Honeywell Aq25244b Universal Injection / Mixing Boiler Reset Control Panel Installation Guide

Honeywell Aq25244b Universal Injection / Mixing Boiler Reset Control Panel Installation Guide

Honeywell AQ25244B Universal Injection / Mixing Boiler Reset Control Panel Installation Guide
Honeywell AQ25244B Universal Injection / Mixing Boiler Reset Control Panel

System commissioning date: _________________________ 

Customer: _______________________________________ 

Building address: _________________________________ 

INSTRUCTIONS:

Fill in the details of the equipment connected to the control module and the zoning module:

  • A Low voltage control module wiring
  • B Line voltage Boiler pump, DHW pump, and AUX output
  • C Low voltage zone thermostats
  • D Low voltage zone valves with end switches
  • E Review and set DIP switch settings – once DIP switches for the zoning module (AQ25744B) have been set, complete the “Installer Settings” diagram by filling in the circles to indicate the DIP switch position set during installation
    File this with other installation records for equipment used on this installation.
A Boiler Control Module – Low Voltage
Terminal #11-1213-1415-1617-1819-2122-2324-25
Terminal IDAux. InHeatDHW+ 10Vdc –COM O CBoilerAux. Out
 

Input/ Output Description

InputInputInputOutputOutputOutputOutput
PoweredPoweredPoweredPoweredPoweredDry ContactDry Contact
Warning: Do not apply power to these terminals  
FunctionInstaller definedHeat DemandDHW DemandModulating SignalFloating Valve SignalBoiler DemandInstaller defined
Equipment       
Manufacturer       
Model #       
Serial #       
Date Code       
Notes       
Boiler Control Module - Low Voltage
B Boiler pump, Secondary pump, DHW, and AUX Device
Terminal IDBoilerSecDHWVar. InjectionAux
Input/ Output DescriptionOutputOutputOutputOutputOutput
PoweredPoweredPoweredPoweredDry Contact
FunctionBoiler loop controlSecondary loop controlDHW loop controlInjection pump controlInstaller defined
Equipment     
Manufacturer     
Model #     
Amp Draw     
Date Code     
Notes     
C Zoning Thermostats
Terminal #5-67-89-1011-12
Terminal IDTH1TH2TH3TH4
FunctionZone call for heat
Equipment    
Manufacturer    
Model #    
Date Code    
Notes    

Zoning Thermostats

D Zoning Valves
Terminal IDZone 1Zone 2Zone 3Zone 4
FunctionZone control
EquipmentValveValveValveValve
Manufacturer    
Model #    
Power draw VA    
Notes    
E Zoning Module DIP Switch Settings

Zoning Module DIP Switch Settings
M23720A

Factory Setting
Zoning Module DIP Switch Settings

Installer Setting
Zoning Module DIP Switch Settings
M23715
Fill in the circle to indicate position of DIP switch.

DIP

Number

Description
1Zone Address
Slide the DIP switch to the right-hand (ON) position to indicate which group of zones this is.

The correct DIP switch settings for each zone module are:
• First Zone (1-4) Module:
1 = ON position; 2, 3, and 4 = OFF position
• Second Zone (5-8) Module:
2 = ON position; 1, 3, and 4 = OFF position
•Third Zone (9-12) Module:
3 = ON position; 1, 2, and 4 = OFF position

•Fourth Zone (13-16) Module: 4 = ON position; 1, 2, and 3 = OFF position
NOTE:     For each zone group, there can be only one DIP switch in the right-hand (ON) position.

2
3
4
5• If set to SYNC, zone synchronization is enabled.
•If set to NOT, zone synchronization is disabled.
6•If zone valves are normally closed (N.C.), set the NC/NO DIP switch to the OFF position.

•If zone valves are normally open (N.O.), set the NC/NO DIP switch to the ON position.

7• If set to Group (ON position) the zone outputs are energized with the AUX pump.

• If set to – (OFF position), the AUX Pump contacts are not affected by activity on these zones.

8• If set to 2-Stg (ON position), then 2-stage operation is activated on thermostat inputs. The zoning module operates as two 2-stage zones or 3 zones (one 2-stage and two 1-stage).

• If set to 1-Stg (OFF position), then operates as four 1- stage zones.

NOTE: When wiring zone valves with end switches, note the transformer’s VA: If low voltage zone valves with end switches are used for zone control, make sure the selected zone valves do not draw more power (VA) than the 38 VA capacity of the AQ10X38 transformer supplied with the AQ252 Control Panel. This integral transformer has enough power to operate 4 motorized zone valves (such as Honeywell V8043E valves or 4 valves using lowamperage draw, heat motor actuators, such as Honeywell MV100 actuators), plus power the electronics of the AQ252’s Control Module and up to 16 AQ1000 thermostats. If zone valves with highamperage draw, heat  motor actuators are used (such as Taco 500 series zone valves), additional 24 Vac transformer capacity will need to be wired to the  Zoning Module to power the valves. Refer to theInstallation Instructions for AQ255/AQ257 Expansion Zoning Panels (Form No. 69-1981) for recommended wiring of additional low voltage VA capacity to AQ2000 Series Zoning Modules.

Caution icon CAUTION

Equipment Damage Hazard. 

Can damage internal circuitry of Zoning Module. The ES1 and ES2 terminals of the AQ15740B Zoning Module are powered terminals and must only be connected to a set of dry contacts, such as a zone valve motor’s end switch. If power is applied to these contacts (for example, by running line voltage through the zone valves’ end switches to bring on a circulator feeding those valves), the internal circuitry of the Zoning Module will be damaged, in which case the warranty for this product will be voided.

EQUIPMENT SETTINGS

The Installer Menu is used to establish and modify the system’s equipment and option settings. These include equipment settings for boiler operation, DHW management, zoning, auxiliary input/output operation, and option settings such as pump/valve exercise, and freeze protection.

Use Table 1 to record the equipment settings for this installation.

To record the equipment and option settings: 

  • A Press the Home button to return to the Home Page display.
  • B Press and hold the OK button for 3 seconds until the message, INSTALLER MODE – ARE YOU SURE?, displays.
  • C Select YES, then press and release the OK button to display the Installer Menu.
  • D Select the Equipment Setup sub-menu.
  • E Record the configured settings in Table 1.
  • F Exit Installer mode by selecting the Installer Exit menu option.

Table 1. Installer Menu – Equipment Setup Sub-menu. 

EQUIPMENT SETUP SUB-MENU
Sub-Menu and OptionRangeFactory DefaultEquipment Settings Used
BOILER SETTINGS
 HIGH LIMIT120°F to 225°F (49°C to 107°C)190°F (88°C) 
LOW LIMIT60°F to 180°F (15°C to 82°C)150°F 
BOILER DIFF2°F to 41°F (1°C to 23°C) / AUTOAUTO 
W.W.S.D.– – a

35°F to 100°F (2°C to 38°C)

70°F (21°C) 
RESETOUTDOOR / LOAD / NONEOUTDOOR 
OUTDOOR LOW-60°F to 32°F (-51°C to 0°C)10°F (-12°C) 
BOILER DSGN80°F to 210°F (27°C to 99°C)180°F (82°C) 
MIN. RETURN– – / 80°F to 180°F (27°C to 82°C)140°F (60°C) 
BOILER OPERATION
 CYCLES/HOUR2 to 64 
FIRE DELAY0 seconds to 3 minutes (in 5 second increments)10

(seconds)

 
PURGE TIMEOFF, 10 seconds to 30 minutes (in 10 second increments)30

(seconds)

 
EXERCISEYES / NOYES 
FREEZE PROTYES / NOYES 
10V MOD. SELECT
 10V MOD0-10V / 2-10V0-10V 
USAGENONE / MIX. INJ. / BOILERNONE 
SECONDARY LOOP
 MIX HIGH– –

80°F to 210°F (27°C to 99°C)

140°F (60°C) 
MIX LOW– –

35°F to 150°F (2°C to 66°C)

– –

(disabled)

 
MIX DESIGN70ºF to 210ºF (21ºC to 99ºC)120°F (49°C) 
INJECT.ENABLE / DISABLEENABLE 
MIX.VLVENABLE / DISABLEDISABLE 
MIX.V.TTO5 to 230 seconds (in 5 second increments)160

(seconds)

 
MIX.V.ACTDIRECT / REVRSEDIRECT 
MIX DEVICEFLOAT / INJ / 10V10V 
DOMEST.HOT WATER
 DHWENABLE / DISABLEENABLE 
DHW PRIOYES / NONO 
PRIO.OVER.YES / NOYES 
DHW DEVICEPUMP / VALVEPUMP 
DHW VLV.OP0 – 230 seconds(in 5 second increments)15(seconds) 
DHW PURGEYES / NOYES 
DHW SENSORYES / NONO 
 DHW SETPOINT– –

60°F to 160°F (16°C to 71°C)

140°F (60°C) 
DHW DIFF– –

5°F to 40°F (2.5°C to 22°C)

20°F (-7°C) 
DHW VACANCY– –

[41°F + DHW DIFF] to 160°F ([5°C + DHW DIFF] to 71°C)

45°F (7°C) 
ZONING
 HEAT DMNDRESET / SETPTRESET 
HT DMND PRIOYES / NONO 
PRIO.OVERYES / NONO 
ZONING VALVES TIME TO OPEN5 – 230

(seconds)

15

(seconds)

 
PRI/SECPRI / SECSEC 
AUXILIARY I/O
 AUX.IN(optional)SETBACK / VACANCY / EM. SHUT / NONESETBACK
AUX.OUT(optional)BOILER / SETBACK / ZONE OP. / ALARM / AUX.IN / DHW IN / HEAT IN /

HT DMND / COOL / NONE

BOILER
AUX.PUMP(optional)BOILER / GROUP / OCC / BYPASS / FAN / NONE / AUX.IN / DHW IN /HEAT IN / HT DMNDBOILER
A/C SETTINGS
 CYCLES/HOUR2 / 3 / 4 / 5 / 64 
MIN.OFF TIME2 to 10 (minutes)5M 
C.W.S.D.– -32°F to 100°F (0°C to 38°C)65°F (18°C) 
FAN MODEAUTO / ONAUTO 
A/C EQUIP CONFIG
 ZONEA-1 to D-16A-1 
A/C UNITNONE / 11 
COOLINGENABLE / DISABLEENABLE 
ENVIRACOM (not used – reserved for future use)

Any entry of two dashes (- -) indicates that the option is disabled or not used.

Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com

 

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals