POTTER PNA Portable Nitrogen Analyzer

POTTER PNA Portable Nitrogen Analyzer

Features

  • Durable N2 analyzer
  • One-button calibration
  • Auto-off
  • 3-digit display
  • Maintenance free

Description

The Portable Nitrogen Analyzer is an easy way to determine the purity of nitrogen that the Potter Nitrogen Generator is producing. Since the analyzer is portable, it gives you the ability to check the end of the line purity of the fire sprinkler system, ensuring the system is protected. Store the N2 analyzer in a temperature similar to its ambient environment of daily use.

Operation

Prior to turning on the unit, wait 5 minutes to allow the sensor to reach equilibrium. Using the “ON/OFF” key, make sure the unit is in the power “ON” mode. Press and hold the Calibration Key for 3 seconds until the display reads “CAL”. This will calibrate the N2 Analyzer to room air. A new calibration is required when the measured N2 percentage is above 80.1% N2 or below 78.1% N2. The N2 Analyzer is ready to use.

Ordering Information

ModelDescriptionStock No.
PNAPortable Nitrogen Analyzer1119504

Technical Specifications

Measurement Range0-99.9%
Resolution0.1% Nitrogen
Operating Temperature15°C to 40°C (59°F to 104°F)
Storage Temperature-15°C to 50°C (5°F to 122°F)
Sensor TypeGalvanic fuel cell
Battery Type3V Lithium button cell (non-replaceable)