Novus Np785 Ultra Low Differential Pressure Transmitter Instruction Manual

Novus Np785 Ultra Low Differential Pressure Transmitter Instruction Manual

NOVUS logoNP785 Ultra Low Differential
Pressure Transmitter NOVUS NP785 Ultra Low Differential Pressure TransmitterINSTRUCTION MANUAL V1.0x G

SAFETY ALERTS

The symbols below are used in the device and throughout this manual to draw the user’s attention to important information related to device safety and use.

warning - 1VECTORFOG BM100 Backpack Motorized Mist Sprayer - Icon 3NOVUS NP785 Ultra Low Differential Pressure Transmitter - icon 12
CAUTION
Read the manual fully before installing and operating the device.
CAUTION OR HAZARD
Risk of electric shock.
ATTENTION
Material sensitive to static charge. Check precautions before handling.

All safety recommendations appearing in this manual must be followed to ensure personal safety and prevent damage to the instrument or system.
If the instrument is used in a manner other than that specified in this manual, the device’s safety protections may not be effective.

PRESENTATION

The NP785 Ultra Low Differential Pressure Transmitter uses a high precision differential pressure sensor and has the stability required to perform measurements in  applications that require high sensitivity. It is a micro processed device with two communication interfaces: USB and RS485 via Modbus RTU protocol. The magnitude read  by the sensor is provided through any of its interfaces, converted to a selected pressure unit from a set of options.
This equipment has a digital alarm output, which supports the configuration of the alarm condition, adjustable set points and custom timing, among other functions. Its  transmission output can be configured to operate in the 0-10 V and 4-20 mA standards, with adjustable range within the sensor limits, and has adjustable behavior options in   case of sensor error.
NXperience software offers a quick and intuitive way to configure of all equipment features. It is also possible to carry out the monitoring and obtain the diagnosis of the  information downloaded.
The NP785 Ultra Low Differential Pressure Transmitter is suitable for use in HVAC applications such as environmental monitoring or climate control or environmental monitoring of industrial processes where high accuracy is required at low pressure ranges.

IDENTIFICATION

3.1 DEVICE IDENTIFICATION
The identification of the device model is described on its side label, together with information regarding its electrical connections and its serial number. Fig. 01 shows the information available in the device housing:

NOVUS NP785 Ultra Low Differential Pressure Transmitter - figFig. 01 – NP785 Ultra Low Differential Pressure Transmitter

3.2 DEVICE MODEL
In order to adapt to the most varied market needs, the NP785 Ultra Low Differential Pressure Transmitter line is available in two models:
• Model NP785-05 of ± 5 mbar.
• Model NP785-20 of ± 20 mbar.

ModelMinimal PressureMaximal PressureUnitBurst PressureStandard Configuration
5 mbar-5.0005.000mbar±200 mbarx
-72.5272.52mpsi
-2.0072.007in H2O
-50.9850.98mm H2O
-500.0500.0Pa
20 mbar-20.00020.000mbar±400 mbarx
-290.08290.08mpsi
-8.0298.029in H2O
-203.94203.94mm H2O
-2000.02000.0Pa

INSTALATION

4.1 MECHANIC INSTALATION
The NP785 Ultra Low Differential Pressure Transmitter is designed to have its housing fixed to a 35 mm DIN rail, as shown in Fig. 02. The 35 mm DIN rail installation must be carried out after the device has been configured.

1NOVUS NP785 Ultra Low Differential Pressure Transmitter - fig 1

Installation recommendations:

  • The pneumatic hoses must be installed after the device has been fitted to the 35 mm DIN rail.
  • In order to avoid problems with condensation, the device must be installed above the point to be measured.
  • The extension of the hoses does not affect the device accuracy. Very long hoses, however, can result in measurement delays.
  • Hoses should not be bent or sharp curves should not be taken. Such actions may result in airflow interruption and possible sensor reading blockage.

1NOVUS NP785 Ultra Low Differential Pressure Transmitter - fig 2

The hose do not come with the device.
Overpressure: Excessive pressure, which exceeds the NP785 Ultra Low Differential Pressure Transmitter capacity, can cause irreversible mechanical and electrical damage to  the device. In order to avoid damaging the operator or the device installer, follow the installation instructions and use the appropriate protection and device.

4.1.1 DIMENSION
Fig. 04 shows the dimensions of the device:

NOVUS NP785 Ultra Low Differential Pressure Transmitter - fig 1

4.2 ELECTRICAL INSTALLATION
4.2.1 RECOMMENDATIONS FOR INSTALLATION

  • Signal conductors should run through the plant separately from the power supply and output conductors. If possible, in grounded conduits.
  • The power supply for electronic instruments must come from an appropriate grid for instruments.
  • RC FILTERS (noise suppressor) are recommended in contactor coils, solenoids, etc.
  • In control applications, it’s essential to consider what could happen when some part of the system fails. The device’s internal devices do not ensure total protection.
  • Grounding helps limit the effects of noise due to electromagnetic interference (EMI). Run the grounding connection by using the grounding bolt and the grounding  plane before turning on the device.

4.2.2 SPECIAL PRECAUTION
Because it is an electronic module, the device needs some care when handling:

  • Due to the risk of damage caused by static electricity and may occur if the electronic circuit is exposed, the device should not be opened.
  • Pay close attention when connecting the wires.
  • Remember to pass all wires through a cable clip before completing electrical connections.
  • When closing the housing, the cover should be placed again properly, ensuring proper sealing for this device.

4.2.3 ELECTRICAL CONNECTIONS
Fig. 05 shows the device electrical connections:

NOVUS NP785 Ultra Low Differential Pressure Transmitter - fig 2

Electrical ConnectionInput
Output1ALARM
2OUT (Retransmission)
3GND
Power Supply4NC
5POWER
6GND
RS4857D1 (D)
8D0 ()
9GND

Table 02 – Electrical connections

4.2.4 USB CONNECTION
The USB connection is used exclusively for the device diagnosis and configuration. The USB interface is on the NP785 Ultra Low Differential Pressure Transmitter side.
It is recommended that the device be configured before it is attached to the DIN rail.
For more information, check the USB Interface chapter.

NOVUS NP785 Ultra Low Differential Pressure Transmitter - fig 3

CONFIGURATION

The NP785 Ultra Low Differential Pressure Transmitter is configurable by any of its interfaces. Due to the ease of use of the interface, it is recommended to configure via  USB using the NXperience software, but the device can also be configured via Modbus RTU by writing directly in their configuration registers.
The description of the device registers, together with the configuration tables, can be found in the Serial Communication chapter.

5.1 GENERAL CONFIGURATION
The purchase of the pressure value is done in digital analogue analysis solutions of the internal sensor of the device. You can select the pressure unit to be used from the  following options: mbar, mpsi, in H2O, mm H2O or Pa. Changes in this setting cause transmission limits and alarm set points to be reverted to the default values, which are the operating limits of the device.
The device also has an Offset function and an internal digital filter for treatment of the measured signal. An offset value can be set, which will be described on the selected  pressure unit, to make small adjustments to the output value. The digital filter allows you to set a time interval, in seconds, to reduce the occurrence of noise effects and peaks  of pressure over a faster response.
It is also possible to configure the Modbus RTU communication parameters, such as Baud Rate, parity and slave address of the device.
For purposes of differentiation between units of the same model, an identifier can be configured in the device.
For testing purposes, the device supports forcing differential pressure measurement, analog output and alarm output. For each of these cases, you can configure a value to be forced and enable or disable the forcing.

5.2 ALARM CONFIGURATION
The NP785 Ultra Low Differential Pressure Transmitter has a digital alarm output. The digital output will be activated whenever an alarm situation is satisfied, except in  particular cases defined by some of its settings.
You can configure the alarm operation mode, high and low set points, hysteresis value, state transition timers, error condition and initial blocking.
Alarm configuration can be performed using the NXperience software (see the Output Parameter section ), allowing different modes of operation:

  • Off: No alarm situation is active.
  • Sensor Error: While there is some error reading the sensor, the alarm output will remain on.
  • Below Lower Setpoint: The alarm output will be triggered when the current pressure is lower than the lower set point. To exit the alarm condition, the differential  pressure must be greater than the lower set point plus the hysteresis value.
  • Above Higher Setpoint: The alarm output will be triggered when the differential pressure is higher than the upper set point. To exit the alarm condition, the differential  pressure must be lower than the lower set point minus the hysteresis value.
  • Intra-range: The alarm output will be activated when the differential pressure is higher than the lower set point and lower than the upper set point. To exit the alarm  condition, the differential pressure must be greater than the upper set point plus the hysteresis value or lower than the lower set point minus the hysteresis value.
  • Extra-range: The alarm output will be activated when the differential pressure is higher than the set point higher or lower than the lower set point. To exit the alarm  condition, the differential pressure must be less than the upper set point minus the hysteresis value and higher than the lower set point plus the hysteresis value.

In addition to the alarm operation modes, other parameters, which do not apply to the Sensor Error mode, can be configured to refine the behavior of the alarm output:

  • Initial Blocking: This parameter determines the use of the alarm output lock soon after the device is started. After initialization, a non-alarm condition is required for the  alarm output to be enabled.
  • Error Condition: The status of this parameter determines whether the alarm output will remain on or off in case of sensor failure.
  • Hysteresis: This parameter stores the pressure value that, with the values of the set points, determines the limit value to leave the alarm situation. Fig. 07 shows the conditions for alarm activation and deactivation.

The alarm output can be timed by means of the Time On and Time Off parameters. For a given state transition to occur, the device must remain in the new state for a period  of time equal to the one configured in the respective transition parameter. These values are initialized to 0 by default.
Extra-range mode is the default mode of alarm output. The default values of the set points, in turn, are the operating limits of the device. Any changes in the pressure unit configuration readjust the values of the set points to the operating limits.

NOVUS NP785 Ultra Low Differential Pressure Transmitter - fig 4

5.3 ANALOG OUTPUT CONFIGURATION
The device has a configurable analog output. You can configure it using the NXperience software (check the Output Parameters section), and you can define: the electrical  pattern, the error mode and the excursion range of the pressure to be transmitted.
The electrical pattern can be selected between 0-10 V and 4-20 mA modes and the error mode determines the behavior of the analog output in case of sensor failure, as shown in Table 03:

Error Mode
ModeLowHighLow/High*
0 – 10 V0 V10 V< Minimum Limit à 0 V
Sensor error à 10 V
> Maximum Limit à 10 V
4 – 20 mA3.6 mA21.0 mA< Minimum Limit à 3.6 mA
Sensor error à 21.0 mA
> Maximum Limit à 21.0 mA

Table 03 – Behavior of the analog output in case of sensor failure

* Available starting with firmware version 1.20 and software version 2.0.6.02.
The excursion of the electric signal respects the values set in the configuration of the lower and upper transmission limits, which allows customizing the differential pressure  range. The factory setting also defines the upper and lower limits of the sensor as the maximum operating limits of each respective model.
The device is factory set with the 4-20 mA electrical standard and the pressure unit in mbar. Any changes in the pressure unit configuration readjust the values of the transmission limits to the operating limits of the device.

USB INTERFACE

The USB interface is used for CONFIGURING or MONITORING the device.
For CONFIGURATION, you must use the NXperience software to create, view, save, and open configurations from the device or files on your computer. The feature to  save and open configurations in files makes it possible to transfer configurations between devices and make backup copies.

NXperience allows you to update the NP785 Ultra Low Differential Pressure Transmitter firmware (internal software) via USB interface.
For MONITORING, any supervision (SCADA) or laboratory software that supports Modbus RTU communication over a serial communication port can be used. When  connected to a computer USB port, NP785 Ultra Low Differential Pressure Transmitter is recognized as a conventional serial port (COM x). Use NXperience or refer to the  Device Manager on Windows Control Panel to identify the COM port assigned to the device.
Refer to the Modbus memory mapping in the device communication manual and its supervision software documentation to perform MONITORING.
Follow the procedure below to use the device USB communication:

  • Download NXperience from our website and install it on your computer (see chapter NXperience Software). The USB drivers required for communication will be  installed along with the software.
  • Connect the USB cable between the device and the computer. The device doesn’t need a power supply. The USB will provide enough power for the communication  operation (other device functions may not operate).
  • Launch NXperience, configure the communication and start the device recognition.

warning - 1 The USB interface IS NOT ISOLATED from the retransmission output and alarm output. Its purpose is temporary use during CONFIGURATION and MONITORING  periods. For the safety of people and device, it should only be used with the device fully disconnected from the external power supply input.
VECTORFOG BM100 Backpack Motorized Mist Sprayer - Icon 3 In any other situation, the USB interface use is possible, but requires a careful analysis by the person responsible for its installation.
For MONITORING for long periods and with inputs and outputs connected, it is recommended to use the RS485, available or optional in most of our device.

SERIAL COMMUNICATION

The NP785 Ultra Low Differential Pressure Transmitter can be recognized on an RS485 network with Modbus RTU protocol as a slave device. All the configurable parameters of the device can be read and/or written via serial communication.
The device supports writing in Broadcast mode, using the slave address Modbus 0.
The available Modbus commands are as follows:
03 – Read Holding Register
05 – Write Single Coil
06 – Write Single Register
16 – Write Multiple Register

7.1 REGISTERS TABLE

NP785-05 Model: Output Registers Table
AddressNameDescriptionR/WTypeStandardMin.Max.Decimal Places
0HR_PRESSDifferential pressure valueROnt_320-5 mbar
-72,52 mpsi
-2,007 inH2O
-50,98 mmH2O
-500,0 Pa
5 mbar
72,52 mpsi
2,007 inH2O
50,98 mmH2O
500,0 Pa
mbar: 3 decimal places mpsi: 2 decimal places inH2O: 3 decimal places
mmH2O: 2 decimal places
Pa: 1 decimal place
1HR_PRESS_H
2HR_PRESS_MINMinimum differential pressure value loggedROint_320-5 mbar
-72,52 mpsi
-2,007 inH2O
-50,98 mmH2O
-500,0 Pa
5 mbar72,52 mpsi
2,007 inH2O
50,98 mmH2O
500,0 Pa
mbar: 3 decimal places mpsi: 2 decimal places inH2O: 3 decimal places mmH2O: 2 decimal places Pa: 1 decimal place
3HR_PRESS_MIN_H
4HR_PRESS_MAXMaximum differential pressure value loggedROint_320-5 mbar
-72,52 mpsi
-2,007 inH2O
-50,98 mmH2O
-500,0 Pa
5 mbar 72,52 mpsi 2,007 inH2O 50,98 mmH2O 500,0 Pambar: 3 decimal places mpsi: 2 decimal places inH2O: 3 decimal places mmH2O: 2 decimal places Pa: 1 decimal place
5HR_PRESS_MAX_H

Table 04 – NP785-05 Model: Output Registers Table

NP785-05 Model: Configuration Registers Table
AddressNameDescriptionR/WTypeStandardMin.Max.Decimal Places
100HR_SENSOR_TYPESensor type: 5 mbar or 20 mbarROuint16001N.A.
101HR_OUT1_TYPERetransmission output type*RWuint16001N.A.
103HR_OUT1_IN_HIGH_LIMITmbar: 3 decimal places
104HR_OUT1_IN_HIGH_LIMIT_HRetransmission upper limit inputRWint_325 mbar
72,52 mpsi
2,007 inH2O
50,98 mmH2O
-5 mbar
-72,52 mpsi
-2,007 inH2O
-50,98 mmH2O
5 mbar
72,52 mpsi

2,007 inH2O

50,98 mmH2O

mpsi: 2 decimal places
inH2O: 3 decimal places
500,0 Pa-500,0 Pa500,0 PammH2O: 2 decimal places
Pa: 1 decimal place
105HR_OUT1_IN_LOW_LIMITmbar: 3 decimal places
106HR_OUT1_IN_LOW_LIMIT_HRetransmission lower limit inputRWint_32-5 mbar
-72,52 mpsi
-2,007 inH2O
-50,98 mmH2O
-5 mbar
-72,52 mpsi
-2,007 inH2O
-50,98 mmH2O
5 mbar
72,52 mpsi
2,007 inH2O
50,98 mmH2O
mpsi: 2 decimal places
inH2O: 3 decimal places
-500,0 Pa-500,0 Pa500,0 PammH2O: 2 decimal places
Pa: 1 decimal place
107HR_OUT1_ERRError type (higher, lower or low/high)*RWuint16102N.A.
108HR_OUT1_HIGH_LIMITRetransmission upper limitROint_325 mbar 72,52 mpsi 2,007 inH2O 50,98 mmH2O 500,0 Pa-5 mbar
-72,52 mpsi
-2,007 inH2O
-50,98 mmH2O -500,0 Pa
5 mbar
72,52 mpsi 2,007 inH2O 50,98 mmH2O 500,0 Pa
mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal places
mmH2O: 2 decimal
109HR_OUT1_HIGH_LIMIT_H
places Pa: 1 decimal place
110HR_OUT1_LOW_LIMITRetransmission lower limitROint_32-5 mbar
-72,52 mpsi
-2,007 inH2O
-50,98 mmH2O
-500,0 Pa
-5 mbar
-72,52 mpsi
-2,007 inH2O
-50,98 mmH2O
-500,0 Pa
 

5 mbar
72,52 mpsi
2,007 inH2O
50,98 mmH2O
500,0 Pa

mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal places
mmH2O: 2 decimal places
Pa: 1 decimal places
111HR_OUT1_LOW_LIMIT_H
113HR_PRESS_FLTRFilter for differential pressure readingRWuint16003000
115HR_UNIT_SYSTEMUnits configuration*RWuint16004N.A.
122HR_A1FUAlarm type*RWuint16505N.A.
 

123

 

HR_A1SPHI_IN

Alarm Setpoint High InputRWint_320-5 mbar
-72,52 mpsi
-2,007 inH2O
-50,98 mmH2O
-500,0 Pa
5 mbar
72,52 mpsi
2,007 inH2O
50,98 mmH2O
500,0 Pa
mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal places
mmH2O: 2 decimal places
Pa: 1 decimal place
124HR_A1SPHI_IN_H
125HR_A1SPLO_INAlarm Setpoint Low InputRWint_320-5 mbar
-72,52 mpsi
-2,007 inH2O
-50,98 mmH2O
-500,0 Pa
5 mbar
72,52 mpsi
2,007 inH2O
50,98 mmH2O
500,0 Pa
mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal places
mmH2O: 2 decimal places
Pa: 1 decimal place
126HR_A1SPLO_IN_H
127HR_A1BLAlarm blockRWuint16001N.A.
128HR_A1HYAlarm hysteresisRWuint16001 mbar
14,50 mpsi
0,401 inH2O
10,20 mmH2O
100,0 Pa
mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal places
mmH2O: 2 decimal places
Pa: 1 decimal place
129HR_A1T1Alarm time ONRWuint160065000
130HR_A1T2Alarm time OFFRWuint160065000
131HR_A1IERRDetermines the alarm status in case of sensor errorRWuint16001N.A.
132HR_A1SPHIAlarm Setpoint HighROint_320-5 mbar
-72,52 mpsi
-2,007 inH2O
-50,98 mmH2O
-500,0 Pa
mbar 72,52 mpsi
2,007 inH2O
50,98 mmH2O
500,0 Pa
mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal places
mmH2O: 2 decimal places
Pa: 1 decimal place
133HR_A1SPHI_H
134HR_A1SPLOAlarm Setpoint LowROint_320-5 mbar
-72,52 mpsi
-2,007 inH2O
-50,98 mmH2O
-500,0 Pa
5 mbar
72,52 mpsi
2,007 inH2O
50,98 mmH2O 500,0 Pa
mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal places
mmH2O: 2
decimal places
Pa: 1 decimal place
135HR_A1SPLO_H
137HR_BAUDBaud Rate*RWuint16407N.A.
138HR_PRTYParity*RWuint16002N.A.
139HR_ADDRSlave addressRWuint1611247N.A.
##HR_OFST_PRESSUreter,. pressure
Offset
RWuin116.1 mi.
-14.50 mPT,
-0,401 k1H20 -10,20 mmH20 -100.0 Pa
1 mbar
14 50 mpsi 0,401 inH20 1020 mmH20 100.0 Pa
##HR_OUT1_FORCE_ENABEnables forang output 1RvVurnt16
##HR_OUT1 JORCE_VALForced value for out.
l
RJJ0.0.00 V
3,60 .
120i0mA0V
##HR_A1_FORCE_ENABEnables form, alarm 1RW0.
##H,A1_STATEChanges:flrol statusRJJurnt16
##HR_FORCE_IN_PRESSrs:e1=’RJJ0.
##HR_FORCE_PRESS_INForced ckfterential
pressure value input
RvVint_325 m.
-72,52 mpsi
-2.007 inH20 50,98 mmH20 -500,0 Pa
5 mbar 7252. 2.007 inH20 50,98 mmH20 500,0 Pa
##HR_FORCE_PRESS_IN_H
##HR_FORCE_PRESSFaced differential
prewure value
RO.1_32-5 rn.
-72.52 mpsi
-2,007 ilH20 50,98 mmH20 500,0 Pa
5 mbar
7252 mpsi 2,007 inH20 50,8 mmH20 500,0 Pa
HR_FORCE_PRESS
##HR_RESET,INReset al lows and fig.RvVumt16
##HR_PRODUCT_TAGO1EOPment tagRJJdear4000OxFFFF
##HR_PRODUCT JAGO2RvVcharOx0000OxFFFF
##HR_PRODUCT_TAGO3RWcharOxC000OxFFFF
##HR_PRODUCT_TA.RWcharOx0000OxFFFF
##HR_PRODUCT _TAGO5RvVcharOx0000OxFFFF
##HR_PRODUCT_TAGO6RJJchacOx0000OxFFFF
##HR_PRODUCT _TAGO7RvVchar0Ox0000OxFFFF
##HR_PRODUCT _TAGO8RJJchacOx0000OxFFFF
##HR_PRODUCT_TA009RWcharOx0000OxFFFF
##HR_PRODUCT _TAG10RJJcharOx0000OxFFFF

* Check the Table 10 for more information about the device configuration registers.
Table 05 – NP785-05 Model: Configuration Registers Table
The registers 103 to 106, 123 to 126, 157 and 158 must be used by the user to enter the values of their respective parameters. If they are within limits, the device will  automatically pass these values to registers 108 to 111, 132 to 135, 159 and 160, which show the values considered during the operation. In case of extrapolation of limits, this condition will be signaled in register 343 (HR_DIAGNOSE03).
For 32-bit data, the two registers that compose them must be read and/or written in order for the values to be updated.

NP785-05 Model: Information Registers Table
AddressNameDescriptionR/WTypeStandardMin.Max.Decimal Places
300HR_NUM_SERIEHSerial Number High 

RO

 

uint_32

0x00000xFFFFN.A.
301HR_NUM_SERIELSerial Number Low0x00000xFFFFN.A.
302HR_VERSAO_SWFirmware versionROuint160x00000xFFFF2
303HR_RELEASERelease versionROuint160x00000xFFFF0
304HR_IDIDROuint160xB30x00000xFFFFN.A.
305HR_MODELInforms the product modelROuint1600x00000xFFFFN.A.
341HR_DIAGNOSE01Diagnostic**ROuint1600x00000xFFFFN.A.
342HR_DIAGNOSE02ROuint1600x00000xFFFFN.A.
343HR_DIAGNOSE03ROuint1600x00000xFFFFN.A.
359HR_PRESS_HIGH_LIMIT5 mbar
72,52 mpsi
2,007 inH2O
50,98 mmH2O
500,0 Pa
-5 mbar
-72,52 mpsi
-2,007 inH2O
-50,98 mmH2O
-500,0 Pa
5 mbar
72,52 mpsi
2,007 inH2O
50,98 mmH2O
500,0 Pa
mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal places
mmH2O: 2 decimal places
Pa: 1 decimal place
360HR_PRESS_HIGH_LIMIT_HMaximum limitsROuint32
361HR_PRESS_LOW_LIMITMinimum limitsROuint32-5 mbar
-72,52 mpsi
-2,007 inH2O
-50,98 mmH2O
-500,0 Pa
-5 mbar
-72,52 mpsi
-2,007 inH2O
-50,98 mmH2O
-500,0 Pa
5 mbar
72,52 mpsi
2,007 inH2O
50,98 mmH2O
500,0 Pa
mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal places
mmH2O: 2 decimal places
Pa: 1 decimal place
362HR_PRESS_LOW_LIMIT_H

** Check the Table 11 for more information about the device configuration registers.
Table 06 – NP785-05 Model: Information registers

NP785-20 Model: Output Registers Table
AddressNameDescriptionR/WTypeStandardMin.Max.Decimal Places
0HR_PRESSDifferential pressure value

 

RO

 

int_32

 

0

 

 

-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa

 

 

20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa

 

mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal places
mmH2O: 2 decimal places
Pa: 1 decimal place
1

 

HR_PRESS_H

 

2HR_PRESS_MINMinimum differential pressure value logged

 

RO

 

int_32

 

0

 

-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa 
 

20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa

 

mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal places
mmH2O: 2 decimal places
Pa: 1 decimal place
3

 

HR_PRESS

 

4HR_PRESS_MAXMaximum differential pressure value logged

 

RO

 

int_32

 

0

 

-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa 
20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa 
mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal places
mmH2O: 2 decimal places
Pa: 1 decimal place
5

 

HR_PRESS_MAX_H

 

Table 07 – NP785-20 Model:16:30 Output Registers Table

NP785 Model: Configuration Registers Table
AddressNameDescriptionR/WTypeStandardMin.Max.Decimal Places
100HR_SENSOR_TYPESensor type: 5 mbar or 20 mbarROuint16101N.A.
101HR_OUT1_TYPERetransmission output type*RWuint16001N.A.
103HR_OUT1_IN_HIGH_LIMITRetransmission upper limit inputRWint_3220 mbar
290,08 mpsi
8,029 inH2O
203,94  mmH2O
2000,0 Pa
-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa
20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa
mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal places
mmH2O: 2 decimal places
Pa: 1 decimal place
104HR_OUT1_IN_HIGH_LIMIT_H
105HR_OUT1_IN_LOW_LIMITRetransmission lower limit inputRWint_32-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa
-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa
20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa
mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal places
mmH2O: 2 decimal places
Pa: 1 decimal place
106HR_OUT1_IN_LOW_LIMIT_H
107HR_OUT1_ERRError type (higher, lower or low/high)*RWuint16102N.A.
108HR_OUT1_HIGH_LIMITRetransmission upper limitROint_3220 mbar
290,08 mpsi
8,029 inH2O
203,94  mmH2O
2000,0 Pa
-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa
20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa
mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal places
mmH2O: 2 decimal places
Pa: 1 decimal place
109HR_OUT1_HIGH_LIMIT_H
110HR_OUT1_LOW_LIMITRetransmission lower limitROint_32-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94  mmH2O
-2000,0 Pa
-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa
20 mbar
290,08 mpsi
8,029 inH2O
203,94  mmH2O
2000,0 Pa
mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal places
mmH2O: 2  decimal places
Pa: 1 decimal place
111HR_OUT1_LOW_LIMIT_H
113HR_PRESS_FLTRFilter for differential pressure readingRWuint16003000
115HR_UNIT_SYSTEMUnits configuration*RWuint16004N.A.
122HR_A1FUAlarm type*RWuint16505N.A.
 

123

 

HR_A1SPHI_IN

Alarm Setpoint High InputRWint_320 

-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa

 

20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa

mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal places
mmH2O: 2 decimal places
Pa: 1 decimal place
124HR_A1SPHI_IN_H
 

125

 

HR_A1SPLO_IN

Alarm Setpoint Low InputRWint_320-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa
20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa
mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal places
mmH2O: 2 decimal places
Pa: 1 decimal place
126HR_A1SPLO_IN _H
127HR_A1BLAlarm blockRWuint16001N.A.
128HR_A1HYAlarm hysteresisRWuint16004 mbar
58,02 mpsi
1,606 inH2O
40,78 mmH2O
400,0 Pa
mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal places
mmH2O: 2 decimal places
Pa: 1 decimal place
129HR_A1T1Alarm time ONRWuint160065000
130HR_A1T2Alarm time OFFRWuint160065000
131HR_A1IERRDetermines the alarm status in case of sensor errorRWuint16001N.A.
132HR_A1SPHIAlarm Setpoint HighROint_320-20 mbar20 mbarmbar: 3 decimal places
133HR_A1SPHI_H-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa
mpsi: 2 decimal places
inH2O: 3 decimal  places
mmH2O: 2 decimal places
Pa: 1 decimal place
134HR_A1SPLOAlarm Setpoint LowROint_320-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa
20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa
mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal  places
mmH2O: 2  decimal places
Pa: 1 decimal  place
135HR_A1SPLO_H
137HR_BAUDBaud Rate*RWuint16407N.A.
138HR_PRTYParity*RWuint16002N.A.
139HR_ADDRSlave addressRWuint1611247N.A.
146HR_OFST_PRESSDifferential pressure offsetRWuint160-4 mbar
-58,02 mpsi
-1,606 inH2O
-40,78 mmH2O
-400,0 Pa
4 mbar
58,02 mpsi
1,606 inH2O
40,78 mmH2O
400,0 Pa
mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal places
mmH2O: 2 decimal places
Pa: 1 decimal place
152HR_OUT1_FORCE_ENABEnables forcing output 1RWuint16001N.A.
153HR_OUT1_FORCE_VALForced value for output 1RWuint1600,00 V
3,60 mA
10,00 V
21 mA
2
154HR_A1_FORCE_ENABEnables forcing alarm 1RWuint16001N.A.
155HR_A1_STATEChanges forced status on alarmRWuint16001N.A.
156HR_FORCE_IN_PRESSEnables differential pressure forcingRWuint16001N.A.
157HR_FORCE_PRESS_INForced differential pressure value inputRWint_320 

-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa

 

20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa

mbar: 3 decimal places
mpsi: 2 decimal  places
inH2O: 3 decimal places
mmH2O: 2 decimal places
Pa: 1 decimal place
158HR_FORCE_PRESS_IN_H
159HR_FORCE_PRESSForced differential pressure valureROint_320 

-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa

 

20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa

mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal  places
mmH2O: 2 decimal places
Pa: 1 decimal places
160HR_FORCE_PRESS_H
161HR_RESET_MIN_MAXReset all lows and highsRWuint16001N.A.
166HR_PRODUCT_TAG01Equipment tagRW2 char00x00000xFFFFN.A.
167HR_PRODUCT_TAG02RW2 char00x00000xFFFFN.A.
168HR_PRODUCT_TAG03RW2 char00x00000xFFFFN.A.
169HR_PRODUCT_TAG04RW2 char00x00000xFFFFN.A.
170HR_PRODUCT_TAG05RW2 char00x00000xFFFFN.A.
171HR_PRODUCT_TAG06RW2 char00x00000xFFFFN.A.
172HR_PRODUCT_TAG07RW2 char00x00000xFFFFN.A.
173HR_PRODUCT_TAG08RW2 char00x00000xFFFFN.A.
174HR_PRODUCT_TAG09RW2 char00x00000xFFFFN.A.
175HR_PRODUCT_TAG10RW2 char00x00000xFFFFN.A.

* Check the Table 10 for more information about the device configuration registers.
Table 08 – NP785 Model: Configuration Registers Table
The registers 103 to 106, 123 to 126, 157 and 158 must be used by the user to enter the values of their respective parameters. If they are within limits, the device will  automatically pass these values to registers 108 to 111, 132 to 135, 159 and 160, which show the values considered during the operation. In case of extrapolation of limits, this condition will be signaled in register 343 (HR_DIAGNOSE03).
For 32-bit data, the two registers that compose them must be read and/or written in order for the values to be updated.

NP785-20 Model: Information Registers Table
AddressNameDescriptionR/WTypeStandardMin.Max.Decimal Places
300HR_NUM_SERIEHSerial number High 

RO

uint_320x00000xFFFFN.A.
301HR_NUM_SERIELSerial number Low0x00000xFFFFN.A.
302HR_VERSAO_SWFirmware versionROuint160x00000xFFFF2
303HR_RELEASERelease versionROuint160x00000xFFFF0
304HR_IDIDROuint160xB30x00000xFFFFN.A.
305HR_MODELInforms the product modelROuint1600x00000xFFFFN.A.
341HR_DIAGNOSE01Diagnostic**ROuint1600x00000xFFFFN.A.
342HR_DIAGNOSE02ROuint1600x00000xFFFFN.A.
343HR_DIAGNOSE03ROuint1600x00000xFFFFN.A.
 

359

 

HR_PRESS_HIGH_LIMIT

Maximum limitsROuint32 

20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa

-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa
20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa
mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal places
mmH2O: 2 decimal places
Pa: 1 decimal place
360HR_PRESS_HIGH_LIMIT_H
361HR_PRESS_LOW_LIMITMinimum limitsROuint32 

-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa

 

-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa

 

20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa

mbar: 3 decimal places
mpsi: 2 decimal places
inH2O: 3 decimal places
mmH2O: 2 decimal places
Pa: 1 decimal place
362HR_PRESS_LOW_LIMIT_H

** Check the Table 11 for more information about the device configuration registers.
Table 09 – NP785-20 Model: Information Registers
Table 10 lists the device configuration registers and the captions for their respective values:

RegisterNameValueDescription
101HR_OUT1_TYPE0
1
Output 4-20 mA;
Output 0-10 V.
107HR_OUT1_ERR0
1
2
Low alarm in case of failure;
High alarm in case of failure;
Low/high alarm in case of failure.
115HR_UNIT_SYSTEM0
1
2
3
4
Unity: mbar;
Unity: mpsi;
Unity: inH2O;
Unity: mmH2O;
Unity: Pa.
122HR_A1FU0
1
2
3
4
5
Alarm: Off;
Alarm: Sensor Error;
Alarm: Lower Setpoint;
Alarm: Higher Setpoint;
Alarm: Intra-range;
Alarm: Extra-range.
137HR_BAUD0
1
2
3
4
5
6
7
Baud Rate: 1200 bps;
Baud Rate: 2400 bps;
Baud Rate: 4800 bps;
Baud Rate: 9600 bps;
Baud Rate: 19200 bps;
Baud Rate: 38400 bps;
Baud Rate: 57600 bps;
Baud Rate: 115200 bps.
138HR_PRTY0
1
2
Parity: No parity;
Parity: Odd parity;
Parity: Even parity.

Table 11 shows the diagnostic bits:

RegisterNameDescriptionBit
HR_DIAGNOSE01DIAG_RESTART_UNITS_ERRORUnits Configuration error.0
DIAG_OUT1_OVERLOADAlarm output overload detection.1
DIAG_ALM1_OUT_STATUSForced alarm state.3
DIAG_ALM1_STATUSAlarm status.5
DIAG_FORCE_ALM1Forced alarm function is enabled.10
DIAG_FORCE_OUT1Forced output function is enabled.12
HR_DIAGNOSE02DIAG_SENSOR_ERRORDifferential pressure sensor error.0
HR_DIAGNOSE03DIAG_OUT1_LIMIT_OORInput of retransmission limits outside the range.1
DIAG_ALM1_SETPT_OORInput of alarm setpoints outside the range.3
DIAG_FORCE_PRESS_OORInput of pressure forcing values out of range.6
HR_DIAGNOSE04DIAG_UNDER_RANGEIndicates that the lower limit of the range has been exceeded.1
DIAG_OVER_RANGEIndicates that the lower limit of the range has been exceeded.2

NXPERIENCE SOFTWARE

NXperience software is the leading configuration, data download and analysis tool for the NP785 Ultra Low Differential Pressure Transmitter. It allows you to explore all the  device’s features by communicating via the USB interface.
This manual describes the software’s generic features. For instructions about device configuration, check the specific operating manual. The software and its manual can be downloaded from our website www.novusautomation.com, in the Downloads Area.

8.1 INSTALLING NXPERIENCE
To install NXperience, just execute the NXperienceSetup.exe file, available from our website.
8.2 RUNNING NXPERIENCE
When opening NXperience software, the home screen is displayed:

NOVUS NP785 Ultra Low Differential Pressure Transmitter - fig 5

To communicate with the software, the NP785 Ultra Low Differential Pressure Transmitter must be connected to the computer and with the previously installed USB drivers.
Then you can click on Configure or Monitor. The Download option is not available for this device model.
The first time you read a device, you must select the device to be connected. Simply double click on the desired device or, once it is selected, click on the Ok button. This  device will be adopted as the default option for the next times the software performs the communication process.

NOVUS NP785 Ultra Low Differential Pressure Transmitter - fig 6

8.3 CONFIGURING WITH NXPERIENCE
To configure the device, it must be connected to a USB port on the computer.
When clicking on the Configure button, the following screen is displayed:

NOVUS NP785 Ultra Low Differential Pressure Transmitter - fig 7

The Create Configuration button creates a configuration from scratch, without needing the device. This configuration can be saved in a file for future use or can be recorded  to a connected device.
The Open Configuration button reads a configuration file already created.
The Read Device button reads the current device configuration. When selecting this option, all features available for configuration will be displayed, as shown in the Fig. 11: NOVUS NP785 Ultra Low Differential Pressure Transmitter - fig 18

NOVUS NP785 Ultra Low Differential Pressure Transmitter - iconGeneral: On this tab, the user can assign an identification name to the device and define the configuration parameters for the serial interface. Additionally, the device model,  serial number, firmware version and the maximum and minimum pressure range of the sensor can be identified.
NOVUS NP785 Ultra Low Differential Pressure Transmitter - icon 1 Input: On this tab, the user can select the system of measures to be used by the device, in addition to configuring the offset and digital filter for the pressure sensor input.
NOVUS NP785 Ultra Low Differential Pressure Transmitter - icon 2 Output: On this tab, the user can configure the transmission analog output and the alarm output.
NOVUS NP785 Ultra Low Differential Pressure Transmitter - icon 3 Diagnostics: On this tab, the user can check if the device is functioning properly by forcing the pressure readings and forcing the alarm output.
NOVUS NP785 Ultra Low Differential Pressure Transmitter - icon 4 Finalization: On this tab, the user can send the configuration to the device, save the configurations in a file, update the device firmware and configure a password to protect the device.
NOVUS NP785 Ultra Low Differential Pressure Transmitter - icon 5Back: Returns to NXperience home screen.

8.3.1 GENERAL PARAMETERS
By clicking on the NOVUS NP785 Ultra Low Differential Pressure Transmitter - iconicon, you can view information of the device being configured and the serial interface configuration parameters.NOVUS NP785 Ultra Low Differential Pressure Transmitter - fig 8

In the Device Tag parameter, you can name the device to be configured to make it easily identifiable within a multi-device network. Serial Number, Firmware Version, and  Model are non-editable parameters that are read by the software and directly from the device.
In order for the NP785 Ultra Low Differential Pressure Transmitter to be recognized as a slave device in a Modbus network, you must assign a unique Modbus Address in the network and configure the Baud Rate and Parity.

8.3.2 INPUT PARAMETERS
By clicking on theNOVUS NP785 Ultra Low Differential Pressure Transmitter - icon 1 icon, you can configure the pressure sensor input.NOVUS NP785 Ultra Low Differential Pressure Transmitter - fig 9

In the Unit parameter, you can select the units mbar, Mpsi, in H2O, mm H2O or pascal. By default, the unit of device is set to mbar.
The Pressure parameter informs the differential pressure of the device when the window opens.
The device also provides Offset and Filter adjustments, allowing not only small corrections to the sensor readings, but also to reduce the speed of response of the sensor.
The Automatic Zero configuration allows automatic offset adjustments. Make sure the pressure points are depressurized and click NOVUS NP785 Ultra Low Differential Pressure Transmitter - icon 6to make the adjustment.

8.3.3 OUTPUT PARAMETERS
By clicking on theNOVUS NP785 Ultra Low Differential Pressure Transmitter - icon 2  icon, you can configure the transmission analog output and the alarm output.

NOVUS NP785 Ultra Low Differential Pressure Transmitter - fig 10

8.3.3.1 TRANSMISSION OUTPUT CONFIGURATION

NOVUS NP785 Ultra Low Differential Pressure Transmitter - fig 11

The Measurement parameter allows the differential pressure quantity reading.
The analog output Mode allows you to select the electrical standard to be used for the transmission: 0-10 V or 4-20 mA. The electrical signal of the output will be  proportional to the selected magnitude, respecting the values configured in the Lower Limit and in the Upper Limit parameters.
In case of sensor failure, the quantity to be transmitted by the analog output will go into Error Mode. For the error condition, you must select the High, Low or Low-High state (check Table 03).

8.3.3.2 ALARM OUTPUT CONFIGURATION
To select the alarm output to be configured, you must click on the button NOVUS NP785 Ultra Low Differential Pressure Transmitter - icon 7 and enable it by sliding the enable switch to the right.

NOVUS NP785 Ultra Low Differential Pressure Transmitter - fig 12

The alarm output may be timed by the Time On and Time Off parameters.
If the equipment is configured in the Value Lower than SPLo, Value Higher than SPHi, Inside the Range or Outside the Range modes, the Error Condition parameter allows  you to configure a safe state of the alarm output in case of sensor failure. Thus, the output will be on or off depending on the value set in this parameter.
Upper Limit and Lower Limit are the differential pressure values that act as alarm activation conditions that, together with the Hysteresis, define the barrier to be exceeded so  that the channel exits the alarm situation. For more information about the alarm configuration, check the Alarm Configuration section.

8.3.4 DIAGNOSTICS
To access this section, the device must be connected to the USB port and the Read Configuration option must be selected.
By clicking on the icon, you can check if the device is functioning properly by forcing the pressure readings. You can force a value either on the sensor reading or directly on the output.

NOVUS NP785 Ultra Low Differential Pressure Transmitter - fig 13

In the input diagnostics, you can view the differential pressure instantaneous value and force a value to it. To force a value, you must type the desired value in the field or run  the slider to the desired value within the model pressure range and press the button.
In the output diagnostics, you can force the output in order to verify the correct operation of the device and test the settings applied to the NP785 Differential Pressure Transmitter.NOVUS NP785 Ultra Low Differential Pressure Transmitter - fig 14

To force a value at a transmission analog output, use the slider or type de desired value directly into the edit field and then press the buttonNOVUS NP785 Ultra Low Differential Pressure Transmitter - icon 8.
From this moment, the NP785 Ultra Low Differential Pressure Transmitter will force the adjusted value into the transmission output and the button used to perform the  forcing will change toNOVUS NP785 Ultra Low Differential Pressure Transmitter - icon 9. If pressed again, the forced value will no longer be applied to the output.

NOVUS NP785 Ultra Low Differential Pressure Transmitter - fig 15For each analogue output, it is also possible to force the transmission of an error value by clicking theNOVUS NP785 Ultra Low Differential Pressure Transmitter - icon 11 andNOVUS NP785 Ultra Low Differential Pressure Transmitter - icon 10 buttons. These values depend on the mode (0-10 V or 4-20 mA) configured for each output.
The alarm output allows forcing the condition on and off. In some cases, it is possible that an alarm output is activated due to an alarm condition.
Thus, it may be desirable to force the off state so that it is possible to identify any faults in the electrical installation or in the device configuration.
The images below shows the forcing interface of the alarm output in the three possible conditions: No forcing, forcing on ON and forcing in OFF state.

NOVUS NP785 Ultra Low Differential Pressure Transmitter - fig 16

8.3.5 FINALIZATION
By clicking on theNOVUS NP785 Ultra Low Differential Pressure Transmitter - icon 4 icon, you can send the configuration to the device, save the configurations in a file, update the device firmware and configure a password to protect it.

NOVUS NP785 Ultra Low Differential Pressure Transmitter - fig 17

TECHNICAL SPECIFICATION

NP785-05 MODELNP785-20 MODEL
Measuring Range-5 to 5 mbar-20 to 20 mbar
Burst Pressure200 mbar400 mbar
Proof Pressure*100 mbar300 mbar
Accuracy1 % of maximum range F.S.**1 % of maximum range F.S.**
 

 

Sensor  Resolution (per unit)

7.630E-4 mbar3.052E-3 mbar
1.107E-2 mpsi4.426E-2 mpsi
3.063E-4 inH2O1.226E-3 inH2O
7.780E-3 mmH2O3.112E-2 mmH2O
7.630E-2 Pa3.052E-1 Pa
Granularity of Pressure Recorders (per unit)0.001 mbar0.001 mbar
0.01 mpsi0.01 mpsi
0.001 inH2O0.001 inH2O
0.01 mmH2O0.01 mmH2O
0.1 Pa0.1 Pa
Start-Up Time< 2 s
Operating Temperature-5 to 65 °C-20 to 85 °C
Storage Temperature-20 to 85 °C
 

Power Supply Voltage

·   Power supply from PWR terminals: 12 Vdc to 30 Vdc;
·   USB cable power: 4.75 Vdc to 5.25 Vdc.
Internal protection against reverse polarity of the supply voltage.
Power Supply Current< 45 mA ± 10 % @ 24 Vdc
InputTwo sockets for the pneumatic hose connection of 4 or 6 mm internal diameter.
OutputThey may be configured independently to operate with signals 0-10 V or 4-20 mA.
· 0-10 V
o Maximum current: 2 mA;
o Resolution: 0.003 V.
· 4-20 mA
o Maximum load: 500 R;
o Resolution: 0.006 mA.
Protection RatingIP 20
HousingABS + PC
Electromagnetic CompatibilityEN/IEC 61326-1
 

NXperience

10, 8 / 8.1 (32 and 64 bits), 7, Vista and XP. configurator software. Menus in Portuguese, Spanish, French and English.
CertificationsCE MARK
This is a Class A product. In a domestic environment, this product may cause radio interference in which case the user may be required to take adequate measures.

* Proof Pressure is defined as the maximum pressure at which the device can be subjected and which still maintains its performance within specifications after returning to the operating range.
** F.S .: Full scale at 25 °C.
Table 12 – Technical Specifications

WARRANTY

Warranty conditions are available on our website www.novusautomation.com/warranty.

NOVUS logo

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals