Cotek Sd1500 Series 1500w Pure Sine Wave Owner's Manual

SD1500 Series 1500W Pure Sine Wave

Product Information:

The SD1500 series is a 1500W pure sine wave power inverter
designed for multiple industrial applications. It features a
parallel redundancy design for power expansion, automatic master
mechanism to eliminate single point failure, and built-in ATS and
AC circuit breaker. The optional STS module allows for transfer
time of less than 4ms. The inverter also offers RS-232
communication and input/output isolation. It has selectable output
voltage/power saving mode and can be controlled remotely using the
CR-10 remote control.

Product Usage Instructions:

To use the SD1500 series power inverter, follow these steps:

  1. Ensure that the input DC voltage matches the requirements of
    your system. The SD1500 series is available in different models
    with different input voltages (12VDC, 24VDC, 48VDC).
  2. Connect the DC input to your power source within the specified
    voltage range. Make sure the polarity is correct to avoid reverse
    polarity damage (fuse protection is provided).
  3. Connect the AC input to the desired load or utility power
    source.
  4. Ensure that the output voltage and power saving mode are set
    according to your requirements. This can be done using the DIP
    switch on the inverter or using the remote control (CR-10).
  5. If necessary, install the optional STS module for faster
    transfer time between utility AC and inverter power.
  6. Make sure the output load does not exceed the maximum rating
    power, and avoid short circuits, overload, over temperature, and
    overvoltage conditions to ensure proper output protection.

Note: The SD1500 series power inverter has a total harmonic
distortion (THD) of less than 3% under specific conditions. It
operates at an efficiency of up to 90% and provides a pure sine
wave output.

1500W Pure Sine Wave
Features:
Parallel redundancy design for power expansion Multiple industrial applications that create 13W / 34W power systems Automatic master mechanism to eliminate single point failure and optimize reliability Built-in ATS and AC circuit breaker Optional STS module, transfer time less 4ms. RS-232 communication Input & output fully isolation Output voltage / power saving mode selectable by DIP switch or remote control (CR-10)
Input Protection: Reverse Polarity (Fuse) / Under Voltage / Over Voltage Output Protection: Short Circuit / Overload / Over Temperature / Over Voltage

SD1500 series

Output DC Input
AC Input
Protection Environment

MODEL
Rating Power Output Power (Max. 3 min.) Peak Power (Max. 3 sec.) Surge Power (Max. 0.2 sec.) Waveform Efficiency (Max.) Output Voltage (@rated VDC) Output Frequency
Total Harmonic Distortion (THD)
DC Voltage Voltage Range No load Power Consumption On Mode @ Save Mode On Mode @ No Load Mode Fuse AC Range Frequency Selectable Synchronous Frequency Circuit Breaker
Transfer Switch ***
BAT.Low Alarm ±3% BAT.Low Shut-down ±3% BAT.Low Restart ±3% BAT.High Alarm ±3% BAT.High Shut-down ±3% BAT.High Restart ±3% Input Protection Output Protection Working Temp. Storage Temp. Relative Humidity Safety Standards

SD1500-112 SD1500-124 SD1500-148 SD1500-212 SD1500-224 SD1500-248

1500VA (de-rating after 40°C, refer to de-rating curve) 1500 ~ 1800VA 1800 ~ 2400VA >2400VA

Pure Sine Wave

88%

89%

100 / 110 / 115 / 120VAC ±3%

50 / 60Hz ±0.1%

90%

88%

88%

90%

200 / 220 / 230 / 240VAC ±3%

< 3% @ under condition : greater than 1.15 times < 3% @ under condition : greater than 1.15 times

of the rated VDC, 110V / linear load)

of the rated VDC, 230V / linear load)

12VDC

24VDC

48VDC

12VDC

24VDC

48VDC

10.0~16.0VDC 20.0~32.0VDC 40.0~64.0VDC 10.0~16.0VDC 20.0~32.0VDC 40.0~64.0VDC

@12VDC

@24VDC

@48VDC

@12VDC

@24VDC

@48VDC

0.9A

0.35A

0.3A

1.1A

0.7A

0.4A

< 2.4A

< 1.2A

< 0.6A

< 3.3A

< 1.6A

< 0.8A

40Ax6

20Ax6

15Ax4

40Ax6

20Ax6

15Ax4

100 / 110 / 115 / 120VAC±12.5%

200 / 220 / 230 / 240VAC±12.5%

50 / 60 Hz

47 – 57 / 53 – 63 Hz

20A

10A

Standard ATS : Inverter to utility AC : 8~10ms.; Utility AC to inverter : 16~25ms.

Optional STS module : <4ms

10.5VDC

21.0VDC

42.0VDC

10.5VDC

21.0VDC

42.0VDC

10.0VDC

20.0VDC

40.0VDC

10.0VDC

20.0VDC

40.0VDC

12.5VDC

25.0VDC

50.0VDC

12.5VDC

25.0VDC

50.0VDC

15.5VDC

31.0VDC

62.0VDC

15.5VDC

31.0VDC

62.0VDC

16.0VDC

32.0VDC

64.0VDC

16.0VDC

32.0VDC

64.0VDC

15.0VDC

30.0VDC

60.0VDC

15.0VDC

30.0VDC

60.0VDC

Reverse Polarity (Fuse) / Under Voltage / Over Voltage Protection / AC over current (Breaker)

Short Circuit / Overload / Over Temperature / Over Voltage

-20 ~ +60°C; refer to SD1500 power de-rating curve

-40 ~ +70°C

Max. 90%, non-condersing

*Certified UL458 (UL only for hardwire)

Certified EN62368-1

Safety & EMC EMC Standards

Certified FCC Class B

**Certified EN 55032, EN 55024,

E-Mark

Control & Signal LED Indicator Remote control

Dimension (WxHxD)

Others

Weight Cooling

Communication Port

­ Input voltage level, faulty status CR-6, CR-8 and CR-10 283x128x351 mm / 11.14×5.04×13.82 inch 5.5 kg Load & Thermal control fan
RS-232 (RJ-11 type connector)

Certified CISPR 25; ISO 7637-2

Note

*UL-458 only support 112 and 124 model. **EN55032, EN55024 Class B : output cable less than 2 meters. ***Please refer to Transfer – Time Table.

REV. A9 22/09/20
1

1500W Pure Sine Wave

SD1500 series

LED Status:
Green LED Solid
Slow Blink Intermittent Blink
Orange LED Fast Blink Slow Blink Red LED Intermittent Blink Fast Blink Slow Blink
Solid Intermittent Blink Intermittent Blink
Output Socket:

LED Signal LED Signal LED Signal

Status
Power OK Power Saving
Bypass
Status
OVP UVP
Status
OTP OVP- Shut-down UVP- Shut-down
OLP Fan Failure Component Failure

Hard Wire

United Kingdom

Universal

Input Socket:
IEC

Hard Wire

De-rating Curve:
1900 1500 1100
700

REV. A9 22/09/20
2

Transfer Time :

1500W Pure Sine Wave

Transfer-Time Table

ModeTransfer Switch

ATS

STS

Haphazard

Frequency is synchronized : <4ms Inverter to utility AC : 8~10ms.; Frequency is not synchronized : Utility AC to inverter : 16 ~ 50ms. Inverter to utility AC : <4ms.;
Utility AC to inverter : 16 ~ 50ms.

Normal (Default)

Inverter to utility AC : 8~10ms.; Utility AC to inverter : 16 ~ 25ms.

<4ms

Exacting

Inverter to utility AC : 8~10ms.; Inverter to utility AC : <4ms.; Utility AC to inverter : 16 ~ 50ms. Utility AC to inverter : 16 ~ 50ms.

Online

Inverter to utility AC : 8~10ms.; Utility AC to inverter : 16 ~ 25ms.

<4ms

Mechanical Drawings:

93.1 [3.66]

351 [13.82] 160.0 [6.3]

SD1500 series
Unit : mm [inch]

268.6 [10.57] 283 [11.14]

128 [5.04]

8.5 [0.33]

REV. A9 22/09/20
3

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.