Ako-14545 Controller For Compressor And Condenser Station User Guide

Ako-14545 Controller For Compressor And Condenser Station User Guide

AKO logo

14545 Controller For Compressor and Condenser Station
User GuideAKO 14545 Controller For Compressor and Condenser Station

AKO-14545
AKO-14545-C

Warnings

-If the equipment is used without adhering to the manufacturer’s instructions the device safety requirements could be compromised. -The installation location of the equipment must be protected from vibrations, water, and corrosive gases where the ambient temperature does not exceed the value featured in the technical data.
-To ensure a correct reading the probe must be located away from external effects.
-The power circuit should be equipped with a switch for its disconnection of at least 2 A, 230 V, situated near the appliance. The cables will be fed in from the rear and will be typed H05VV-F or H05V-K.
-The section to be used will depend on the local standard in force, however, must never be less than 1 mm.
-The wiring cables for the contact relays must have a section of 2.5 mm.
-Make the connection before plugging in the terminals to the equipment (See Fig. A).
ATTENTION: The equipment is not compatible with AKO-14917 (external communication module) and AKO-14918 (programming key).

InstallationAKO 14545 Controller For Compressor and Condenser Station - fig 9Quick start

AKO 14545 Controller For Compressor and Condenser Station - fig

By using keys Up Buttons and Down Buttons select the most suitable option according to the installation type in accordance with the table in the “WIZARD” appendix and press SET. The wizard configures the equipment parameters and assigns the input and output functions according to the installation type chosen.AKO 14545 Controller For Compressor and Condenser Station - fig 1

Select the refrigerant gas type used from amongst the following options:
0=R134a 1=R404a 2=R717a 3=R22 4=R410a 5=R507a 6=R744 7=R407a 8=R407f 9=R1234y
10=R448a 11=R449a 12=R450a 13=R454A 14=R454C 15=R455A 16=R1234ze 17=R515b 18=R452A 19=R452bAKO 14545 Controller For Compressor and Condenser Station - fig 2

Select the primary and secondary display units from amongst the following options:
0=bar-ºC; 1=psi-ºF; 2=psi-ºC; 3=bar-ºF; 4=ºC-bar; 5=ºF-psi; 6=ºC-psi; 7=ºF-barAKO 14545 Controller For Compressor and Condenser Station - fig 4

Configure the rest of the parameters to their default value? :
0=No, the configuration is kept for all the parameters except for C01, C02, C04, C05 C06, C08, and C09.
1=Yes, all the parameters are configured to their default value (see parameters table)
(This option does not affect parameters C01, C02, C04, C05 C06, C08, and C09)

“WIZARD” table

The “WIZARD” table in the appendix is divided into 3 groups of columns. The first describes the different installation types (number of compressors and fans, if they have an inverter, etc.) associated with the INI option.
The second group specifies the function assigned to each relay depending on the INI option selected.
The third group specifies the function assigned to each digital input depending on the INI option selected.
Installation typeAKO 14545 Controller For Compressor and Condenser Station - fig 7

Relay functionAKO 14545 Controller For Compressor and Condenser Station - fig 5

Input functionAKO 14545 Controller For Compressor and Condenser Station - fig 6

*The meaning of each function is described in the “WIZARD” appendix

Operation

ESC key
In the programming menu, exit the parameter without saving changes, return to the previous level, or exit programming.
SET key
By pressing this key for 1 second the probe display units change (according to parameter C09).
Pressing it for 10 seconds accesses the programming menu.
In the programming menu, it accesses the level shown on the display or, during the setting of a parameter accepts the new value.
Up Buttons UP key
By pressing this key for 1-second probe 2 is displayed for 5 seconds (or probe 1, according to parameter P02). By pressing a second time the probe ambient temperature value will be shown (only if I07 or I08=3).
In the programming menu, it allows scrolling around the different levels, or during the setting of a parameter, changing its value.
Down Buttons DOWN key
Pressing this key returns the equipment to its normal operation after an alarm that requires a reset (the causes which triggered the alarm must have disappeared).
In the programming menu, it allows scrolling around the different levels, or during the setting of a parameter, changing its value.AKO 14545 Controller For Compressor and Condenser Station - fig 8

Operation start-up

Upon being supplied with power the equipment will start up in WIZARD mode (INI / 1 flashing), press Up Buttons or Down Buttons to select the most suitable option for the installation type, and check the options in the “WIZARD” appendix.
The wizard configures the equipment parameters and assigns the input and output functions according to the installation type chosen.

Technical specifications

Power supply . . . . . . . . . . . . . . . . . . . 90-240 V~ 50/60 Hz
Maximum voltage in the SELV circuits . . . . . . . . . . . . . . 20 V
Inputs . . . . . . . . . . . . . . . . 2 analog inputs + 6 digital inputs
Relays R1 to R4 . . . . . . . . (EN60730-1: 5(4) A 250 V~ SPST)
Relay R5 . . . . . . . . . . . . . (EN60730-1: 5(4) A 250 V~ SPDT)
No. of relay operations . .  . . . . . . . . EN60730-1: 100.000 operations
Types of probes . . . . . . . . . . . . . . . . . . . . NTC AKO-149xx
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20 mA
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0-5 V ratiometric
Measuring range
NTC . . . . . . . . . -50,0 ºC to +99,9 ºC (-58,0 ºF to 211 ºF)
4-20 mA / 0-5 V . . . . . . . . . . . . . . . . . . . . . . -60 to 999
Resolution
NTC . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.1 ºC (0.1 ºF)
4-20 mA / 0-5 V -99.9 to 99.9. . . . . . . . . . . . . . . 0.1
≤-100 / ³ 100 . . . . . . . . . . . . . . 1
Working environment . . . . . . . -10 to 50 ºC, moisture <90 %
Storage environment . . . . . . . . -30 to 70 ºC, moisture <90 %
Protection degree of the front part . . . . . . . . . . . . . . . . IP65
Fixing . . . . . . . . . . . . . . . . . . . Panel mounting with anchors
Panel cavity dimensions . . . . . . . . . . . . . . . . . . . 71 x 29 mm
Front part dimensions . . . . . . . . . . . . . . . . . . . . 79 x 38 mm
Depth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 mm
Connections:
Terminal to screw for cables with a section of up to 2.5 mm Control device classification: Built-in assembly, with Type 1.B automatic operation action feature, for use in clean situations, logical support (Software) class A and continuous operation. Degree of contamination 2 acc. to UNE-EN 60730-1. Double power input insulation, secondary circuit, and relay output.
Rated pulse voltage . . . . . . . . . . . . . . . . . . . . . . . . . 2500 V
Pressure ball test temperature:
Accessible parts . . . . . . . . . . . . . . . . . . . . . . . . . . 75 ºC
Parts that position active elements . . . . . . . . . . . . 125 ºC
Voltage and current declared by the EMC tests:  . . . . . . . . . . 207 V, 17 mA
Radio interference suppression test current . . . . . . . . . 270 mA

Table of parameters and messages

The Def. column indicates the ex-works configured default parameters. The pressure values featured on the table are expressed in bar and those for temperature in ºC. If the wizard meanwhile selects another set of units (parameter C09), the equipment will make the conversion automatically.

INSTALLATION CONFIGURATION

AKO 14545 Controller For Compressor and Condenser Station - fig10

EVAPORATION CONFIGURATION AKO 14545 Controller For Compressor and Condenser Station - fig11

CONDENSATION CONFIGURATIONAKO 14545 Controller For Compressor and Condenser Station - fig13

CONDENSATION CONFIGURATION
AKO 14545 Controller For Compressor and Condenser Station - fig12

PROBE CONFIGURATION Units AKO 14545 Controller For Compressor and Condenser Station - fig13

DIGITAL INPUT CONFIGURATIONAKO 14545 Controller For Compressor and Condenser Station - fig 14

ENERGY-SAVING CONFIGURATION

Description
Start of energy-saving – Day of the week:  =Deactivated 1=Monday 2=Tuesday
UnitsMin.Def.Max.
ESS013=Wednesday
4=Thursday
5=Friday
6=Saturday
9=Monday to Saturday
10=Monday to Friday
7=Sunday 8=Monday
11=Saturday to Sunday
to Sunday0011
S02Start of the energy-saving – Hour (see remark 2)h.0023
S03Start of the energy-saving – Minute (see remark 2)min.0059
S04Duration of the energy-saving (see remark 2)h.0024

TIMING CONFIGURATION

DescriptionUnitsMin.Def.Max.
AKO 14545 Controller For Compressor and Condenser Station - icont01Minimum operation time for a compressorsec. x1012999
t02Minimum disconnection time for a compressor **sec. x1012999
t03Delay time between the compressor start-up/stage and the next onesec.130999
t04Delay time between the compressor stop/stage and the next onesec.110999
t05Minimum operation time for a fansec. x1011999
t06Minimum disconnection time for a fansec. x1011999
t07Delay time between the fan start-up and the next onesec.12999
t08Delay time between the fan stop and the next onesec.12999
EPOutput to level 1

CONFIGURATION OF PROTECTIONS AND ALARMS

DescriptionUnitsMin.Def.Max.
 

AKO 14545 Controller For Compressor and Condenser Station - icon 1

A01Number of active compressor stages with error in probe 100
A02Number of active fans or inverter % with error in probe 2Without inverter0C05C05
With inverter0100%100%
A03Low-pressure alarm in probe 1bar-0.7075
A04Low-pressure alarm differentialbar0.11.020
A05High-pressure alarm in probe 2bar-0.72075
A06High-pressure alarm differentialbar0.11.020
A07Alarm delay after reaching the valuesec.060999
A08Delay of temperature alarms in the start-up.sec.00255
A09High-pressure alarm limit (per digital input) per hour without a manual reset.
(If I07 or I08=1) (0=deactivated) Once the limit has been exceeded a manual reset will be required for each new alarm.
 

0

 

0

 

255

DATE AND TIME CONFIGURATION

DescriptionUnitsMin.Def.Max.
AKO 14545 Controller For Compressor and Condenser Station - icon 3r01Hour000023
r02Minutes000059
r03Day1131
r04Month1112
r05Year001599

ACCESS AND INFORMATION CONTROL

DescriptionUnitsMin.Def.Max.
P5Address for units with communication11255
L5Access code (Password)00999
PUProgram version
PrCheck

OPERATION TIMES

DescriptionUnitsMin.Def.Max.
 

AKO 14545 Controller For Compressor and Condenser Station - icon 2

 

c1This shows the operation time for the compressor or fan 1hours x10999
c2This shows the operation time for the compressor or fan 2hours x10999
c3This shows the operation time for the compressor or fan 3hours x10999
c4This shows the operation time for the compressor or fan 4hours x10999
c5This shows the operation time for the compressor or fan 5hours x10999
EPOutput to level 1

Programming output
* Depending on the compressor control type: Proportional=E01; Neutral zone=E01-E06. ** If the compressor is equipped with an inverter, this period of time halves. *** The number of stages depends on the configuration selected in the wizard. Remark 1: The equivalent value in pressure is calculated depending on the refrigerant gas
specified in the wizard. Remark 2: In the event of the energy-saving and the variation in the set point per digital input being activated at the same time, the variation in the set point per digital input will always prevail.

AKO 14545 Controller For Compressor and Condenser Station - fig 5Access code (Password) requestD
Pump down detained due to timeD
Clock battery dead or clock deprogrammedD
Low-pressure alarm due to probe 1DR
High-pressure alarm due to probe 2DR
Thermal alarm 1DR
Thermal alarm 2DR
Thermal alarm 3DR
Thermal alarm 4DR
Thermal alarm 5DR
Severe external alarm (input I5 or I6)DR
Remote regulation detained due to digital input (input I5 or I6)D
Low-pressure alarm due to digital input (input I5 or I6)DR
High-pressure alarm due to digital input (input I5 or I6)DR
Error in probe 1 (open circuit, probe crossed or out of range)DR
Error in probe 2 (open circuit, probe crossed or out of range)DR
Error in probe 3 (open circuit, probe crossed or out of range)DR

D: The message is shown on the display.
R: Alarm relay activated (if available, see WIZARD table).

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals