Cwce Em30 Constant Power Led Emergency Converter Instruction Manual

EM30 Constant Power LED Emergency Converter

Product Information

The EM30 15W/20W/30W All In One Constant Power LED Emergency
Converter is designed to be used with high bay luminaires that have
integrated LEDs and remote LED drivers. It can be suspended with a
luminaire to provide a back-up supply in case of a power outage.
The emergency driver requires a permanent live un-switched supply
to maintain battery charge and has a rated output of 1.5 or 3
hours. It has an IP65 rating.

Features

  • Constant power output for LED modules with a wide rated voltage
    of 30-150VDC
  • Two gears for adjusting maximum output voltage of 60V/150V
  • Three gears for adjusting emergency power of 15W/20W/30W
  • Wireless remote control for emergency testing
  • Maintenance for emergency lighting system
  • Conforms to EN 61347-1, EN 61347-2-7, and EN 61347-2-13
  • Equipped with IP68 certified water-proof connector
  • Automatically starts to work during voltage fluctuation and
    flicker
  • Over-charge, over-current, short-circuit, and deep discharge
    protection for battery
  • Test button for a quick functional test
  • Design life:

Model List

Model No.Input VoltageOutput PowerTest Mode
EM30-180A/B-6Ah-LFP220-240VAC15WMT/AT
EM30-120A/B-6Ah-LFP220-240VAC20WMT/AT
EM30-090A/B-6Ah-LFP220-240VAC30WMT/AT

Specifications

  • Output Power: EM30-180A-6Ah-LFP, EM30-180B-6Ah-LFP,
    EM30-120-6Ah-LFP, EM30-120B-6Ah-LFP, EM30-090A-6Ah-LFP,
    EM30-090B-6Ah-LFP
  • Discharge Duration: 180Mins, 120Mins, 90Mins
  • Input Voltage: 220-240VAC
  • Input Current: MT/AT
  • Power Factor: N/A
  • Output Voltage: 30-150VDC
  • Output Current: 15W/20W/30W
  • Battery: LiFePO4 12.8V 6Ah
  • Charge Time: 24H
  • Test Mode: MT/AT
  • IP Rating: IP65
  • Ambient Temperature: N/A

Wiring Diagram

(insert wiring diagram image here)

Product Usage Instructions

  1. Attach the EM30 emergency driver to a high bay luminaire with
    integrated LEDs and remote LED drivers.
  2. Connect the EM30 to a permanent live un-switched supply to
    maintain battery charge.
  3. In the event of a power outage, the battery will supply the
    integrated LEDs at rated output for 1.5 or 3 hours depending on the
    model.
  4. The EM30 has a wireless remote control for emergency
    testing.
  5. The EM30 has a test button for a quick functional test.
  6. After repairing a service fault, press and hold the test button
    for more than 2 seconds to reset the flashing indicator light to
    green.

EM30 15W/20W/30W ALL IN ONE
CONSTANT POWER LED EMERGENCY CONVERTER

Smart Charge

1.5 or 3 Hours

IP 65

Product Information
This emergency driver is designed for use with the high bay luminaires with integrated LEDs and remote LED drivers. It can be suspended with a luminaire to provide a back-up supply in the event of the power cut. This emergency driver requires a permanent live un-switched supply to maintain the battery charge. In the event of the power cut, the battery will supply the integrated LEDs at rated output.

Features
Constant poweroutput For LED modules with a widerated voltage
30-150VDC Tow gears for adjustingmaximum output
voltage60V/150V Three gears for adjusting emergency power
15W/20W/30W Wireless remote control for emergency testing For high bay luminaires with integrated LEDs
and remote LED drivers Maintenance of emergency lighting system Conforms to EN 61347-1,EN 61347-2-7 and EN
61347-2-13 Equipped with IP68 certified water-proof
connector Automatically starts to work during voltage
fluctuation and flicker. 1.5/2/3 hours rated duration Over-charge, over-current, short-circuit and
deep discharge protection for battery Test button for a quick functional test Design life:
8 years @ 25°C max ambient temperatures. 6 years @ 35°C max ambient temperatures. 4 years @ 45°C max ambient temperatures. Warranty 3 years.

Wire Color 1mm² Brown 1mm² Black 1mm² Blue 1mm² Yellow/Green

Explain AC Line Ac Line Switch Neutral Ground

86

PG11

226 L=1000
365

L=300

PG7 PG9
95 (Unit: mm)

Model List

Model No.

Input Voltage Output Power Test Mode

EM30-180A/B-6Ah-LFP

220-240VAC

15W

EM30-120A/B-6Ah-LFP

220-240VAC

20W

EM30-090A/B-6Ah-LFP

220-240VAC

30W

MT/AT MT/AT MT/AT

Charge Time Discharge Duration Battery

24H

180Mins

24H

120Mins

24H

90Mins

LiFePO4 12.8V 6Ah LiFePO4 12.8V 6Ah LiFePO4 12.8V 6Ah

2/4

Specifications

Output Power Discharge Duration Input Voltage Input Current Power factor Output Voltage Output Current Battery Charge Time Test Mode IP Rating Ambient Temperature

EM30-180A-6Ah-LFP
15W 180Mins 220-240VAC,50/60Hz 100mA Max. 0.5 30-60VDC 250-500mA LiFePO4 12.8V 6Ah 24H MT/AT IP65 0°C-45°C

Output Power Discharge Duration Input Voltage Input Current Power factor Output Voltage Output Current Battery Charge Time Test Mode IP Rating Ambient Temperature

EM30-180B-6Ah-LFP
15W 180Mins 220-240VAC,50/60Hz 100mA Max. 0.5 60-150VDC 100-250mA LiFePO4 12.8V 6Ah 24H MT/AT IP65 0°C-45°C

Wiring diagram

EM30-120-6Ah-LFP
20W 120Mins 220-240VAC,50/60Hz 100mA Max. 0.5 30-60VDC 330-670mA LiFePO4 12.8V 6Ah 24H MT/AT IP65 0°C-45°C
EM30-120B-6Ah-LFP
20W 120Mins 220-240VAC,50/60Hz 100mA Max. 0.5 60-150VDC 130-330mA LiFePO4 12.8V 6Ah 24H MT/AT IP65 0°C-45°C

EM30-090A-6Ah-LFP
30W 90Mins 220-240VAC,50/60Hz 100mA Max. 0.5 30-60VDC 500-1000mA LiFePO4 12.8V 6Ah 24H MT/AT IP65 0°C-45°C
EM30-090B-6Ah-LFP
30W 90Mins 220-240VAC,50/60Hz 100mA Max. 0.5 60-150VDC 200-500mA LiFePO4 12.8V 6Ah 24H MT/AT IP65 0°C-45°C

Antenna Emergency driver

-DC

+DC

-DC

+DC

Emergency function connector

Brown L Black SL
Ground Blue N

Switch & Indicator

LN

AC input port

LN

15W 20W 30W
Power DIP Switch

3/4

System Status indication

TEST AT MT

LED indicator

LED indication
Greenpermanent
GreenSlow flash (4s on, 1s off) Red Slow flash (4s on, 1s off) Red medium flash (1s on, 1s off) Red fast flash once, then pause (o.5s on, 0.5s off, 4s pause) Fast flash twice, then pause (o.5s on, 0.5s off, 4s pause) Fast flash 3 times, then pause (o.5s on, 0.5s off, 4s pause) Fast flash 4 times, then pause (o.5s on, 0.5s off, 4s pause) Fast flash 4 times, then pause (o.5s on, 0.5s off, 4s pause)
Green and Red Off

System Status Power on and System OK Charging
Duration testand 5days indication following completion of test Function test Battery not connected or short-circuited Low battery capacity
Charge circuit fault
LED driver circuit fault LED lamp fault Power off

Notes:After repairing a service fault, press and hole the test button for more than 2 seconds to reset the flashing indicator light to green.

Green Green

Permanent Off

Normal standby mode or charging Power off or battery fault

Remote Control Operation Instructions

Use 9V carbon block battery to drive the remote control

A. Press the remote control button “A” once to enter the emergency test mode of nominal duration.
B. Press the remote control button “B” once to close or exit the emergency mode.
C. From side switch to “N” to connect the battery, remote control is in remote control state. If toggled switch to “F”, the battery will be disconnected, and the remote control will be unavailable (it is recommended to disconnect the battery if it is not used for a long time).
D. Other parameters 1) Use 433MHz transmission and reception frequency, not easily interfered. 2) Remote control direction 360 degrees without dead angle, not easy to block. 3) Super power transmitting and receiving antenna, remote control distance is longer, linear remote control distance 20-50M. 4) No need to learn, use one-to-many control mode, one remote control can control all emergency lamps.

4/4

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals