SK 3138000 Roof Mounted Fan
Rittal Roof-Mounted Fan
The Rittal Roof-Mounted Fan is a ventilation system designed to
improve air circulation in enclosures. It is available in different
models: SK 3138000, SK 3139100, SK 3139110, SK 3140100, SK 3140110,
SK 3140140, SK 3140500, and SK 3140510.
1. Safety Instructions
1.1 Safety Instructions
Before installing and using the Rittal Roof-Mounted Fan, please
read and follow the safety instructions provided in the assembly
and installation instructions manual.
1.2 Intended Use
The Rittal Roof-Mounted Fan is intended for use as a ventilation
system in enclosures. It is not suitable for use in hazardous
environments or for any other purpose.
2. Product Description
2.1 Components
The Rittal Roof-Mounted Fan consists of the following
components:
- Cover
- Fan plate with fan
- Inflow nozzle for air routing
- Base tray with pleated filter
- Electrical connector
Refer to Figure 1 for a visual representation of the
components.
2.2 Scope of Supply
The Rittal Roof-Mounted Fan comes with the following:
- Rooftop-mounted fan unit
- Pleated filter
- Assembly and installation instructions manual
- Connector
Refer to Table 1 for a detailed description of the scope of
supply.
2.3 Function
The Rittal Roof-Mounted Fan improves air circulation in
enclosures. It has safety devices and filter mats to ensure proper
ventilation. Refer to the assembly and installation instructions
manual for more information about its function.
3. Mounting
3.1 Choosing the Installation Site
When choosing the installation site for the Rittal Roof-Mounted
Fan, ensure that the unit is guaranteed. Refer to the assembly and
installation instructions manual for more information about
choosing the installation site.
3.2 Notes on Installation
3.2.1 General
Check the packaging carefully for signs of damage before
installing the unit. Any packaging damage may cause a subsequent
functional failure. Ensure that the inlet filter provides adequate
air exchange.
3.2.2 Layout of the Electronic Components in the Enclosure
Take note of the air flows from the internal fans of installed
electronic components. When installing the Rittal Roof-Mounted Fan,
ensure that the airflows of fans and built-in electronic components
do not adversely influence one another (air short-circuit). Observe
the corresponding minimum distances between the fan and component
to ensure unhindered air circulation.
3.2.3 General
Carefully deburr the cut-out to prevent injuries caused by sharp
edges. Check that the clips are completely snapped into place to
ensure that the Rittal Roof-Mounted Fan is securely held in the
mounting cut-out.
3.3 Installing the Roof-Mounted Fan
Refer to the assembly and installation instructions manual for
detailed steps on how to install the Rittal Roof-Mounted Fan. The
manual provides additional installation steps for different
protection categories and air throughput.
4. Electrical Connection
4.1 Connecting the Power Supply
Refer to the assembly and installation instructions manual for
information on the electrical installation and connection data.
Ensure that the PE conductor connection, overvoltage protection,
and supply line load are properly installed.
4.2 Installing the Pilot Wire
Refer to the assembly and installation instructions manual for
information on how to install the pilot wire.
5. Commissioning
Refer to the assembly and installation instructions manual for
information on how to commission the Rittal Roof-Mounted Fan.
6. Inspection and Maintenance
Refer to the assembly and installation instructions manual for
information on how to inspect and maintain the Rittal Roof-Mounted
Fan.
7. Storage and Disposal
Refer to the assembly and installation instructions manual for
information on how to store and dispose of the Rittal Roof-Mounted
Fan.
8. Technical Specifications
Refer to the assembly and installation instructions manual for
technical specifications of the Rittal Roof-Mounted Fan.
9. Accessories
Refer to the assembly and installation instructions manual for
information on available accessories for the Rittal Roof-Mounted
Fan.
10. Warranty
Refer to the assembly and installation instructions manual for
information on the warranty of the Rittal Roof-Mounted Fan.
11. Customer Services Addresses
Refer to the assembly and installation instructions manual for
customer service addresses.
Roof-mounted fan
SK 3138000 SK 3139100 SK 3139110 SK 3140100
SK 3140110 SK 3140140 SK 3140500 SK 3140510
Assembly and installation instructions
Contents
1. Safety instructions
3
1.1 Safety instructions
3
1.2 Intended use
3
2. Product description
4
2.1 Components
4
2.2 Scope of supply
5
2.3 Function
6
2.3.1 General
6
2.3.2 Safety devices
6
2.3.3 Filter mats
6
3. Mounting
7
3.1 Choosing the installation site
7
3.2 Notes on installation
7
3.2.1 General
7
3.2.2 Layout of the electronic components in
the enclosure
7
3.2.3 General
7
3.3 Installing the roof-mounted fan
8
3.3.1 Installation IP 21
8
3.3.2 Additional installation steps: Installation
from outside IP 54/UL Type 12
9
3.3.3 Additional installation steps: Installation
from inside IP 54/UL Type 12
10
3.3.4 Additional installation steps: Enhanced
protection category IP 55/UL Type 12
10
3.3.5 Additional installation steps: Protection
category IP 21/UL Type 1 and higher air
throughput
11
4. Electrical connection
12
4.1 Connecting the power supply
12
4.1.1 Notes on electrical installation
12
4.1.2 Connection data
12
4.1.3 Overvoltage protection and supply line load 12
4.1.4 PE conductor connection
12
4.1.5 Installing the power supply
12
4.2 Installing the pilot wire
14
5. Commissioning
15
6. Inspection and maintenance
15
7. Storage and disposal
15
8. Technical specifications
16
9. Accessories
17
10. Warranty
19
11. Customer services addresses
19
2
Rittal roof-mounted fan
1. Safety instructions
1.1 Safety instructions
Assembly, installation and servicing may only be performed by properly trained specialists.
Do not obstruct the air inlet and air outlet of the roof-mounted fan inside and outside the enclosure.
The specific air throughput of the roof-mounted fans must be adequate to meet the climate control requirements of the enclosure.
Use only original spare parts and accessories. Do not make any changes to the roof-mounted fan other than
those described in these and other applicable instructions. The roof-mounted fan must only be connected to the mains
with the system de-energised. Connect the prefuse specified in the Technical Specifications. Never insert your fingers into the rotating fan blade. The roof-mounted fan must only be fitted on a sealed enclosure with protected access to the electrical connection. Electrical connection and any repairs may only be carried out by authorised, specialist personnel. Children and persons with limited cognitive/coordinative abilities must not operate, maintain or clean the unit or be allowed to use it as a toy. Spending long periods in the airflow may irritate the eyes and muscles. If extinguisher gas is used in the enclosure, the roof-mounted fan must be incorporated into the fire protection concept.
1.2 Intended use
Rittal roof-mounted fans were developed and designed in accordance with the state of the art and the recognised rules governing technical safety. Nevertheless, if used improperly, they may pose a threat to life and limb or cause damage to property. The unit is only intended for ventilating enclosures and electronic cases. Any other use is deemed improper. The manufacturer will not be liable for any damages caused as a result of improper use, or for incorrect assembly, installation or use. All risk is borne solely by the user. Proper usage also includes the observation of all valid documents and compliance with the inspection and servicing conditions.
Rittal roof-mounted fan
3
2. Product description
2.1 Components 1
Key
1 Cover 2 Fan plate with fan 3 Inflow nozzle for air routing 4 Base tray with pleated filter 5 Electrical connector
2 3 4
5 Fig. 1: Components
4
Rittal roof-mounted fan
2. Product description
2.2 Scope of supply Description
Illustration
Roof-mounted fan
Qty.
Annotation
1x
Pleated filter
Assembly and installation instructions Connector Tab. 1: Scope of supply
Dachlüfter Roof-mounted fan Ventilateur de toit
Montage- und Installationsanleitung Assembly and installation instructions Notice de montage et d’installation
4x
pre-installed
1x 1x
Rittal roof-mounted fan
5
2. Product description
2.3 Function
2.3.1 General The roof-mounted fan in conjunction with the corresponding inlet filter(s) is used to dissipate heat loss from enclosures and ventilate the enclosure, thereby protecting temperature-sensitive components. This is achieved via the direct infeed of ambient air, the temperature of which must be lower than the admissible enclosure interior temperature. The ambient air enters the enclosure via an air inlet grille in the lower section and is drawn upwards through the enclosure by the roof-mounted fan. The warmed air is then returned to the outside via the fan. It is not possible to change the air flow direction. 2.3.2 Safety devices The fan is equipped with a thermal winding protection for protection against overload. 2.3.3 Filter mats The roof-mounted fan is supplied with four pleated filters (class ePM10 50% to ISO 16890) pre-installed. The filter must be checked regularly depending on the level of dust exposure, and replaced as necessary.
6
Rittal roof-mounted fan
3. Mounting
3.1 Choosing the installation site
When choosing the installation site for the enclosure, please observe the following:
The site for the enclosure, and hence the position of the roof-mounted fan, must be carefully selected so as to ensure good ventilation.
The site must be free from excessive dirt and moisture. Roof-mounted fans must always be installed on horizontal
panels (roof). The ambient temperature must be lower than the admissible
enclosure interior temperature. The mains connection data as stated on the rating plate of
the unit must be guaranteed.
3.2 Notes on installation
3.2.1 General Check the packaging carefully for signs of damage.
Any packaging damage may be the cause of a subsequent functional failure.
Note: The inlet filter must ensure an adequate air exchange.
The enclosure must be sealed on all sides (IP 54). If the enclosure has a leak, unfiltered, contaminated air may enter the enclosure.
The fan motor is a rotating component that may transfer vibrations and oscillations.
Appropriate measures to decouple vibration must be taken in advance by the company responsible for the overall plant or system.
During transportation, the roof-mounted fan must be secured in accordance with section 3.3.2 or section 3.3.3 to prevent damage.
3.2.2 Layout of the electronic components in the enclosure
Take note of the air flows from the internal fans of installed electronic components.
When installing the roof-mounted fan, it is important to ensure that the airflows of fans and built-in electronic components do not adversely influence one another (air short-circuit).
The corresponding minimum distances between the fan and component must be observed in order to ensure unhindered air circulation.
3.2.3 General
Carefully deburr the cut-out to prevent injuries caused by sharp edges.
The position of the roof-mounted fan in the mounting cut-out is freely selectable. It should be based on the position of the electrical connection inside the enclosure.
No filter mats are needed in order to achieve protection category IP 21.
Check that the clips are completely snapped into place to ensure that the roof-mounted fan is securely held in the mounting cut-out.
The filter mats may be removed to achieve a higher air throughput. In this case, the protection category will be reduced to IP 21 and UL Type 1.
Use only original Rittal filters which bear the Rittal logo to be sure of the protection category, air throughout and approvals.
The protection category of the roof-mounted fan can be raised to IP 55. To this end, the pleated filters must be replaced with Rittal filter mats SK 3174100. The side with the Rittal logo must face towards the fan (see section 3.3.4).
Note: This reduces the air throughput. For details, please refer to the performance diagrams which can be found on the Rittal website.
You should inspect the filter regularly depending on the amount of dust. Recommended: Replace after 2,000 operating hours at the latest, and as and when necessary.
The orientation of the cover on the base tray is freely selectable.
Rittal roof-mounted fan
7
3. Mounting
3.3 Installing the roof-mounted fan 3.3.1 Installation IP 21
1
258±2 258±2
2
CLICK!
CLICK!
8
Rittal roof-mounted fan
3. Mounting
3.3 Installing the roof-mounted fan 3.3.2 Additional installation steps: Installation from outside IP 54/UL Type 12
3
4
¼
5
TX25
TX25
6
MA = max. 2 Nm (4x)
7 ¼
TX25
Rittal roof-mounted fan
9
3. Mounting
3.3 Installing the roof-mounted fan 3.3.3 Additional installation steps: Installation from inside IP 54/UL Type 12
3
TX25
MA = max. 2 Nm (4x) 3.3.4 Additional installation steps: Enhanced protection category IP 55/UL Type 12
5a
5b
10
Rittal roof-mounted fan
3. Mounting
3.3 Installing the roof-mounted fan 3.3.5 Additional installation steps: Protection category IP 21/UL Type 1 and higher air throughput
5a
6
Rittal roof-mounted fan
11
4. Electrical connection
4.1 Connecting the power supply
4.1.1 Notes on electrical installation When performing the electrical installation, it is important to
observe all valid national and regional regulations as well as the provisions of the responsible electrical supply company. The electrical installation must only be carried out by a qualified electrician who is responsible for compliance with the existing standards and regulations.
4.1.2 Connection data The connected voltage and frequency must correspond to
the values stated on the rating plate. The electrical installation and any repairs may only be carried
out by authorised specialist personnel. Use only original spare parts! Install the pre-fuse cited in the Technical Specifications (cir-
cuit-breaker or slow fuse) to protect from short-circuits. If several fans are operated on a single pre-fuse, observe the
total connected load. The roof-mounted fan must be connected to the mains via
an all-pole disconnecting device to overvoltage category III (IEC 61058-1).
4.1.3 Overvoltage protection and supply line load The unit does not have its own overvoltage protection. Measures must be taken at the supply end by the switch-
gear manufacturer or operator to ensure effective protection against lightning and overvoltage. The units are classified as overvoltage category III. The mains voltage must not exceed a tolerance of ±10%.
4.1.4 PE conductor connection The PE conductor must be connected to the PE conductor
system of the overall system.
4.1.5 Installing the power supply Remove the mains connector from the packaging and con-
nect to the mains as shown in the connection diagram. The connection terminal supplied allows the connection of
cable cross-sections of 0.5 to 4 mm². A smaller pilot wire (section 4.2) may be selected (min. 0.34
mm²). In accordance with NFPA 70 (NEC), only copper conduc-
tors must be used to connect the supply cable to the mains connector. If no wire end ferrules are used, strip the individual wires by max. 9 mm (observe the applicable clearances and creepage distances). Connect the connector to the roof-mounted fan from below.
Connection L N PE
+10 V
0…10 V/PWM
GND
Speed
Pin
Function/assignment
Power supply
Neutral conductor
PE conductor
Voltage output 10 V max. 1.1 A,
1
galvanically isolated, not short
circuit-protected
Control input 0…10 V or PWM,
2
galvanically isolated, impedance
100 k
3
GND connection of the control interface
Speed output Open Collector, 1
4
pulse per revolution, galvanically
isolated
Tab. 2: Connection designations
12
Rittal roof-mounted fan
4. Electrical connection
4.1 Connecting the power supply 4.1.5 Installing the power supply
SK 3139100/SK 3139110/ SK 3140100/SK 3140110
SK 3140140
max. 9 mm
L N PE / 1 2 3 4
SK 3140500/SK 3140510
Strain relief
Fig. 2: Connection diagrams
Fig. 3: Connector and strain relief
Rittal roof-mounted fan
13
4. Electrical connection
4.2 Installing the pilot wire
To control the EC roof-mounted fans via an external control unit (e.g. SK 3235440), types SK 31405xx have additional connections for the pilot wire.
Release and remove the jumper between the “+10 V” and “0 10 V/PWM” (terminals 1 and 2) connections.
Use a screwdriver with a 3.5 x 0.5 mm blade.
Open the terminal with the screwdriver and insert the connection cable as shown in the connection diagram.
Remove the screwdriver. To operate without a pilot wire, the jumper
should be left in the connection terminal. The unit will then be operated at maximum speed.
+10 V
0 10 V/ PWM
0 10 V/ PWM
GND
0 10 V/ PWM
GND
+10 V
0 10 V/ PWM
GND
0 10 V/ PWM
Fig. 4: Pilot wire
1
Max. speed (as delivered, with jumper between the “+10 V” and “0 10 V/PWM” connections.
2
Adjustable speed
3
Adjustable speed via PWM 1 10 kHz
4
Adjustable speed via potentiometer
14
Rittal roof-mounted fan
5. Commissioning
Once all the assembly and installation work is complete, switch on the power supply to the roof-mounted fan. The roof-mounted fan operates automatically, in other words, the fan will start up once the power has been switched on.
EC roof-mounted fans start running with a delay of approx. 15 sec.
6. Inspection and maintenance
Disconnect the electrical connection cable of the roof-mounted fan from the power supply.
The installed maintenance-free fan is mounted on ball bearings, protected against moisture and dust, and fitted with a temperature monitor.
The life expectancy is at least 50,000 operating hours (L10, 40 °C).
The roof-mounted fan is therefore largely maintenance-free. From time to time, the components may need to be cleaned
using a vacuum cleaner or compressed air if they become visibly dirty. Any stubborn, oily stains may be removed using a nonflammable detergent, such as degreaser. Never use flammable liquids for cleaning the unit.
Sequence of maintenance work Check the level of dirt: If necessary, vacuum the fan housing,
or clean with compressed air. Filter soiling: Replace the filter. Check the noise generation of the fan.
7. Storage and disposal
The roof-mounted fan must be stored at a temperature within the range specified in the technical data.
Disposal can be entrusted to the Rittal factory. Please call for further information.
Rittal roof-mounted fan
15
8. Technical specifications
Technical specifications
Unit
SK 3138000 SK 3139100 SK 3139110 SK 3140100 SK 3140110 SK 3140140 SK 3140500 SK 3140510
Electrical specifications Rated operating voltage Tolerance rated operating voltage
380…415,
V
without fan 220…240,
115, 1~,
220…240,
115, 1~,
3~, 50/60 220…240,
115, 1~,
Hz
motor
1~, 50/60
60
1~, 50/60
60
400…480, 1~, 50/60
60
3~, 60
±10 %
Rated current max. Power consumption Pre-fuse
A
0.23/0.27
0.56
0.43/0.56
1.2
0.17/0.2
1
1.51
W
51/62
65
99/130
138
90/120 98/130
129
112
A
3
3
Motor circuit-breaker
0.2…0.4
Rated insulation voltage (Ui)
V
300
Rated impulse withstand voltage (Uimp)
kV
4
2
Control interface
included
Weight
Weight (net)
kg
3.2
5.2
6.0
5.6
Air throughput (for performance diagrams, see Rittal homepage)
Air throughput, unimpeded air flow (without filter mats)
Air throughput, unimpeded air flow (with pleated filter IP 54)
Air throughput, unimpeded air flow (with chopped-fibre filter IP 55)
m³/h m³/h m³/h
500/525
525
873/965
965
863/942
1069
475/515
515
810/868
868
800/853
975
417/446
446
725/759
759
700/749
841
Air throughput (with filter mats and inlet filter)
1069 975 841
1 x SK 3243200 with chopped-fibre filter
m³/h
360/383
383
557/572
572
550/565
690
690
1 x SK 3243200 with pleated filter Fan Electromagnetic compatibility
m³/h
425/460
460
698/730
730
690/720
847
847
Radial/rotary
Radial/capacitor motor
current
Radial/EC motor
motor
Immunity to interference
For industrial areas to EN 61000-6-2
Emitted interference
For residential, business and commercial areas and small companies to EN 61000-6-3
Other
Noise level (with filter mats)
dB (A)
52/54
54
58/60
60
56/58
60
60
Noise level (without filter mats)
dB (A)
54/56
56
60/62
62
60/61
63
63
Operating temperature range
°C
-20…+55
Storage temperature range
Degree of protection (according to IEC 60529)
Degree of protection (NEMA)
°C
-40…+70
IP 21 (without filter and installation in accordance with section 3.3.1 or 3.3.5) IP 54 (with pleated filter and installation in accordance with section 3.3.2 or 3.3.3) IP 55 (with chopped-fibre filter and installation in accordance with section 3.3.4)
Type 1 (without filter and installation in accordance with section 3.3.2, 3.3.3 or 3.3.5) Type 12 (with pleated or chopped-fibre filter and installation in accordance with section 3.3.2 or 3.3.3)
Tab. 3: Technical specifications
16
Rittal roof-mounted fan
8. Technical specifications
133 H2
Fig. 5: Dimensions
400 400
258±2 258±2
H2 = 27.5 mm for SK 3138000
H2 = 34.6 mm for SK 3139100, SK 3139110, SK 3140100, SK 3140110, SK 3140140, SK 3140500, SK 3140510
9. Accessories
Pleated filter
To fit Model No. SK 3138000, SK 3139100, SK 3139110, SK 3140100, SK 3140110, SK 3140140, SK 3140500, SK 3140510 Tab. 4: Pleated filter Chopped-fibre filter
To fit Model No. SK 3138000, SK 3139100, SK 3139110, SK 3140100, SK 3140110, SK 3140140, SK 3140500, SK 3140510 Tab. 5: Chopped-fibre filter
Filter class in accordance with
DIN EN 779
ISO 16890
M5
ePM10 50 %
Filter class in accordance with
DIN EN 779
ISO 16890
G3
ISO coarse 50 %
Packs of 12 pc(s).
Model No. SK 3174120
Packs of 12 pc(s).
Model No. SK 3174100
Rittal roof-mounted fan
17
9. Accessories
Enclosure internal thermostat To fit Model No. SK 3139100, SK 3139110, SK 3140100, SK 3140110, SK 3140140, SK 3140500, SK 3140510
Tab. 6: Enclosure internal thermostat Digital enclosure internal temperature display and thermostat
To fit Model No. SK 3139100, SK 3139110, SK 3140100, SK 3140110, SK 3140140, SK 3140500, SK 3140510 Tab. 7: Digital enclosure internal temperature display and thermostat Hygrostat To fit Model No. SK 3139100, SK 3139110, SK 3140100, SK 3140110, SK 3140140, SK 3140500, SK 3140510 Tab. 8: Hygrostat Speed control To fit Model No. SK 3139100, SK 3139110, SK 3140100, SK 3140110 Tab. 9: Speed control Sensor for speed control To fit Model No. SK 3140500, SK 3140510 Tab. 10: Sensor for speed control Control unit for speed control To fit Model No. SK 3140500, SK 3140510 Tab. 11: Control unit for speed control Outlet filter To fit Model No. SK 3138000, SK 3139100, SK 3139110, SK 3140100, SK 3140110, SK 3140140, SK 3140500, SK 3140510 Tab. 12: Outlet filter
Packs of 1 pc(s).
Packs of 1 pc(s).
Packs of 1 pc(s).
Packs of 1 pc(s).
Packs of 1 pc(s).
Packs of 1 pc(s).
Packs of 1 pc(s).
Model No. SK 3110000
Model No. SK 3114200
Model No. SK 3118000
Model No. SK 3120200
Model No. SK 3235450
Model No. SK 3235440
Model No. SK 3243200
18
Rittal roof-mounted fan
10. Warranty
The conditions named in the sales and delivery conditions of the associated Rittal agents and subsidiaries apply.
11. Customer services addresses
Headquarters Germany RITTAL GmbH & Co. KG Auf dem Stuetzelberg 35745 Herborn Germany Phone +49(0)2772 505-1855 Fax +49(0)2772 505-1850 E-mail: [email protected]
Service HUB USA RITTAL North America LLC 801 State Route 55 Dock 25 Urbana, OH 43078 Phone: +1 800 477 4000, option 3 E-mail: [email protected]
Service HUB China RITTAL Electro-Mechanical Technology Co. Ltd. No. 1658, Minyi Road Songjiang District Shanghai, 201612 Phone +86 21 5115 7799-213 Fax +86 21 5115 7788 E-mail: [email protected]
Service HUB India RITTAL India Pvt. Ltd. Nos. 23 & 24, KIADB Industrial Area Veerapura Doddaballapur-561 203 Bengaluru District Phone +91 (80) 22890792 Fax +91 (80) 7623 343 E-mail: [email protected]
Rittal roof-mounted fan
19
20
Rittal roof-mounted fan
Notes
Rittal roof-mounted fan
21
Enclosures Power Distribution Climate Control IT Infrastructure Software & Services
You can find the contact details of all Rittal companies throughout the world here.
www.rittal.com/contact
RITTAL GmbH & Co. KG Auf dem Stuetzelberg · 35745 Herborn · Germany Phone +49 2772 505-0 E-mail: [email protected] · www.rittal.com
03.2022/D-0000-00000432-04-EN