Delta Dvp04pt06pt-s Temperature Measurement Instructions

Delta Dvp04pt06pt-s Temperature Measurement Instructions

DELTA-DVP04PT06PT-S-Temperature-Measurement-LOGO

DELTA DVP04PT06PT-S Temperature Measurement

DELTA-DVP04PT06PT-S-Temperature-Measurement-PRODUCT

Thank you for choosing Delta DVP series PLC. DVP04/06PT-S is able to receive 4/6 points of RTDs and convert them into 16-bit digital signals. Through FROM/TO instructions in DVP Slim series MPU program, the data can be read and written. There are many 16-bit control registers (CR) in modules. The power unit is separate from it and is small in size and easy to install.
DVP04/06PT-S is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity, electric shock and vibration. To prevent non-maintenance staff from operating DVP04/06PT-S, or to prevent an accident from damaging DVP04/06PT-S, the control cabinet in which DVP04/06PT-S is installed should be equipped with a safeguard. For example, the control cabinet in which DVP04/06PT-S is installed can be unlocked with a special tool or key.

  • DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring again before DVP04/06PT-S is powered up. After
  • DVP04/06PT-S is disconnected, Do NOT touch any terminals in a minute. Make sure that the ground terminalDELTA-DVP04PT06PT-S-Temperature-Measurement-FIG-1 on
  • DVP04/06PT-S is correctly grounded in order to prevent electromagnetic interference.

Product Profile & DimensionDELTA-DVP04PT06PT-S-Temperature-Measurement-FIG-2DELTA-DVP04PT06PT-S-Temperature-Measurement-FIG-3

  • I/O Terminal LayoutDELTA-DVP04PT06PT-S-Temperature-Measurement-FIG-4

External WiringDELTA-DVP04PT06PT-S-Temperature-Measurement-FIG-5

  • Note1: Use only the wires that are packed with the temperature sensor for analog input and separate them from other power line or any wire that may cause noise.
    Note 2: 3-wire RTD sensor provides a compensation loop that can be used to subtract the wire resistance while 2-wire RTD sensor has no mechanism to compensate. Use cables (3-wired) with the same length (less than 200 m) and wire resistance of less than 20 ohm.
  • Note3: If there is noise, please connect the shielded cables to the system earth point, and then ground the
    system earth points or connect it to the distribution box.
    Note 4: Please keep wires as short as possible when connecting the module to a device whose temperature is going to be measured, and keep the power cable used as far away from the cable connected to a load as possible to prevent noise interference.
  • Note 5: Please connect a power supply module and on the temperature module to a system
    ground, and then ground the system ground or connect the system ground to a distribution box.

Electrical Specifications

Max. rated power consumption2W
Operation/storageOperation: 0°C~55°C (temp.), 5~95% (humidity), pollution degree 2

Storage: -25°C~70°C (temp.), 5~95% (humidity)

Vibration/shock resistanceInternational standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea)
 

Series connection to DVP-PLC MPU

The modules are numbered from 0 to 7 automatically by their distance from MPU. No.0 is the closest to MPU and No.7 is the furthest. Maximum

8 modules are allowed to connect to MPU and will not occupy any digital I/O points.

Functional Specifications

DVP04/06PT-SCelsius (°C)Fahrenheit (°F)
Analog input channel4/6 channels per module
Sensors type2-wire/3-wire Pt100 / Pt1000 3850 PPM/°C (DIN 43760 JIS C1604-1989)

/ Ni100 / Ni1000 / LG-Ni1000 / Cu100 / Cu50/ 0~300Ω/ 0~3000Ω

Current excitation1.53mA / 204.8uA
Temperature input rangePlease refer to the temperature/digital value characteristic curve.
Digital conversion rangePlease refer to the temperature/digital value characteristic curve.
Resolution0.1°C0.18°F
Overall accuracy±0.6% of full scale during 0 ~ 55°C (32 ~ 131°F)
Response timeDVP04PT-S: 200ms/channel; DVP06PT-S: 160/ms/channel
Isolation method

(between digital and analog circuitry)

There is no isolation between channels.

500VDC between digital/analog circuits and Ground 500VDC between analog circuits and digital circuits 500VDC between 24VDC and Ground

Digital data format2’s complement of 16-bit
Average functionYes (DVP04PT-S: CR#2 ~ CR#5 / DVP06PT-S: CR#2)
Self diagnostic functionEvery channel has the upper/lower limit detection function.
RS-485 Communication ModeSupported, including ASCII/RTU mode. Default communication format: 9600, 7, E, 1, ASCII; refer to CR#32 for details on the communication format.

Note1: RS-485 cannot be used when connected to CPU series PLCs. Note2: Refer to Slim Type Special Module Communications in the appendix E of the DVP programming manual for more details on RS-485 communication setups.

The unit of temperature would be displayed as 0.1°C/0.1°F. If the temperature unit is set to be Fahrenheit, the second decimal place would not be shown.

Control Register

CR#AddressLatchedAttributeRegister contentDescription
#0H’4064ORModel name

(Set up by the system)

DVP04PT-S model code= H’8A DVP06PT-S model code = H’CA
 

 

 

 

 

 

 

 

#1

 

 

 

 

 

 

 

 

H’4065

 

 

 

 

 

 

 

 

X

 

 

 

 

 

 

 

 

R/W

 

 

 

 

 

 

 

 

CH1~CH4 Mode setting

b15~12b11~8b7~4b3~0
CH4CH3CH2CH1
Take CH1 mode (b3,b2,b1,b0) for example.

1. (0,0,0,0): Pt100 (default)

2. (0,0,0,1): Ni100

3. (0,0,1,0): Pt1000

4. (0,0,1,1): Ni1000

5. (0,1,0,0): LG-Ni1000

6. (0,1,0,1): Cu100

7. (0,1,1,0): Cu50

8. (0,1,1,1): 0~300 Ω

9. (1,0,0,0): 0~3000 Ω

10. (1,1,1,1)The channel is disabled.

Mode 8 and 9 are only available for DVP04PT-S V4.16 or later and DVP06PT-S V4.12 or later.

 

 

 

 

#2

 

 

H’4066

 

 

 

 

O

 

 

 

 

R/W

 

DVP04PT-S:

CH1 average number

Number piece of readings used for the calculation of “average” temperature on CH1.

Setting range: K1~K20. Default setting is K10.

 

 

 

DVP06PT-S:

CH1~CH6 average number

Number piece of readings used for the calculation of “average” temperature on CH1 ~ 6.

Setting range: K1~K20. Default setting is K10.

 

 

#3

 

 

H’4067

 

 

O

 

 

H’4067

 

DVP04PT-S:

CH2 average number

Number piece of readings used for the calculation of “average” temperature on CH2.

Setting range: K1~K20. Default setting is K10.

 

 

#4

 

 

H’4068

 

 

O

 

 

H’4068

 

DVP04PT-S:

CH3 average number

Number piece of readings used for the calculation of “average” temperature on CH3.

Setting range: K1~K20. Default setting is K10.

 

 

#5

 

 

H’4069

 

 

O

 

 

H’4069

 

DVP04PT-S:

CH4 average number

Number piece of readings used for the calculation of “average” temperature on CH4.

Setting range: K1~K20. Default setting is K10.

#6H’406AXRCH1 average degreesDVP04PT-S:

Average degrees for CH1 ~ 4 DVP06PT-S:

Average degrees for CH1 ~ 6 Unit: 0.1°C, 0.01 Ω (0~300 Ω),

0.1 Ω (0~3000 Ω)

#7H’406BXRCH2 average degrees
#8H’406CXRCH3 average degrees
#9H’406DXRCH4 average degrees
#10XRCH5 average degrees
#11XRCH6 average degrees
#12H’4070XRCH1 average degreesDVP04PT-S:

Average degrees for CH1 ~ 4 DVP06PT-S:

Average degrees for CH1 ~ 6 Unit: 0.1°C, 0.01 Ω (0~300 Ω),

0.1 Ω (0~3000 Ω)

#13H’4071XRCH2 average degrees
#14H’4072XRCH3 average degrees
#15H’4073XRCH4 average degrees
#16XRCH5 average degrees
#17XRCH6 average degrees
#18H’4076XRPresent temp. of CH1DVP04PT-S:

Present temperature of CH 1~4

#19H’4077XRPresent temp. of CH2
CR#AddressLatchedAttributeRegister contentDescription
#20H’4078XRPresent temp. of CH3DVP06PT-S:

Present temperature of CH1~6 Unit: 0.1°C, 0.01 Ω (0~300 Ω),

0.1 Ω (0~3000 Ω)

#21H’4079XRPresent temp. of CH4
#22XRPresent temp. of CH5
#23XRPresent temp. of CH6
#24H’407CXRPresent temp. of CH1 

DVP04PT-S:

Present temperature of CH 1~4 DVP06PT-S:

Present temperature of CH 1~6 Unit: 0.1°C, 0.01 Ω (0~300 Ω),

0.1 Ω (0~3000 Ω)

#25H’407DXRPresent temp. of CH2
#26H’407EXRPresent temp. of CH3
#27H’407FXRPresent temp. of CH4
#28XRPresent temp. of CH5
#29XRPresent temp. of CH6
 

#29

 

H’4081

 

X

 

R/W

 

DVP04PT-S:

PID mode setup

Set H’5678 as PID mode and other values as normal mode

Default value is H’0000.

 

#30

 

H’4082

 

X

 

R

 

Error status

Data register stores the error status. Refer to the error code chart for details.
 

 

#31

 

H’4083

 

O

 

R/W

DVP04PT-S:

Communication address setup

Set up the RS-485 communication address; setting range: 01~254. Default: K1
 

 

X

 

R/W

DVP06PT-S:

CH5~CH6 Mode setting

CH5 mode: b0 ~ b3 CH6 mode: b4 ~ b7 See CR#1 for reference
 

 

 

 

 

 

 

 

 

32

 

 

 

 

 

 

H’4084

 

 

 

 

 

 

O

 

 

 

 

 

 

R/W

 

 

 

 

 

DVP04PT-S:

Communication format setting

For baud rate, the settings are 4,800/9,600/19,200/38,400/57,600/

115,200 bps.

Communication format:

ASCII: 7,E,1 / 7,O,1 / 8,E,1 / 8,O,1 / 8,N,1

RTU: 8,E,1 / 8,O,1 / 8,N,1

Factory default : ASCII,9600,7,E,1 (CR#32=H’0002)

Refer to ※CR#32 communication

format settings at the end of this

table for more information.

 

 

 

 

 

 

X

 

 

 

R/W

 

 

DVP06PT-S: CH5~CH6

Error LED indicator setting

b15~12b11~9b8~6b5~3b2~0
ERR LEDreservedCH6CH5
b12~13 correspond to CH5~6, when bit is ON, the scale exceeds

the range, and the Error LED indicator flashes.

 

 

 

 

 

 

#33

 

 

H’4085

 

 

O

 

 

R/W

DVP04PT-S: CH1~CH4

Reset to default setting And Error LED indicator setting

b15~12b11~9b8~6b5~3b2~0
ERR LEDCH4CH3CH2CH1
If b2~b0 are set to 100, all the setting values of CH1 will be reset to the defaults. To reset all channels to defaults, set b11~0 to H’924 (DVP04PT-S supports single and all channels reset; DVP06PT-S supports all channels reset only). b12~15 correspond to CH1~4, when bit is ON, the scale exceeds

the range, and the Error LED indicator flashes.

 

 

 

 

 

 

X

 

 

 

R/W

 

 

DVP06PT-S:

CH1~CH4 Reset to default setting And CH1~CH4 Error LED indicator setting

#34H’4086ORFirmware versionDisplay version in hexadecimal. ex: H’010A = version 1.0A
#35 ~ #48 For system use
Symbols: O means latched. (Supported with RS485, but does not support when connecting to MPUs.) X means not latched. R means can read data by using FROM instruction or RS-485.

W means can write data by using TO instruction or RS-485.

  1. Added the RESET function is only for 04PT-S modules with firmware V4.16 or later and not available for 06PT-S. Connect the module power input to 24 VDC and write H’4352 into CR#0 and then turn the power off and on again; all parameters in modules, including communication parameters are restored to factory defaults.
  2. If you want to use Modbus address in decimal format, you can transfer a hexadecimal register to decimal format and then add one to have it become a decimal Modbus register address. For example transferring the address “H’4064” of CR#0 in hexadecimal format to decimal format, to have the result 16484 and then adding one to it, you have 16485, the Modbus address in decimal format.
  3. CR#32 communication format settings: for DVP04PT-S modules with firmware V4.14 or previous versions, b11~b8 data format selection is not available. For ASCII mode, the format is fixed to 7, E, 1 (H’00XX) and for RTU mode, the format is fixed to 8, E, 1 (H’C0xx/H’80xx). For modules with firmware V4.15 or later, refer to the following table for setups. Note that the original code H’C0XX/H’80XX will be seen as RTU, 8, E, 1 for modules with firmware V4.15 or later.
b15 ~ b12b11 ~ b8b7 ~ b0
ASCII/RTU,

exchange low and high byte of CRC check code

 

Data format

 

Baud rate

Description
H’0ASCIIH’07,E,1*1H’014800 bps
 

H’8

RTU,

do not exchange low and

high byte of CRC check code

H’18,E,1H’029600 bps
H’2reservedH’0419200 bps
 

H’C

RTU,

exchange low and high byte of CRC check code

H’38,N,1H’0838400 bps
H’47,O,1*1H’1057600 bps
 H’58.O,1H’20115200 bps
  • Note *1: This is only available for ASCII format.
  • Ex: Write H’C310 into CR#32 for a result of RTU, exchange low and high byte of CRC check code, 8,N,1 and baud rate at 57600 bps.
  • RS-485 function codes: 03’H is for reading data from registers. 06’H is for writing a data word to registers. 10’H is for writing multiple data words to registers.
  • CR#30 is the error code register.

Note: Each error code will have a corresponding bit and should be converted to 16-bit binary numbers (Bit0~15). Two or more errors may happen at the same time. Refer to the chart below:

Bit number0123
 

Description

Power source abnormalThe contact is not connected to

anything.

 

Reserved

 

Reserved

Bit number4567
DescriptionReservedReservedaverage number errorInstruction error
Bit number891011
DescriptionCH1 Abnormal conversionCH2 Abnormal conversionCH3 Abnormal conversionCH4 Abnormal conversion
Bit number12131415
DescriptionCH5 Abnormal conversionCH6 Abnormal conversionReservedReserved
  1. Temperature/Digital Value Characteristic Curve

The mode of measuring Celsius (Fahrenheit) temperature:DELTA-DVP04PT06PT-S-Temperature-Measurement-FIG-6

SensorTemperature rangeDigital value conversion range
°C (Min./Max.)°F (Min./Max.)°C (Min./Max.)°F (Min./Max.)
Pt100-180 ~ 800°C-292 ~ 1,472°FK-1,800 ~ K8,000K-2,920 ~ K14,720
Ni100-80 ~ 170°C-112 ~ 338°FK-800 ~ K1,700K-1,120 ~ K3,380
Pt1000-180 ~ 800°C-292 ~ 1,472°FK-1,800 ~ K8,000K-2,920 ~ K14,720
Ni1000-80 ~ 170°C-112 ~ 338°FK-800 ~ K1,700K-1,120 ~ K3,380
LG-Ni1000-60 ~ 200°C-76 ~ 392°FK-600 ~ K2,000K-760 ~ K3,920
Cu100-50 ~ 150°C-58 ~ 302°FK-500 ~ K1,500K-580 ~ K3,020
Cu50-50 ~ 150°C-58 ~ 302°FK-500 ~ K1,500K-580 ~ K3,020
SensorInput resistor rangeDigital value conversion range
0~300Ω0Ω ~ 320ΩK0 ~ 320000~300Ω0Ω ~ 320Ω
0~3000Ω0Ω ~ 3200ΩK0 ~ 320000~3000Ω0Ω ~ 3200Ω
  1. When CR#29 is set to H’5678, CR#0 ~ CR#34 can be used for PID settings with DVP04PT-S version V3.08 and above.
PID Mode description
CR#KeepR/W CR#KeepR/W 

 

#0ORModel name#24OR/WCH1 KD
#1XR/WCH1~CH4 Mode setting#25OR/WCH2 KD
#2XRPID Output % at CH1#26OR/WCH3 KD
#3XRPID Output % at CH2#27OR/WCH4 KD
#4XRPID Output % at CH3   Run/Stop & Auto tuning

 

Bit0:CH1 PID Run/Stop Bit1:CH2 PID Run/Stop Bit2:CH3 PID Run/Stop Bit3:CH4 PID Run/Stop 0=PID Stop,1=PID Run

 

Bit4:CH1 Auto tuning Bit5:CH2 Auto tuning Bit6:CH3 Auto tuning Bit7:CH4 Auto tuning

1: The auto tuning function is enabled. After the auto tuning is complete, the value becomes 0.

#5XRPID Output % at CH4   
CR#2~CR#5: 0~1000; Unit: 0.1%   
#6XRAverage temperature (0C) at CH1   
#7XRAverage temperature (0C) at CH2   
#8XRAverage temperature (0C) at CH3   
#9XRAverage temperature (0C) at CH4#28XR/W
CR#6~CR#9:Unit: 0.1%   
#10OR/WSet temperature at CH1   
#11OR/WSet temperature at CH2   
#12OR/WSet temperature at CH3   
#13OR/WSet temperature at CH4   
CR#10~CR#13: Set the PID target value (SV)   
#14OR/WCH1 KP 

#29

 

X

 

R/W

 

Enter PID mode(H’5678) K0: Exit the PID mode

#15OR/WCH2 KP
#16OR/WCH3 KP#30XRError code
#17OR/WCH4 KP#31OR/WCH1 Sampling time
#19OR/WCH1 KI#32OR/WCH2 Sampling time
#20OR/WCH2 KI#33OR/WCH3 Sampling time
#21OR/WCH3 KI#34OR/WCH4 Sampling time
#22OR/WCH4 KICR#31~CR#34: 1~30; Unit: 1s
Note: CR#29 must be set to H’5678 so as to enter the PID mode before configuring settings on other control registers.

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals