Aerco 750 Through 6000 Benchmark And Benchmark Platinum Boilers Instruction Manual

Aerco 750 Through 6000 Benchmark And Benchmark Platinum Boilers Instruction Manual

AERCO logo750 through 6000 Benchmark and Benchmark Platinum Boilers
Instruction Manual

750 through 6000 Benchmark and Benchmark Platinum Boilers

Electrical Power Design Guide
Benchmark® and Benchmark Platinum Boilers
Models 750 through 6000 AERCO 750 through 6000 Benchmark and Benchmark Platinum Boilers fig 2

Other documents for this product include:
OMM-0127, GF-205-K BMK750K-3000K Installation-Startup KOREA
OMM-0128, GF-206-K BMK750K-3000K Operation- Maintenance KOREA
OMM-0136, GF-210 BMK750-6000 Platinum-Edge Installation-Startup
OMM-0137, GF-211 BMK750-6000 Platinum-Edge Operation-Service
OMM-0138, GF-212 BMK750-6000 Platinum-Edge Reference Manual
AERCO 750 through 6000 Benchmark and Benchmark Platinum Boilers fig 1TAG-0019, GF-2070 Benchmark Boiler Application Guide
TAG-0022, GF-2050 Benchmark Vent & Combustion Air Guide
TAG-0047, GF-2030 Benchmark Gas Guide

Disclaimer
The information contained in this manual is subject to change without notice from AERCO International, Inc. AERCO makes no warranty of any kind with respect to this material, including, but not limited to, implied warranties of merchantability and fitness for a particular application. AERCO International isnot liable for errors appearing in  this manual, not for incidental or  consequential damages occurring in connection with the furnishing, performance, or use of these materials.
Heating and Hot Water Solutions
AERCO International, Inc. • 100 Oritani Drive • Blauvelt, NY 10913
USA: T: (845) 580-8000 • Toll Free: (800) 526-0288 • AERCO.com
Technical Support • (800) 526-0288 • Mon-Fri, 8 am – 5 pm EST
© 2020 AERCO

General

Benchmark (BMK) Gas Fired Boilers are fully factory wired packaged units which require simple external power wiring as part of the installation (Figure 1). This technical guide is intended to help designers provide electrical power wiring (line voltage) to Benchmark units. Control wiring details are provided in other publications, depending upon unit application. This document is intended only as a guide and therefore cannot include all possible alternatives or unit applications. In order to comply with all codes and authorities having jurisdiction, designers and installers must plan the electrical wiring carefully and execute the installation completely. Emergency shutoffs, fusible fire switches, break glass stations, and other electrical requirements should be considered and installed whenever necessary.

Boiler Electrical Requirements

Benchmark boilers are available with the following power options:

BMK ModelVoltagePhaseAmperage
BMK750 — 1000 Domestic120 V10 / 60 Hz15
BMK750 — 1000 International220 V10 / 50-60 Hz20
BMK1500 — 2000 Domestic120 V10 / 60 Hz20
BMK1500 — 2000 International220 V10 / 50-60 Hz20
BMK2500 – 3000 Domestic208 V30 / 60 Hz20
480 V30 / 60 Hz15
BMK2500 – 3000 International380-415 V30 / 50-60 Hz15
BMK4000 – 5000N Domestic208 V30 / 60 Hz40
480 V30 / 60 Hz20
BMK4000 – 5000N International380-415 V30 / 50-60 Hz20
BMK5000 – 6000 Domestic208 V30 / 60 Hz30
480 V30 / 60 Hz20
BMK5000 – 6000 Canada575 V30 / 60 Hz20
BMK5000 – 6000 International380-415 V30 / 50-60 Hz20

Voltages lower than those specified in the table above will result in increased wear and premature failure of the blower motor. Wire size and type should be made per the National Electrical Code based on length and load.
For all Benchmark models, the power box for field wiring connections is located in the upper right corner behind the unit front panel. All copper wire must be connected to the power box.AERCO 750 through 6000 Benchmark and Benchmark Platinum Boilers fig 3

Figure 1: Service Disconnect Switch Typical LocationAERCO 750 through 6000 Benchmark and Benchmark Platinum Boilers fig 4Figure 2a: Power Box Components, BMK750 & 1000 – DOMESTIC AERCO 750 through 6000 Benchmark and Benchmark Platinum Boilers fig 5

Figure 2a: Power Box Components, BMK750 & 1000 – INTERNATIONALAERCO 750 through 6000 Benchmark and Benchmark Platinum Boilers fig 6

Figure 3a: Power Box Components, BMK1500 – 2000 – DOMESTIC AERCO 750 through 6000 Benchmark and Benchmark Platinum Boilers fig 7Figure 3b: Power Box Components, BMK1500 – 2000 – INTERNATIONALAERCO 750 through 6000 Benchmark and Benchmark Platinum Boilers fig 8Figure 4a: Power Box Components, BMK2500 – 6000 – DOMESTIC AERCO 750 through 6000 Benchmark and Benchmark Platinum Boilers fig 9

Figure 4b: Power Box Components, BMK2500 – 6000 – INTERNATIONAL

Provisions for Service

Designers must provide emergency shutoffs and other devices to satisfy electrical codes. It is also recommended to provide an electrical shutoff disconnect switch of suitable load carrying characteristics near each BMK boiler. No electrical boxes or field components should be mounted to the surface of the boiler or where they would interfere with the removal of the side or top panels for maintenance. The service disconnect switch should be mounted near the unit, as illustrated in Diagram 1. Wiring conduit, EMT, or other wiring paths should not be secured to the unit but supported externally. Electricians should be instructed as to where the wiring conduit should be located, such as away from the relief valve discharge, drains, etc. All electrical conduit and hardware should be installed so that it does not interfere with the removal of any covers, inhibit service or maintenance, or  prevent access between the unit and walls or another unit.

Boiler Wiring

A dedicated protected circuit should be provided from the power source to the boiler. No other electrical devices should be permanently wired on the same circuit. The protected circuit and circuit breaker switch must be sized for the amperage values below. An emergency switch (electrical shutoff) must be wired in series with power to the unit. Connecting an emergency shutoff switch (E-stop) to the main power terminals of the boiler is the recommended and safest way to totally disable and un-power the unit. Use of the remote interlock, located on the I/O board, is not recommended since it does not cutoff power within the unit, it only disables it. Under no circumstance should the remote interlock of the BST Manager unit be used as an emergency switch for the plant.AERCO 750 through 6000 Benchmark and Benchmark Platinum Boilers fig 10

The following table lists the input power requirements for all Benchmark boilers, including the diagram number of each model’s corresponding schematic diagram:

DOMESTIC UNITSINTERNATIONAL UNITS
BMK ModelDiag.Voltage/Phase/FrequencyAmpsWiresDiag.Voltage/Phase/FrequencyAmpsWires
750 — 1000la120V/ 10/60 Hz©15 A3lb220V / 1 Z / 50- 60 Hz20 A3
1500 — 200020 A
2500/30002208V / 30 / 60 Hz20 A5
4
4
3b380-415V / 3.Z / 50- 60 Hz15 A4 I
3a480V / 30 / 60 Hz15 A
4000/5000N7208 V / 30 / 60 Hz40A
6a480V / 30 / 60 Hz20 A46b380-415V / 3Z / 50- 60 Hz20 A4
5000/60004208V / 30 / 60 Hz30A4
5a480V or 575V / 3Z / 60 Hz20 A45b380-415V / 3Z / 50-60 Hz20 A4

For applicable wiring connections, refer to the schematic diagrams below. AERCO 750 through 6000 Benchmark and Benchmark Platinum Boilers fig 11

Diagram 1a – BMK750 – 2000: 120 V / 1ø / 60 Hz Wiring Schematic – 3 Wire – DOMESTIC
AERCO 750 through 6000 Benchmark and Benchmark Platinum Boilers fig 12
Diagram 1b – BMK750 – 2000: 220 V / 1ø / 50-60 Hz Wiring Schematic – 3 Wire – INTERNATIONAL
AERCO 750 through 6000 Benchmark and Benchmark Platinum Boilers fig 13
Diagram 2 – BMK2500/3000: 208 V / 3ø / 60 Hz Wiring Schematic- 5 Wire – DOMESTIC
AERCO 750 through 6000 Benchmark and Benchmark Platinum Boilers fig 14Diagram 3a – BMK2500-5000N: 480 V / 3ø / 60 Hz Wiring Schematic- 4 Wire – DOMESTIC
AERCO 750 through 6000 Benchmark and Benchmark Platinum Boilers fig 15

Diagram 3b- BMK2500-5000N: 380-415 V / 3ø / 50-60 Hz Wiring Schematic- 4 Wire – INTERNATIONAL
AERCO 750 through 6000 Benchmark and Benchmark Platinum Boilers fig 16
Diagram 4: BMK5000/6000: 208 V / 3ø / 60 Hz Wiring Schematic- 4 Wire – DOMESTIC
AERCO 750 through 6000 Benchmark and Benchmark Platinum Boilers fig 17Diagram 5a: BMK5000/6000: 480 V or 575 V / 3ø / 60 Hz Wiring Schematic- 4 Wire – DOMESTIC
AERCO 750 through 6000 Benchmark and Benchmark Platinum Boilers fig 18Diagram 5b: BMK5000/6000: 380-415 V / 3ø / 50-60 Hz Wiring Schematic- 4 Wire – INTERNATIONAL
AERCO 750 through 6000 Benchmark and Benchmark Platinum Boilers fig 19
Diagram 6a – BMK4000-5000N: 480 V / 3ø / 60 Hz Wiring Schematic- 4 Wire – DOMESTIC
AERCO 750 through 6000 Benchmark and Benchmark Platinum Boilers fig 20Diagram 6b- BMK4000-5000N: 380-415 V / 3ø/ 50-60 Hz Wiring Schematic- 4 Wire – DOMESTIC AERCO 750 through 6000 Benchmark and Benchmark Platinum Boilers fig 21

Diagram 7: BMK4000-5000N: 208 V / 3ø / 60 Hz Wiring Schematic- 4 Wire – DOMESTIC

Multiple Unit Wiring

Whenever multiple units are installed within the same mechanical spaces, electrical code requirements call for a single electrical shutoff for emergency use. It is the responsibility of the electrical designer to comply with local codes and regulations affecting an individual installation.
Change Log:

DateDescriptionChanged by
6/9/2020Rev 0:
Added BMK5000N information where applicable.
Linley Thobourne, Chris
Blair
8/6/2020Rev P:
Added diagram and description of E-Stop power shutoff switch to Section 4.
Added 208 V row to BMK 4000/5000N — Domestic, changed amperage from 15 to 20 in Sections 2 and 4. Added new wiring schematic diagrams 6a, 6b and 7 for the BMK4000 & 5000N.
Chris Blair

AERCO logoAERCO 750 through 6000 Benchmark and Benchmark Platinum Boilers icon© AERCO International, Inc., 2020

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals