Danfoss Fc 360 Vlt Automationdrive Frequency Converter User Guide

Danfoss Fc 360 Vlt Automationdrive Frequency Converter User Guide

Danfoss FC 360 VLT AutomationDrive Frequency Converter User Guide
Danfoss FC 360 VLT AutomationDrive Frequency Converter

Introduction

This operating guide provides necessary information for qualified personnel to install and commission the AC drive. Read and follow the instructions to use the drive safely and professionally.

Dustbin Icon
Do not dispose of equipment containing electrical components together with domestic waste. Collect it separately in accordance with local and currently valid legislation.

Safety

Pay particular attention to the safety instructions and general warnings to avoid the risk of death, serious injury, and equipment or property damage.

Warning IconWARNING Warning Icon

HIGH VOLTAGE
AC drives contain high voltage when connected to AC mains input, DC supply, or load sharing.

UNINTENDED START
The motor may start from control panel, I/O inputs, or fieldbus at any time, when the drive is connected to the AC mains, DC supply, or load sharing.

DISCHARGE TIME
The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be present even when the warning indicator lights are off.

  • Stop the motor, and disconnect AC mains, permanent magnet type motors, and remove DC-link supplies, including battery backups, UPS, and DC-link connections to other drives.
  • Wait for the capacitors to discharge fully and measure it before performing any service or repair work.
  • The minimum waiting time is 4 minutes for 0.37–7.5 kW (0.5–10 hp) drives and 15 minutes for 11–90 kW (15–125 hp) drives.

LEAKAGE CURRENT
Leakage currents of the drive exceed 3.5 mA. Make sure that the minimum size of the ground conductor complies with the local safety regulations for high-touch-current equipment.

Installation

Mechanical Dimensions

Mechanical Dimensions

Illustration 1: Mechanical Dimensions, Enclosure Sizes J1–J7

Enclosure size 380–480 VJ1J2J3J4J5J6J7
Power size [kW (hp)]0.37–2.2(0.5–3)3.0–5.5(4.0–7.5)7.5(10)11–15(15–20)18.5–22(25–30)30–45(40–60)55–90(75–125)
Height A210 (8.3)272.5 (10.7)272.5 (10.7)317.5 (12.5)410 (16.1)515 (20.3)550 (21.7)
Width B75 (3.0)90 (3.5)115 (4.5)133 (5.2)150 (5.9)233 (9.2)308 (12.1)
Depth C168 (6.6)168 (6.6)168 (6.6)245 (9.6)245 (9.6)241 (9.5)323 (12.7)
Depth C(1)173 (6.8)173 (6.8)173 (6.8)250 (9.8)250 (9.8)241 (9.5)323 (12.7)
D180 (7.1)240 (9.4)240 (9.4)270 (10.6)364.7 (14.4)452 (17.8)484.5 (19.0)
Mounting holes
a198 (7.8)260 (10.2)260 (10.2)297.5 (11.5)390 (15.4)495 (19.5)521 (20.5)
b60 (2.4)70 (2.8)90 (3.5)105 (4.1)120 (4.7)200 (7.9)270 (10.6)
Mounting screwM4M5M5M6M6M8M8
Removing the Front Cover

Procedure:
Remove the front cover with a screwdriver.

Illustration 2: Removing the Front Cover
Removing the Front Cover

Illustration 5: Mains, Motor, and Ground Connections (Enclosure Sizes J1–J5)
Removing the Front Cover

Connecting to Mains, Motor, Control Terminals, and Relays

Illustration 3: Control Terminals and Relays Connections (Enclosure Sizes J1–J5)
Control Terminals

Illustration 4: Control Terminals and Relays Connections (Enclosure Sizes J6–J7)
Control Terminals

Illustration 6: Mains, Motor, and Ground Connections (Enclosure Sizes J6–J7)
Control Terminals

Control Terminals

Illustration 7: Control Terminals
Control Terminals

Specifcations

Table 2: Electrical Data for High Overload, Mains Supply 3×380–480 V AC, Enclosure Size J1–J3

DriveHK37HK55HK75H1K1H1K5H2K2H3K0H4K0H5K5H7K5
Enclosure sizeJ1J1J1J1J1J1J2J2J2J3
High overload=150–160 % current during 60 s
Typical shaft output [kW]0.370.550.751.11.52.2345.57.5
Typical shaft output [hp]0.50.7511.52345.57.510
Output current (3-phase)
Continuous (3×380–440 V) [A]1.21.72.233.75.37.291215.5
Continuous (3×441–480 V) [A]1.11.62.12.83.44.86.38.21114
Intermittent (60 s overload) [A]1.92.73.54.85.98.511.514.419.224.8
Continuous kVA (400 V AC) [kVA]0.841.181.532.082.573.684.996.248.3210.74
Continuous kVA (480 V AC) [kVA]0.91.31.72.52.84.05.26.89.111.6
Enclosure sizeJ1J1J1J1J1J1J2J2J2J3
Maximum input current
Continuous (3×380–440 V) [A]1.21.62.12.63.54.76.38.311.215.1
Continuous (3×441–480 V) [A]1.01.21.82.02.93.94.36.89.412.6
Intermittent (60 s overload)1.92.63.44.25.67.510.113.317.924.2
Maximum cable size (mains, motor, brake, and load sharing) [mm2 (AWG)]4 (12)
Estimated power loss at rated maximum load [W]20.8825.1630.0140.0152.9173.9794.81115.5157.54192.83
Weight [kg (lb)](Enclosure protection rating IP20)2.3(5.1)2.3(5.1)2.3(5.1)2.3(5.1)2.3(5.1)2.5(5.5)3.6(7.9)3.6(7.9)3.6(7.9)4.1(9.0)
Efficiency [%]96.297.097.297.497.497.697.597.697.798.0

Table 3: Electrical Data for High Overload, Mains Supply 3×380–480 V AC, Enclosure Size J4–J7

DriveH11KH15KH18KH22KH30KH37KH45KH55KH75K
Enclosure sizeJ4J4J5J5J6J6J6J7J7
High overload=150–160% current during 60 s
Typical shaft output [kW]111518.5223037455575
Typical shaft output [hp]1520253040506075100
Output current (3-phase)
Continuous (3×380–440 V) [A]23313742.5617390106147
Continuous (3×441–480 V) [A]2127344052657796124
Intermittent (60 s overload) [A]34.546.555.563.891.5109.5135159220.5
Continuous kVA (400 V AC) [kVA]15.9421.4825.6429.4542.350.662.473.4101.8
Continuous kVA (480 V AC) [kVA]17.522.428.333.343.254.064.079.8103.1
Maximum input current
Continuous (3×380–440 V) [A]22.129.935.241.55770.384.2102.9140.3
Continuous (3×441–480 V) [A]18.424.729.334.649.360.872.788.8121.1
Intermittent (60 s overload)33.244.952.862.385.5105.5126.3154.4210.5
Maximum cable size (mains, motor, brake, and load sharing) [mm2 (AWG)]16 (6)50 (1/0)95 (3/0)
Estimated power loss at rated maximum load [W]289.53393.36402.83467.52630848117512501507
Weight [kg (lb)](Enclosure protection rating IP20)9.4(20.7)9.5(20.9)12.3(27.1)12.5(27.6)22.4(49.4)22.5(49.6)22.6(49.8)37.3(82.2)38.7(85.3)
Efficiency [%]97.897.898.197.998.198.097.798.098.2

Table 4: Electrical Data for Normal Overload, Mains Supply 3×380–480 V AC, Enclosure Size J4–J7

DriveQ11KQ15KQ18KQ22KQ30KQ37KQ45KQ55KQ75KQ90K
Enclosure sizeJ4J4J5J5J6J6J6J7J7J7

Normal overload=110% current during 60 s

Typical shaft output [kW]111518.522303745557590
Typical shaft output [hp]1520253040506075100125
Output current (3-phase)
Continuous (3×380–440 V) [A]23313742.5617390106147177
Continuous (3×441–480 V) [A]2127344052657796124160
Intermittent (60 s overload) [A]25.334.140.746.867.180.399116.6161.7194.7
Continuous kVA (400 V AC) [kVA]15.9421.4825.6429.4542.350.662.473.4101.8122.6
Continuous kVA (480 V AC) [kVA]17.522.428.333.343.254.064.079.8103.1133

Maximum input current

Continuous (3×380–440 V) [A]22.129.935.241.55770.384.2102.9140.3165.6
Continuous (3×441–480 V) [A]18.424.729.334.649.360.872.788.8121.1142.7
Intermittent (60 s overload)24.332.938.745.762.777.392.6113.2154.3182.2
Maximum cable size (mains, motor, brake, and load sharing) [mm2 (AWG)]16 (6)50 (1/0)95 (3/0)120 (4/0)
Estimated power loss at rated maximum load [W]289.53393.36402.83467.526308481175125015071781
Weight [kg (lb)]

(Enclosure protection rating IP20)

9.4

(20.7)

9.5

(20.9)

12.3

(27.1)

12.5

(27.6)

22.4

(49.4)

22.5

(49.6)

22.6

(49.8)

37.3

(82.2)

38.7

(85.3)

40.7

(89.7)

Efficiency [%]97.897.898.197.998.198.097.798.098.298.3

Table 4: Electrical Data for Normal Overload, Mains Supply 3×380–480 V AC, Enclosure Size J4–J7

DriveQ11KQ15KQ18KQ22KQ30KQ37KQ45KQ55KQ75KQ90K
Enclosure sizeJ4J4J5J5J6J6J6J7J7J7
Normal overload=110% current during 60 s
Typical shaft output [kW]111518.522303745557590
Typical shaft output [hp]1520253040506075100125
Output current (3-phase)
Continuous (3×380–440 V) [A]23313742.5617390106147177
Continuous (3×441–480 V) [A]2127344052657796124160
Intermittent (60 s overload) [A]25.334.140.746.867.180.399116.6161.7194.7
Continuous kVA (400 V AC) [kVA]15.9421.4825.6429.4542.350.662.473.4101.8122.6
Continuous kVA (480 V AC) [kVA]17.522.428.333.343.254.064.079.8103.1133
Maximum input current
Continuous (3×380–440 V) [A]22.129.935.241.55770.384.2102.9140.3165.6
Continuous (3×441–480 V) [A]18.424.729.334.649.360.872.788.8121.1142.7
Intermittent (60 s overload)24.332.938.745.762.777.392.6113.2154.3182.2
Maximum cable size (mains, motor, brake, and load sharing) [mm2 (AWG)]16 (6)50 (1/0)95 (3/0)120 (4/0)
Estimated power loss at rated maximum load [W]289.53393.36402.83467.526308481175125015071781
Weight [kg (lb)](Enclosure protection rating IP20)9.4(20.7)9.5(20.9)12.3(27.1)12.5(27.6)22.4(49.4)22.5(49.6)22.6(49.8)37.3(82.2)38.7(85.3)40.7(89.7)
Efficiency [%]97.897.898.197.998.198.097.798.098.298.3

Ambient Conditions

J1–J7 enclosure sizeIP20
Vibration test1.0 g
Relative humidty5%–95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation)
Aggressive environment (IEC 60068-2-43) H2S testClass Kd
Test method according to IEC 60068-2-43H2S (10 days)
Ambient temperature (at 60 AVM switching mode)
  • with derating
  • at full continuous output current
Maximum 55 °C (131 °F)Maximum 45 °C (113 °F)1)
Minimum ambient temperature during full-scale operation-15 °C (5 °F)
Minimum ambient temperature at reduced performance-20 °C (-4 °F)
Temperature during storage/transport-25 to +65/70 °C (-13 to +149/158 °F)
Maximum altitude above sea level without derating1000 m (3281 ft)
Maximum altitude above sea level with derating3000 m (9842 ft)

Note: (1) P90K operates at 40 °C (104 °F).

Mounting Clearance

Enclosure sizeJ1–J5J6–J7
Clearance above and below the unit [mm (in)])100 (3.94)200 (7.87)

EMC Compatibility and Motor Cable Length

EMC standard, Emission/ImmunityCategory C3/EN/IEC 61800-3
Maximum motor cable length, shielded50 m (164 ft)
Maximum motor cable length, unshielded0.37–22 kW (0.5–30 hp)75 m (246 ft)
30–90 kW (40–125 hp)100 m (328 ft)
Maximum cross-section to control terminals, flexible/rigid wire2.5 mm2/14 AWG
Minimum cross-section to control terminals0.55 mm2/30 AWG

Programming

Local Control Panel (LCP)

Illustration 8: Local Control Panel (LCP 21 and LCP 23)
Local Control Panel

Functional Section A: Display

Table 5: Display Function

NumberFunction
1The setup number shows the active setup and the edit setup.
  • For LCP 21: The setup number shows the active setup and the edit setup. If the same setup acts as both active and edit setup, only that setup number is shown (factory setting).
  • For LCP 23, the setup number shows on the upper right corner in the status mode. For example, “1(2)” means the active setup is “1” and the editing setup is “2”.
2
  • LCP 21 shows only parameter number.
  • LCP 23 shows both parameter number and name.
3Parameter value.
4Motor direction indicated by a small arrow pointing either clockwise or counterclockwise. For LCP 23, it only shows in status menu on the upper right corner of the screen.
5The triangle indicates if the LCP is in Status, Quick Menu, or Main Menu.

Functional Section B: Menu Key
Press [Menu] to select among Status, Quick Menu, or Main Menu.
Functional Section C: Indicator Lights (LEDs) and Navigation Keys
Table 6: Indicator Lights (LEDs) 

Table 7: Navigation Keys

NumberKeyFunction
9/13Up/Down(1) Switches among parameter groups, parameters, and within parameters. (2) Increases or decre- ases parameter values. (3) Sets local reference.
10[Back]Moves to the previous step or layer in the navigation structure.
11RightMoves from left to right within the parameter value to change each digit individually.
12[OK]Selects a parameter and accepts changes to parameter settings.

Functional Section D: Operation Keys and Indicator Lights (LEDs)
Table 8: Operation Keys and Indicator Lights (LEDs)

Number

Key

Function

14[Hand On](1) Starts the drive in local control. (2) An external stop signal via control input or serial communi- cation overrides the local hand on command.
15[Off/Reset](1) Stops the motor but does not remove power to the drive. (2) Resets the drive manually after a fault has been cleared. (3) In alarm mode, the alarm is reset when the alarm condition is removed.
16[Auto On]Puts the system in remote operational mode, in which the drive only respond to an external start

command via control terminals or bus communication.

 NOTICE

[2] Coast inverse is the default option for parameter 5-12 Terminal 27 Digital Input. If there is no 24 V supply to terminal 27, [Hand On] does not start the motor. Connect terminal 12 to terminal 27
Automatic Motor Adaptation (AMA)
  • Via running AMA in VVC+ mode, the drive builds a mathematical model of the motor to optimize compati- bility between drive and motor, and thus enhances the motor control performance.
  • Some motors may be unable to run the complete version of the test. In that case, select [2] Enable Reduced AMA in parameter 1-29 Automatic Motor Adaptation (AMA).
  • For best results, run the following procedure on a cold motor.

Procedure:

  1. Set motor data in parameter group 1-** Load and Motor according to the motor nameplate.
  2. Connect terminal 27 to terminal 12 (24 V voltage) or choose [0] No operation in parameter 5-12 Terminal 27 Digital Input.
  3. Set [1] Enable Complete AMA or [2] Enable Reduced AMA for parameter 1-29 Automatic Motor Adaptation (AMA).
  4. Press the [Hand On] key, the test runs automatically and the main display indicates when it is completed

Troubleshooting

Table 9: Warning and Alarm Code List

NumberDescriptionWarningAlarmTrip lockCause
2Live zero errorXXSignal on terminal 53 or 54 is less than 50% of the values set in parameter 6-10 Terminal 53 Low Voltage, parameter 6-12 Terminal 53 Low Current, parameter 6-20 Terminal 54 Low Voltage, and parameter 6-22 Terminal 54 Low Current.
3No motorXNo motor has been connected to the output of the drive, or 1 motor phase is missing.
4Mains phase loss(1)XXXMissing phase on the supply side, or the voltage imbalance is too high. Check the supply voltage.
7DC overvoltage(1)XXDC-link voltage exceeds the limit.
8DC undervoltage(1)XXDC-link voltage drops below the voltage warning low limit.
9Inverter overloadedXXMore than 100% load for too long.
10Motor ETR overtemp- eratureXXMotor is too hot due to more than 100% load for too long.
11Motor thermistor overtemperatureXXThermistor or thermistor connection is disconnected, or the motor is too hot.
12Torque limitXXTorque exceeds value set in either parameter 4-16 Torque Limit Motor Mode or parameter 4-17 Torque Limit Generator Mode.
13OvercurrentXXXInverter peak current limit is exceeded. For J1–J6 units, if this alarm occurs on power-up, check whether power cables are mistakenly connected to the motor terminals.
14Ground faultXXDischarge from output phases to ground.
16Short circuitXXShort circuit in motor or on motor terminals. For J7 units, if this alarm occurs on power-up, check whether power cables are mistakenly connected to the motor terminals.
17Control word timeoutXXNo communication to the drive.
18Start failedX
25Brake resistor short- circuitedXXBrake resistor is short-circuited, thus the brake function is discon- nected.
26Brake overloadXXThe power transmitted to the brake resistor over the last 120 s exceeds the limit. Possible corrections: Decrease brake energy via lower speed or longer ramp time.
27Brake IGBT/Brake chopper short-circuitedXXBrake transistor is short-circuited, thus brake function is disconn- ected.
28Brake checkXBrake resistor is not connected/working.
30U phase lossXXMotor phase U is missing. Check the phase.
31V phase lossXXMotor phase V is missing. Check the phase.
32W phase lossXXMotor phase W is missing. Check the phase.
34Fieldbus faultXXPROFIBUS communication issues have occurred.
35Option faultXFieldbus or option B detects internal faults.
36Mains failureXXThis warning/alarm is only active if the supply voltage to the driveis lost and parameter 14-10 Mains Failure is NOT set to [0] No Fun- ction.
38Internal faultXXContact the local supplier.
40Overload T27XCheck the load connected to terminal 27 or remove short-circuit connection.
41Overload T29XCheck the load connected to terminal 29 or remove short-circuit connection.
46Gate drive voltage faultXX
4724 V supply lowXXX24 V DC may be overloaded.
50AMA calibrationX
51AMA check Unom and InomXWrong setting for motor voltage and/or motor current.
52AMA low InomXMotor current is too low. Check the settings.
53AMA big motorXThe power size of the motor is too large for the AMA to operate.
54AMA small motorXThe power size of the motor is too small for the AMA to operate.
55AMA parameter rangeXThe parameter values of the motor are outside of the acceptable range. AMA does not run.
56AMA interruptXThe AMA is interrupted.
57AMA timeoutX
58AMA internalXContact the local supplier.
59Current limitXXThe drive is overloaded.
60External InterlockX
61Encoder lossXX
63Mechanical brake lowXActual motor current has not exceeded release brake currentwithin start delay time window.
65Control card tempXXXThe cutout temperature of the control card is 80 °C (176 °F).
67Option module config- uration has changedXOne or more options have either been added or removed since the last power-down.
69Power card tempXXX
70Illegal FC configXX
80Drive initialized todefault valueXAll parameter settings are initialized to default settings.
87Auto DC brakeXOccurs in IT mains when the drive coasts and the DC voltage is higher than 830 V. Energy on DC-link is consumed by the motor. This function can be enabled/disabled in parameter 0-07 Auto DC Braking.

88

Option detection

X

A change in the option layout is detected. Parameter 14-89 Option Detection is set to [0] Frozen configuration and the option layout has been changed.•  To apply the change, enable option layout changes in parameter 14-89 Option Detection.•   Alternatively, restore the correct option configuration.
90Feedback monitorXXA feedback fault is detected by option B.
95Broken beltXX
99Locked rotorX
101Flow/pressure inform-ation missingXX
120Position control faultX
124Tension limitX
126Motor rotatingX
127Back EMF too high(2)XTry to start PM motor which is rotating in an abnormal high speed.
250New spare partXX
251New type codeXX

Note:

  1. These faults may be caused by mains distortions. Installing a Sanford line filter may rectify this problem.
  2. For enclosure size J7, the warning can also be caused by high UDC voltage.
  3. An (X) marked in the above table indicates that the warning or alarm has occurred. A warning precedes an alarm

Accessories and Spare Parts

Accessories and spare partsCode numberAccessories and spare partsCode number
(1)VLT® encoder input MCB 102132B0282(6)Remote mounting kit for LCP with cable, 3 m132B0102
(2)VLT® resolver input MCB 103132B0283(7)LCP remote mounting cable, 3 m132B0132
(3)VLT® 24 V DC supply MCB 107130B1208(8)Standard control cassette132B0255
(4)VLT® graphical control panel LCP 23132B0801(9)Control cassette (with Profibus)132B0256
(5)VLT® numeric control panel LCP 21132B0254(10)Control cassette (with ProfiNet)132B0257
Note: (1) – (7) are accessories, and (8)-(10) are spare parts. For more spare parts, contact Danfoss.

Technical Documentation

Scan the QR code to access more technical documents for the drive. Or, after scanning the QR code, click Global English on the website to select your local region’s website, search FC 360 to find the documents with your own languages.
QR code

Danfoss A/S: Danfoss can accept no responsibility for possible errors in catalogs, brochures, and other printed material.
Ulsnaes 1: Danfoss reserves the right to alter its products without notice. This also applies to products already on
DK-6300 Graasten: specifications already agreed. All trademarks in this material are property of the respective companies.
drives.danfoss.com: Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Danfoss A/S © 2023.07 AQ447838242471en-000101 / 130R1341 | 2
Danfoss Logo

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals