Senva Pw30 Wet Pressure Transmitter Instruction Manual

Senva Pw30 Wet Pressure Transmitter Instruction Manual

SENVA logoPW30 Wet Pressure Transmitter
Instruction ManualSENVA PW30 Wet Pressure TransmitterINSTALLATION INSTRUCTIONS
PW30
Wet-Wet Pressure Transmitter

PW30 Wet Pressure Transmitter

IMPORTANT WARNINGS

  • Only qualified trade installers should install this product
  • This product is not intended for life-safety applications
  • Do not install in hazardous or classified locations
  • The installer is responsible for all applicable codes
  • De-energize power supply prior to installation or service

PRODUCT APPLICATION LIMITATION:

Senva products are not designed for life or safety applications. Senva products are not intended for use in critical applications such as nuclear facilities, human implantable device or life support. Senva is not liable, in whole or in part, for any claims or damages arising from such uses.
IMPORTANT!
-Do NOT exceed gauge pressure rating of sensor.
-Use ONLY Senva gauge pressure sensors provided with your PW transmitter to obtain the specified transmitter accuracy.
-Follow instructions step by step to ensure proper setup.

INSTALLATION

1. Identify PWC sensors A & B and their respective PSIG rating.
If the expected system gauge pressure exceeds the PSIG rating on the PWT sensors call factory and DO NOT proceed with install.SENVA PW30 Wet Pressure Transmitter - Identify PWC sensors2. Plumb PWT sensors to media. Sensor A is intended for supply pressure and sensor B is intended for return pressure of the system. Plumb PWT sensors to the side or top of pipe, as plumbing to the bottom will cause sediment to settle and could clog or affect sensor accuracy. It is advisable to use a single wrap of PTFE tape on the PWT sensors threads, or other thread sealing alternative, to improve sensor accuracy.
No bypass valve manifold is necessary. Use only Senva gauge pressure sensor elements provided with your transmitter. Optional shutoff valves are available – Senva recommends closing service valves when flushing system to prevent containments and water hammer from damaging PWT sensing elements.
4. Run the appropriate length cables between the PW transmitter and PWT sensors.
Senva recommends 22AWG stranded, 4 conductor shielded cable to wire between the PW transmitter and PWT sensors.
5. Loosen the top screw on each PWT sensor and remove the terminal block for wiring as shown below:SENVA PW30 Wet Pressure Transmitter - Conduit Adapter6. Run the cable through the conduit adapter and connect the wires to the PWT terminal block. Note that the conduit terminal block is numbered and color coded to match the terminal label colors on the PW transmitter.
IMPORTANT: DO NOT connect the shield at the PWT sensor element end. The shielding should only be connected to the ground terminal at the PW transmitter end.
SENVA PW30 Wet Pressure Transmitter - Identify PWC sensors 1

PinConnectionColor
1PWRRed
2GNDGreen
3Signal (S1/S2)White

Earth

ShieldBlack

7. Reassemble the PWT conduit adapter and terminal block.
Place the rubber cover back on the conduit adapter and plug the adepter onto the PWT sensor. Tighten the assembly screw. DO NOT attempt to plumb or tighten the PWT sensors while wires are attached, as you run the risk of pulling wires from cable attachments.
8. Wire PWT sensors A & B to the PW Transmitter terminals labeled A & B respectively. See above table if wiring a pre ordered cable length for color coordination. For strain relief, tighten cable glands.SENVA PW30 Wet Pressure Transmitter - SENSORIMPORTANT: Shielding should be connected to the shield (Earth ) Terminal at the PW transmitter end, and left unconnected at the PWT sensor element end.
9. Connect conduit fittings to the PWT sensors and PW transmitter. Use water tight fittings if required by your installation conditions.
10. Wire PW transmitter for voltage or current output as shown (Remote zero wiring is optional):SENVA PW30 Wet Pressure Transmitter - transmitter11. Select 20mA, 5V or 10V output using OUTPUT switch based on wiring configuration.
SENVA PW30 Wet Pressure Transmitter - switch based12. Configure output range and sensor PSIG using DIP switches 1-7. DIP 1-3 set the sensor PSIG corresponding to the PWT ordered. DIP 4-7 are used to set the desired output signal range. Both use the binary code system outlined in the table.
PW Transmitter DIP Switch Configuration:
DIP Switch SettingsSENVA PW30 Wet Pressure Transmitter - DIP Switch

DIPFunctionLEFTRIGHT
1SENSOR20 (off)1 (on)
2SENSOR101
3SENSOR001
4RANGE301
5RANGE201
6RANGE101
7RANGE001
8UnitsKPAPSI
9UNI/BIBIUNI
10MODEFASTSLOW
11SWAPB-AA-B
12ABSABS+/-
DIPBinarySENSOR (PSIG)
1-3000TEST
00115*
01025*
01150
100100
101200*
110250
111500
DIPBinaryRANGE (PSID)
4-700000-1
00010-2
00100-5
00110-10
01000-15
01010-20
01100-25
01110-30
10000-40
10010-50
10100-75
10110-100
11000-125
11010-150
11100-250
11110-500

*15, 25 and 200 PSIG sensors are not offered by senva
13. Inspect LCD for readings. LCD toggles between sensor A reading, sensor B reading, and PSID reading. Sensor A reading is indicated by a tick mark on the top left of LCD. Sensor B reading is indicated by a tick mark at the bottom left of LCD. PSID reading is displayed without any mark at the left of the LCD.
O/R symbol will flash in bottom center of LCD if differential pressure reading is over range. If this occurs, select larger PSID range to avoid clipping of readings.
14. Check remaining DIP switch (8-12) configurations for additional setup options:
Units: LCD will display readings in PSI or kPa. LCD will indicate PSI or kPa at top of screen.
UNI/BI: PW transmitter can be setup in Uni or Bi directional mode.
Bi-Directional Mode Example range set at 100 PSID:

ABDPOUTPUT
1000+10020mA/10V/5V
10050+5016mA/7.5V/3.75V
5050012mA/5V/2.5V
50100-508mA/2.5V/1.25V
0100-1004mA/0V/0V

MODE: In ‘Slow Mode’ the output returns a reading averaged over 64 samples. In ‘Fast Mode’ the output returns the most recently calculated reading for PSI.
SWAP: If PWT sensor A was plumbed to the return (low) side and PWT sensor B was plumbed to the supply (high) side instead of re-plumbing the sensors, the Port Swap can be utilized without a physical reconfiguration.
ABS: In Absolute Mode, values will always be reported positive.
15. To custom zero the device (optional), hold down the zero button for 5 seconds (until the LCD blinks once). Hold down for 10 seconds (until LCD blinks twice) to  reset/clear the zero value.
16. Seal remaining conduit knockouts on PW transmitter.

SENVA TECHNICAL SUPPORT

Need further assistance? Call our toll-free number for live technical support: (866) 660-8864 or feel free to email us at [email protected]

DIMENSIONS

PW30WSENVA PW30 Wet Pressure Transmitter - DIMENSIONS

SPECIFICATIONS

Power supplyVoltage output mode (0-5v) Voltage output mode (0-10v) Current (4-20mA) output mode12-30VDC/24VAC (1), 20mA max.
13-30VDC/24VAC required for 10V FS output 15-30VDC(0 ohm)/16-30VDC (250 Ohm)/
18-30VDC (500 Ohm) , 20mA max.
OutputsSwitch selectable2-wire 4-20mA, 3-wire 0-5V/10V
Operating TemperatureTransmitter-22 to 158oF (-30 to 70C)
Media CompatibilityType TemperatureWater, other 316 SS compatible media (316L diaphragm) 32 to 250oF (0-125oC)
Zero adjustmentAutomaticPushbutton, Remote zero
Press button for 5 seconds to re-zero
Hold for 10 seconds to restore factory settings
Sensor TypeMicro-machined silicon strain gauge
PW Transmitter Accuracy(2)
Range according to PSID table in PW Transmitter DIP Switch Configuration table
Sensor PSIG2% Accurate ranges1% Accurate ranges
250-1 / 0-2 PSID0-5 / 0-10 / 0-15 / 0-20 / 0-25 PSID
500-10 / 0-15 PSID0-20 / 0-25 / 0-30 / 0-40 / 0-50 PSID
1000-15 / 0-20 / 0-25 / 0-30 PSID0-40/ 0-50 / 0-75 / 0-100 PSID
2500-30 / 0-40 / 0-50 PSID0-75 / 0-100 / 0-125 / 0-150 / 0-250 PSID
5000-75 / 0-100 / 0-125 PSID0-150 / 0-250 / 0-500 PSID
Sensor PerformanceAccuracy< +/-0.25% BFSL
Stability (1 year)+/-0.2% FS, typ
Over-range protection200% rated pressure
Pressure Cycles> 100 Million
Compensated Range14 to 158oF (-10-70oC)
Temperature Compensation
%FS/C
Zero, <+/-0.03(<100kPa), <+/-0.02( >100kPa) Span,<+/-0.03(<100kPa), <+/-0.02( >100kPa)
Vibration10G peak, 20 to 2000 Hz.
Enclosure, PW30MConstructionPowder coated steel
RatingNEMA 3R
Enclosure, PW30WConstructionPC/ABS
RatingNEMA 4X
Enclosure, PWT[xxx] SensorConstructionStainless Steel, 304, 1/4” MNPT, PG9 Conduit Fitting
  1. One side of transformer secondary is connected to signal common. Dedicated transformer is recommended.
  2. Because of lower accuracy, it is not factory recommended to use an output range less that 10% of the total sensor PSIG.

TROUBLESHOOTING

Symptom

Solution

No outputCheck wiring. Ensure power supply meets requirements
Pressure reading errorVerify control panel software is configured for correct output scaling
Verify switch and jumper settings
Device will not zeroHold ZERO button for full 5-seconds until LCD blinks once
Continue holding ZERO button for 10-15 seconds, until LCD blinks twice, to restore factory settings

Issued1/6/2021 Document #152-0412-0CSENVA logo

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals