Fanmaster Wpc-9000 3 Ton Portable Air Conditioner Owner's Manual

WPC-9000 3 Ton Portable Air Conditioner

Product Information

Product Name: Model WPC-9000

Product Type: Air Conditioner

Product Usage Instructions

Self-Diagnostic Alarm Codes

Alarm DisplayProblem CauseCorrective Action
Frost prevention sensor and Abnormal temperature sensor
value
Indoor heat exchanger temperature too lowEnsure ambient temperature is not lower than the specified
limit. Clean air filter and ensure exhaust duct is not blocked or
kinked.
Refrigerant high pressure switchBlocked air filter, blocked/kinked exhaust duct, or ambient
temperature too high
Clean air filter and ensure exhaust duct is not blocked or
kinked. Do not use the air conditioner if ambient temperature is
higher than the specified limit.
Abnormal temperature sensor value TH1(Outlet) temperature
sensor has a loose or broken connection
Contact a qualified service agentContact a qualified service agent for repair.
Abnormal temperature sensor value TH2(Inlet) temperature sensor
has a loose or broken connection
Contact a qualified service agentContact a qualified service agent for repair.
Compressor overloaded Ambient temperature is too high Unstable
voltage supply Defective compressor
Do not use the air conditioner if ambient temperature is higher
than the specified limit. Replace compressor if necessary.
Do not use the air conditioner if ambient temperature is higher
than the specified limit. Replace compressor if necessary.
Condensate water level alarm Drain pump alarmCondensate tank is full Drain pump defective or improper hose
connection (including kink or blockage)
Empty the water tank. After installation of the water tank,
press the SPOT/COOL or ROOM/COOL button to resume operation. Check
the hose connection and hose. Replace drain pump if necessary.

Troubleshooting Chart

SymptomPossible Cause(s)Corrective Action
Water leakageHigh water level in condensate tank1. Remove blockage from drain hose. 2. Remove any object stuck
underneath the black panel under the water tank.
The unit doesn’t work1. Power supply issue. 2. Power cord not connected.1. Reset the circuit breaker and restart the unit. 2. Connect
the power cord.
No cold air flows from the cold air outlet1. Dirty filter. 2. Unit turned off and on quickly.1. Clean the filter if dirty and not regularly cleaned. 2. Wait
2 minutes after turning off the unit before turning it back
on.
Water flow can be heard after compressor shuts offNo specific causeIt is common to hear coolant flowing after the unit shuts
off.
Alarm displays FT with less than half of condensate water in
the tank
Spring is possibly brokenReplace the spring. Refer to the Maintenance page (Page 8) for
instructions.

Owner’s manual

Model WPC-9000

SELF-DIAGNOSTIC ALARM CODES

Alarm Display Problem

Cause

Corrective Action

Frost prevention sensor and Abnormal temperature sensor value

Indoor heat exchanger
temperature too low
TH3 temperature sensor
has a loose or broken connection

Do not use the air conditioner if ambient temperature is lower than
18°C (64°F) Contact a qualified service agent

Refrigerant high pressure switch

Blocked air filter Blocked / kinked exhaust duct Ambient temperature is too high

Clean air filter Ensure exhaust duct is not
blocked / kinked
Do not use the air conditioner if ambient temperature is higher than
45°C (113°F)

Abnormal temperature sensor value

TH1(Outlet) temperature
sensor has a loose or broken connection

Contact a qualified service agent

Abnormal temperature sensor value

TH2(Inlet) temperature
sensor has a loose or broken connection

Contact a qualified service agent

Compressor overloaded

Ambient temperature is
too high
Unstable voltage supply Defective compressor

Do not use the air conditioner if ambient temperature is higher than
45°C (113°F) Contact a qualified service agent
Replace compressor

Condensate water level
alarm
Drain pump alarm

Condensate tank is full
Drain pump defective or improper hose connection (including kink or blockage)

Empty the water tank
After installation of the water tank, press the SPOT/ COOL or ROOM/COOL button to resume operation
Check the hose connection and hose Replace drain pump

9

Owner’s manual

Model WPC-9000

Troubleshooting chart

Symptom Water leakage
The unit doesn’t work

Possible Cause(s)

Corrective Action

High water level in condensate tank

1. Remove blockage from drain hose
2. Remove any object stuck undeerneath of the black panel nuder the water tank

1. Check the power supply to verify that 1. Reset the circuit breaker and restart

power is available to the unit

the unit

2. Verify that the power cord is connected 2. Connect power cord

No cold air flows from the cold air outlet

1. Ambient air cannot be properly cooled 1. Clean the filter if the filter is dirty and not regularly cleaned

2. Compressor will not work if the unit is 2. Wait 2 minutes after unit is turned

turned off and on quickly.

off before turning the unit back on.

3. The ambient air temperature may be too high

3. The temperature of the compressor can be higher when the ambient temperature is too high. The compressor will not work unless the ambient air temperature is within the acceptable operating range of the unit

Water flow can be heard No cause after compressor shuts off

Common to hear coolant flowing after unit shuts off

Alarm displays “FT”with

Spring is possibly broken

less than half of condensate

water in the tank

Spring is possibly broken

Replace a new spring (See Maintenance page 8)