Schneider Electric Powerpact H And J Frame Electronic Trip Circuit Breaker Instruction Manual

Schneider Electric Powerpact H And J Frame Electronic Trip Circuit Breaker Instruction Manual

PowerPacT H and J Frame Electronic Trip Circuit Breaker

Product Information

This product is the PowerPacTTM H- and J-Frame Electronic TripCircuit Breaker. It is a device that automatically interrupts an electrical circuit during an  overload or short circuit. This circuit breaker is equipped with a Visi-TripTM LED handle that helps in quickly locating a circuit breaker that requires attention. The product comes with internal accessories that need to be installed prior to installing the circuit breaker. It is important to note that failure to follow the instructions may result in death or serious injury.

The required specifications for installation include screws, extension blanks, lugs, and cords. The product has different Ir (x Io) and Io (A) values that depend on the type of cord used. The product also has a DINP chemical that is known to cause cancer and DIDP chemical that is known to cause birth defects or other reproductive harm.

Product Usage Instructions

Before starting the installation, read and understand all instructions provided in the Instruction Bulletin. Turn off all power supplying this equipment before working on or inside equipment. Install the internal accessories as instructed in the bulletins shipped with each accessory. Remove any installed handle extension if it will interfere with the enclosure door closing.

When performing annual maintenance, operate the push to trip button (if equipped) to verify the Visi-Trip functionality. Cycle the circuit breaker from tripped to OFF, and then from OFF to ON and take note of the battery health.

It is important to follow the precautions provided in the Instruction Bulletin to avoid death or serious injury. For more information about the chemicals used in this product, visit: www.P65Warnings.ca.gov.

PowerPacT™ H- and J-Frame Electronic Trip Circuit Breaker Installation

Retain for future use.

Before starting the installation, read and understand all instructions.

Scan the QR code on the product for additional product information.

For information about other products, see our website: https://www.se.com:
For application assistance, please call 1-888-778-2733.

Precautions
DANGER: HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, CSA Z462 or NOM 029-STPS.
  • This equipment must be installed and serviced only by qualified electrical personnel.
  • Turn off all power supplying this equipment before working on or inside equipment.
  • Always use a properly rated voltage sensing device to confirm power is off.
  • Replace all devices, doors, and covers before turning on power to this equipment.

Failure to follow these instructions will result in death or serious injury.

WARNING: This product can expose you to chemicals including DINP, which is known to the State of California to cause cancer, and DIDP which is known to the State of California to cause birth defects or other reproductive harm. For more information go to: www.P65Warnings.ca.gov.

Required for InstallationCircuit breaker with Visi-Trip handle shown

Circuit Breaker ScrewsExtension Blanks 
1/4-20 x

3/4 in.  

8-32 x

2-5/8 in.  

7/8-16 x

0.56 in. 

HLN4EBLHLW4EBL
Schneider-Electric-PowerPa-T-H and-J-Frame-Electronic-Trip -02
Schneider-Electric-PowerPa-T-H and-J-Frame-Electronic-Trip -03
I-Line™, MicroLogic™ 1/2/3 trip unit60–150 A
250 A3
I-Line, MicroLogic 5/6 trip unit60–150 A11
250 A311
Lugs one end60–150 A32
250 A323
Lugs both ends60–150 A2
250 A26
No Lugs60–150 A62
250 A62

No Lugs

Installation

  1. Turn off all power supplying this equipment before working on or inside equipment.
  2. Trip the circuit breaker (Figure 1, a–c).
    Note: All internal accessories must be installed prior to installing the circuit breaker.
  3. Install the internal accessories (d) as instructed in the bulletins shipped with each accessory.
  4. Remove any installed handle extension (e) if it will interfere with the enclosure door closing.

Visi-Trip™
The Visi-Trip LED handle aids in quickly locating a circuit breaker that requires attention. Inspect the handle position for circuit breaker trip indication. The Visi-Trip handle will flash an LED light as described in Table 1.

Note: When performing annual maintenance in accordance with MCCB Field Testing and Maintenance Guide
(0600IB1201), operate the push to trip button (if equipped) to verify the Visi-Trip functionality. Cycle the circuit breaker from tripped to OFF, and then from OFF to ON and take note of the battery health. See Table 2.
Wait five seconds between handle operation and push-to-trip button operation to ensure that the Visi-Trip handle is on standby mode. Tripping the circuit breaker too soon after toggling may result in the Visi-Trip handle not operating as intended.1

TABL. 1 :

Light Pattern Indicator / 
Fast flash for two seconds.Battery low (20% remaining).
Long duration slow flash (continuous flash up to for six hours).Inspect the handle position for circuit breaker trip indication. 1
  1. Refer to the Schneider Electric Frequently Asked Questions page. https://www.se.com/us/en/faqs/home/ for more information.
  2. If a nuisance LED flashing occurs on ON or OFF position, it can be reset by toggling the circuit breaker. If toggling the circuit breaker is not desired, LED flashing will reset after six ours.

Individually-Mounted Circuit Breaker Installation
DANGER: HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Install circuit breaker so minimum clearance distance to grounded metal is maintained.
Failure to follow these instructions will result in death or serious injury.

  1. Check electrical clearances (Figure 2, a–c).

FIG. 2 :Clearances

J-Frame Enclosure Insulation2

Fiber Insulating Plate

Enclosure Dimensions

Frame Standard (80%) Rated 100% Rated / 
HD/HG/HJ/HL15–150 A15.6 x 6.12 x 3.49 in. (396 x 155 x 89 mm)15.6 x 6.12 x 3.49 in. (396 x 155 x 89 mm)
HR18.13 x 8.63 x 4.13 in. (461 x 219 x 105 mm)62 x 22.5 x 14 in. (1575 x 572 x 356 mm)
JD/JG/ JJ/JL2150–250 A18.72 x 6.12 x 3.49 in.

(476 x 155 x 89 mm)

18.72 x 6.12 x 3.49 in. (476 x 155 x 89 mm)
JR28.5 x 12.38 x 5.38 in. (724 x 314 x 137 mm)62 x 22.5 x 14 in. (1575 x 572 x 356 mm)
  1. If dimension “A” is less than 0.56 in. (14.2 mm), attach fiber insulating plate (not provided)  to enclosure cover.
  2. Insulation required if circuit breaker side < 4.13 in. (105 mm) from metal.

Install the circuit breaker (Figure 3, a– b).

I-Line Circuit Breaker Installation
NOTICE /: HAZARD OF EQUIPMENT DAMAGE

  • Do not adjust jaws.
  • Do not remove joint compound.
  • If necessary, use Square D joint compound PJC7201.

Failure to follow these instructions can result in equipment damage.

  1. Rack the circuit breaker onto the bus (Figure 4, a–b).
  2. Tighten the mounting bracket screw (c–d).
  3. For circuit breakers with MicroLogic™ 5 or 6 trip units, attach a blank extension HLN4EBL (narrow) or HLW4EBL (wide) to the equipment dead front (e-f).
    See installation bulletin 80030-695-02 for additional information on installing blank extensions.

Cable Installation

  • Note: If needed, install lugs as directed in the instruction shipped with the lug kit.
    To convert AL250JD lugs to AL175JD lugs, use the included wire binding screws and the instructions packed with the screws.
  • Note: See Table 2 for strip lengths and torques.

Notice: HAZARD OF FALSE TORQUE INDICATION
Do not allow conductor strands to interfere with threads of wire binding screws.
Failure to follow these instructions can result in equipment damage.

TABL. 2 :


  
AL150HDH-frame60/100/150 A(1) Al/Cu14–10 AWG

(3,5–6 mm2)

0.65 in. (16 mm)50 lb-in. / lbs-pulg / lb-po (5 N•m)
8–3/0 AWG (10–95 mm2)0.65 in. (16 mm)120 lb-in. / lbs-pulg / lb-po (14 N•m)
CU150HDH-frame 60/100/150 A(1) Cu14–2/0 AWG (2,5–70 mm2)0.65 in. (16 mm)120 lb-in. / lbs-pulg / lb-po (14 N•m)
AL175JD1J-frame60/100/150 A(1) Al/Cu4–4/0 AWG (50–95 mm2)1 in.
(25 mm)
225 lb-in. / lbs-pulg / lb-po (26 N•m)
AL250JDJ-frame250 A(1) Al/Cu3/0 AWG–350 kcmil (120–185 mm2)1 in.
(25 mm)
225 lb-in. / lbs-pulg / lb-po (26 N•m)
CU250JDJ-frame250 A(1) Cu1/0 AWG–300 kcmil (50–185 mm2)1 in.
(25 mm)
250 lb-in. / lbs-pulg / lb-po (28 N•m)
  • For wire sizes smaller than 3/0 AWG, remove wire binding screws and replace with 7/8-15 x 0.56 screws, provided. /
  1. Preform the conductors to their final configuration. Strip the conductor ends (Figure 5, a). Do not nick strands.
  2. Install the cables in the lugs and torque the wire binding screws (b–c).
    • Install wire larger than 12 AWG in center of channel (d).
    • Install 14–12 AWG wire on the side of channel (e) on all lugs to avoid damage to wire.

Bus Installation
Note: If terminal nut inserts are not installed, install the terminal nut inserts as directed in the instructions shipped with the terminal nut kit.

  1. Prepare the bus connections as shown (Figure 6, a).
  2. Install the bus connections, using the supplied hardware (b–c).

FIG. 6 :

DimensionH-frame J-frame 
A0.250 in. (6.4 mm)0.250 in. (6.4 mm)
B0.125–0.375 in.
(3.2–9.5 mm)
0.125–0.375 in.
(3.2–9.5 mm)
C0.50 in. (12.7 mm)0.50–0.75 in.
(12.7–19.1 mm)
D0.3 in. (7.6 mm)0.625 in.
(15.9 mm)
E0.3 in. (7.6 mm)0.375 in. (9.5 mm)

Control Wiring Installation
(All Circuit Breakers)
Note: Refer to the bulletin shipped with each accessory for accessory installation instructions.

  1. Remove accessory cover (Figure 7, a–b).
  2. Install auxiliary devices into corresponding accessory compartments (c).

FIG. 7 :

Auxiliary Devices 
OFAuxiliary contact 

A1, A3

SDAlarm switch 

A1

MNUnder voltage trip 

A2

MXShunt trip 

A2

SDEOvercurrent trip 

A3

SDxRelay moduleA1 & A2
SDTAMRelay moduleA1 & A2
NSX Cord Cordón NSX Cordon NSXCommunications cordA3 alone

A1 with BSCM / A3 solo

A1 con BSCM

7 mm

0.27 in.

1–2.5 mm2

18-14 AWG

1.4±0.14 N•m
12±1.2 lb-in.
BSCMBreaker status communication module 

A3

24 Vdc Terminal blockPower supply terminal block 

A3

MN Spring clampUndervoltage trip spring clamp 

A2

1
MX Spring clampShunt trip spring clamp 

A2

7 mm
0.27 in. 0.5–1.5 mm²
20–16 AWG

  1. Multi-stranded end only.
    Note: SDx or SDTAM accessories require a fuse.A: 200 mA fuse required, Bussman Fuse KTK-2/10 or equivalent.
    NOTICE: HAZARD OF EQUIPMENT DAMAGE
    • Tighten all accessory cover screws to stated torque.
    • Do not overtorque screws.
    • Do not use power equipment to torque screws.
      Failure to follow these instructions can result in equipment damage.
  2. Route the wiring (Figure 8, a).
  3. Replace the accessory cover (b–c), being careful not to pinch the wires when installing the cover.
    Note: Confirm that the catalog number on the side accessory label (d) and on the accessory cover (e) match.
  4. Replace Visi-Trip handle (f), note proper orientation (g).
  5. Mark on the side accessory label (d) which device was installed..

FIG. 8 :
Individually-Mounted Circuit Breakers

I-line Circuit Breakers 

Trip Unit Adjustment
MicroLogic 2 and 3 Trip Units:
Set the trip unit using the dials on the front of the trip unit (Figure 9, a–d). See Figure 10 for dial information.
See bulletin 48940-310-01, MicroLogic™ 1, 2, and 3 Electronic Trip Unit—Users Manual, for more information on the trip unit.

FIG. 9 :

For example: To set Ir to 80, rotate dial until arrow points to 80.

FIG. 10 :

  • A. Sensor rating In
  • B. Long-time protection pickup setting dial Ir
  • C. Long-time protection time delay setting dial tr
  • D. Instantaneous protection pickup setting dial Ii
  • E. Short-time protection pickup setting dial Isd
  • F. Full load amp setting dial FLA
  • G. Long-time protection trip class dial Class
  • H. FLA adjustment range

 Protective Functions Trip Curve

NFunction MicroLogic Trip Unit 
3.2S3.22.2 M
1InNN
2IrAA
3trNA
4IsdAA
5tsdNN
6IiAAN
7FLA Min/MaxN
8FLAA
9ClA
  • A = Adjustable
  • N = Not Adjustable
  • _ = Not Available
Function Description 
InSensor rating / Valor nominal del sensor
IrLong-time protection pickup
trLong-time protection time delay
IsdShort-time protection pickup
tsdShort-time protection time delay
IiInstantaneous protection pickup
FLA Min/MaxFull load amp adjustment range
FLAFull load amp setting
ClLong-time protection trip class

MicroLogic 5 and 6 Trip Units:
Set the protection functions:

  • The Pocket Tester or the UTA Tester can be used to power the MicroLogic 5/6 trip unit (Figure 11, a–g). Use enclosed screwdriver to adjust dial settings if necessary (h–i).
  • Use the keypad for fine adjustments.

See Figure 12 for dial information.
See bulletin 48940-312-01, MicroLogic™ 5 and 6 Electronic Trip Units—Users Manual, for more information on setting and operation of the trip unit.

  • A. Sensor rating In
  • B. Long-time protection pickup setting dial Ir
  • C. Instantaneous protection pickup setting dial Ii

Protective Functions Trip Curve 

  • A = Adjustable
  • AR=Adjustable with RSU software
  • N = Not Adjustable
  • — = Not Available
NoFunction MicroLogic Trip Unit
5.26.2
1InNN
2IrAA
3trAA
4IsdAA
5tsdAA
6I2t ON/OFFAA
7IiAA
8IgA
9tgA
10I2t ON/OFFA

 

Function Description 
InSensor rating
IrLong-time protection pickup
trLong-time protection time delay
IsdShort-time protection pickup
tsdShort-time protection time delay
I2t ON/OFFShort-time protection I2t curve in ON or OFF position
IiInstantaneous protection pickup
IgGround-fault protection pickup
tgGround-fault protection time delay
I2t ON/OFFGround-fault protection I2t curve in ON or OFF position

Circuit Breaker Removal

  1. Turn off all power supplying this equipment before working on or inside equipment.
  2. Remove circuit breaker in reverse order of installation.

Troubleshooting

If problems occur during installation, refer to the following guide. If trouble persists, contact the local field office.

DANGER: HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

  • This equipment must be installed and serviced only by qualified electrical personnel.
  • Troubleshooting may require energizing auxiliary devises with a test power supply. Make sure that the power supply is Off (O) before connecting or disconnecting it to the auxiliary device.
  • Qualified persons performing diagnostics or troubleshooting that require electrical conductors to be energized must comply with NFPA 70 E – Standard for Electrical Safety Requirements for Employee Workplaces and OSHA Standards -29 CFR Part 1910 Subpart S -Electrical.

Failure to follow these instructions will result in death or serious injury.

ConditionPossible CausesSolution
Circuit breaker fails to stay closed.Short circuit or overload on system.Check system for short circuit or overload.
Circuit beaker trips, but no short circuit or overload is evident.Voltage is below undervoltage trip setting.Check system for low voltage.
Push-to-trip button does not trip circuit breaker.Circuit breaker already tripped.Move circuit breaker handle to reset then to on (I).
Circuit breaker cannot be opened manually.Damage to current path.Contact local field office.

Electrical equipment must be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
Schneider Electric and Square D are trademarks and the property of Schneider Electric SE, its subsidiaries, and affiliated companies. All other trademarks are the property of their respective owners.

Schneider Electric Limited
Stafford Park 5
Telford TF3 3BL
United Kingdom
www.se.com/uk

Schneider Electric USA, Inc.
800 Federal Street
Andover, MA 01810 USA
888-778-2733
www.se.com/us

© 2011-2022 Schneider Electric All Rights Reserved

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals