightness) Setting

Click theNOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - icon 6 to adjust backlight brightness of the device. The backlight brightness setting ranges from 0 to 20, 0 being the darkest and 20 being the brightness. Click on the indicator on the meter to edit brightness level.
NOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - Menu Screen 4Display Setting
Click [Screen Saver] to set how long the screen will stay lit before the screen saver function is effective. If the touch panel is not touched or if information is not updating automatically, the backlight will turn off according to the specified setting. Screen saver time ranges from 1 to 60 minutes. If the timer is set to 0, the screen saver function will turn of.

NOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - Menu Screen 5Click [Oriantation ] to set the HMI display orientation.
Click [ Language ] to change the language displayed in BIOS.

Calibration

If touch points deviate from contact point or are unresponsive, click [Calibrate] to reset the device calibration and correct the touch points. A cross-arrow will appear and the system will prompt the user to click on the cross-arrow as it moves across the four corners and to the center of the screen. After completion of these steps, the user can verify a successful calibration by touching the screen and ensuring the cursor follows correctly. Touch the center cross-arrow to accept calibration and the [OK] to save the calibration setting. If the touch point is not corrected, click [Cancel] to restart the calibration process.NOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - Menu Screen 6Note: The touch panel is a high precision electronic product, therefore, during calibration or anytime you press the screen, avoid sharp items that may potentially scratch or hurt the touch panel. This will help remain the lifetime of the product .

RTC Setting

Click [Date Format] to choose the formatting of the date displayed on the HMI. Options include: [Month/Day/Year], [Day/Month/Year], and [Year/Month/Day].
After choosing a format, the user can set the date and time accordingly. NOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - Menu Screen 7System Status

System Status displays the current status and information of the device, which includes: Applications size and capacity, BIOS, Firmware Version, and etc.
NOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - Power On Test 3Click [DIP Switch] and [COM Port] to display information relating to DIP Switch and COM Port, respectively.

COM Port

NOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - Menu Screen 9

COM Port (RS232 and RS422/485)
PinRS232RS422RS485
1TX+TX/RX+
2RX
3TX
4RX+
5SGSGSG
6TX-TX/RX-
7NC
8Optional + 5V/103mA
9I RX-

* The assignment of each pin and COM port varies from that of a standard PC. Please refer to the above table for signal connection and pin assignment.
* The number of COM ports varies with HMI model.
Dip Switch NOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - Menu Screen 10

SW1SW2SW3SW4Function description
ONONONONNormal operation
ONONONOFFBypass self – test
ONONOFFOFF ONON Reserved
ONONOFFOFFSystem menu
ON OFFxxReserved
OFFONxxCOM port test
OFFOFFOFFOFFBench Test
OFFOFFOFFONIndividual Function test
OFFOFF OFFONxReserved

MISC Setting

Both BIOS and Application could set the communication parameters of each COM port. Click [Buzzer] to enable or disable beep upon touch.  NOVAKON P04 4.3 Inch HMI Intelligent IIoT Gateway - Menu Screen 11Under [Debug Mode], click [Run application] to run application under debug mode, or click [Backup log] to save log file into USB or SD card when malfunction occurs.
Click [WiFi Setting] to choose HMI either as WiFi [Station] or as WiFi [AP].
Click [OK] to confirm and save all adjustments.
Click [Cancel] to cancel all adjustments.

NOVAKON logoHMI – Your Intelligent IIoT Gateway Solutions
1306.0015 Rev:1.1

References

    Documents / Resouces

    Download manual
    Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


    Related Manuals