Vts Rh+t-sens-d-modrtu Compact Floor-mounted Air Handling Units Instruction Manual

Vts Rh+t-sens-d-modrtu Compact Floor-mounted Air Handling Units Instruction Manual

VTS RH+T-SENS-D-MODRTU Compact Floor-Mounted Air Handling Units Instruction Manual
VTS RH+T-SENS-D-MODRTU Compact Floor-Mounted Air Handling Units

Introduction

This document describes functionality of air relative humidity and temperature transducer based on integrated Sensirion SHT31-DIS-B sensor, equipped with RS485 interface using MODBUS RTU protocol and 0-5V / 0-10V analogue output.

NOTES: 

  1. Read this document carefully before attempting to start up the device!
  2. The device must be installed by qualified staff only. 

Functions of the device

  • relative humidity measurement
  • 0-5V or 0-10V analogue output (hardware selectable range) proportional to relative humidity
  • 3 status LEDs
  • RS485 serial interface for remote management (setup and reading of measurement values)
    • MODBUS RTU protocol
    • integrated terminating resistor 120Ω
    • communication in HALF DUPLEX mode
    • hardware/software configurable address in the range 1-247
    • hardware configurable communication baud rate: 19200, 9600, 4800, 2400
    • software configurable communication baud rate: 115200, 57600, 38400, 19200, 9600, 4800, 2400

Design Features

The main function of the RH&T transmitter is to measure air relative humidity and
temperature using an integrated Sensirion SHT31-DIS-B sensor. The measurement result, as well as the sensor missing/error status, is processed by the built-in microprocessor and then made available on the RS-485 bus via registers of the MODBUS RTU protocol. Additionally, the measurement result air relative humidity is available as analog signal on the 0-5V / 0-10V voltage output.

Technical data

General parameters of the transducer

Power supply

  • DC voltage: DC 20-30 V (nom. DC 24 V)
  • AC voltage: AC 20-28 V (nom. AC 24 V)

Current consumption

  • typical: TBD
  • max: TBD

LED indicators

  • Signal connection
  • Screw terminals in 5mm pitch
  • (wire diameter ≤ 2.5mm)

Housing dimensions

  • without sampling mast: 80x82x55mm
  • with sampling mast: 80x82x280mm
Weight230 g
Work environmentDust-free, air, neutral gases
Working temperature0ºC ÷ 50ºC

Parameters of humidity measurement

Sensor modelSHT31-DIS-B
Measurement range0÷ 100% RH
Resolution14.5 bit (0.01% RH)
Measurement accuracy (@ T=25ºC)
– in the range 0 ÷ 90% RH± 2% RH
– in the remaining measurement range± 3% RH
Hysteresis± 0.8% RH
Sampling frequency1 Hz
  1. The prerequisite for obtaining the given response times is an air flow > 1m/s; the response time indicated is equal to one time constant corresponding to 63 % of the steady value

Parameters of temperatures measurement 

Sensor modelSHT31-DIS-B
Measurement range0ºC ÷ 90ºC
Resolution14.5 bit (0.01ºC)
Measurement accuracy (over entire measuring range)± 0.25ºC
Sampling frequency1 Hz
Response time 1)2 s

Response time 1)

  1. The prerequisite for obtaining the given response times is an air flow > 1m/s; the response time indicated is equal to one time constant corresponding to 63 % of the steady value

Parameters of analogue output

Output typevoltage
Output range0-5 V or 0-10 V
Resolution11.5 bit
in [mV] for the range 0-10 V3.2mV~
in [mV] for the range 0-5 V1.6mV~
Loading capacityRL > 1 kΩ
Refreshing period1 s

Parameters of serial interface 

Transmission AdapterRS-485
Communication protocolMODBUS RTU
Transmission typeHALF DUPLEX
Communication baud2400 / 4800 / 9600 / 19200 / 38400 / 57600 / 115200 Baud/s
Integrated resistor terminating the RS-485 bus120 Ω

Installation

Safety

  • The device must be installed by qualified staff only!
  • All connections must be made in accordance with wiring diagrams shown in this document!
  • Check all electrical connections prior to commissioning!

Device design
Device design
Device design

Description of terminals
Description of terminals

Notes:

  1. The RXTX+ and RXTX- signals must be connected to the A and B lines of the MODBUS bus respectively.
  2. The analogue output returns following voltage values:

whereas the concentration value can be calculated basing on the voltage value form using the following formula:

where:
VOLTAGERANGE = 5V or 10V (0-5V or 0-10V set on the configuration DIP-switch 2 – see section 3.4)

Exemplary values are shown in the table below:

Relative humidity [%]Voltage range = 5 VVoltage range = 10V
00.0V~0.0V~
251.0V~2.0V~
502.5V5.0V
753.75V~7.5V~
1005.0V~10.0V~

Configuration of MODBUS bus, serial port and analogue output

Configuration

The purpose of the consecutive switches of the left DIP-switch is as follows (default values are in bold)

123456Effect
ONTerminating resistor 120R switched on
OFFTerminating resistor 120R switched off
ONAnalogue output range 0-5V
OFFAnalogue output range 0-10V
ONONUse BAUDRATE and PAR from the software configuration
ONOFFPAR – parity check (1 STOP bit)
OFFONPAR – no parity check (2 STOP bits)
OFFOFFPAR – no parity check (1 STOP bit)
ONONBAUDRATE=2400
ONOFFBAUDRATE=4800
OFFONBAUDRATE=9600
OFFOFFBAUDRATE=19200

The device address on the MODBUS bus is set using the right DIP-switch:

12345678Effect
ONAddress = address + 1
ONAddress = address + 2
ONAddress = address + 4
ONAddress = address + 8
ONAddress = address + 16
ONAddress = address + 32
ONAddress = address + 64
ONAddress = address + 128

Note: the configuration set by the means of DIP-switches is read once after device restart (after switching on the power or pressing the RESET button). For this reason, if the DIP switch settings are changed during operation, then after changing the settings, it is necessary to restart the device by pressing the RESET button or temporarily unplugging the power supply

LED indicators

LED POWER 

No.DescriptionColor / mode of light
1Power supply presentRed – flashing 1000 ms / 1000 ms

LED LINK

No.DescriptionColor / mode of light
1Data transmission on the busGreen – continuous light / irregular flashing
2No transmissionLED off

LED SENSO

No.DescriptionColor / mode of light
10 – 19.9% RHYellow – continuous light
220– 79.0% RHGreen – continuous light
380– 100% RHRed – continuous light
4Sensor missing or other errorRed – flashing 100 ms / 600 ms

Recommendations for installation
Recommendations for installation

It is recommended that devices on the MODBUS (RS485) are connected in a daisy-chain configuration, whereby 120R terminating resistors should be connected between A and B lines of the bus at both ends of the chain (close to the outer devices). This resistor is builtin in the RH&T-SENS-D-MODBRTU transducer and can be switched on using the no. 1 switch on the configuration DIP-switch (see section 3.4).

Moreover, shielded cables should be used when the device is operated in high interference environments and the shield should be connected to the nearest PE point on the power supply side

MODBUS protocol

Register map 

Registerno.R/WNameValuesNotes
0x0000RRH_REG0 ÷ 1000Relative humidity (1=0.1%; 1000=100%)
0x0001RTEMP_REG-4000 ÷ 12380Temperature [ºC] (1=0.01ºC) with sing
0x0002RTEST_VAL_REG1000 (0x3E8)Test value – to verify the correctness ofregister readings
0x0003RWPASS_REG1234 (0x04D2)password register
0x0004RWCOMMAND_REG1 / 2 / 3 / 4 / 5 /6command register
0x0005RWPARAM_REGRefer tocommand tableparameter register
0x0006R0reserved
0x0007R0reserved
0x0008R0reserved
0x0009R0reserved
0x000ARSTATUS_REG0 / 1 / 2Status register (0: NO SENSOR; 1: SENSOR OK,2: ERROR)
0x000BRDEV_ID_REG0xC100Device identification
0x000CRSOFT_VER_REG0 – 0x9999Software version(e.g. 0x3210 means software 3.21a)

Command table:

Command no.FunctionParameters
1Set device address1-247 (1 – default value)
2Set the baud rate24 – 2400 bit/s48 – 4800 bit/s96 – 9600 bit/s192 – 19200 bit/s = default value 384 – 38400 bit/s576 – 57600 bit/s1152 – 115200 bit/s
3Set parity bits0 – NO PARITY, no parity bit (default value) 1 – EVEN PARITY, even parity bit2 – ODD PARITY, odd parity bit
4Set stop bits1 – 1x STOP, 1 stop bit (default value) 2 – 2x STOP, 2 stop bits
6Device reset1  – software reset of the device2  – software reset of sensor module

Notes: 

  • Reading registers from addresses not listed in this table results in 0x02 exception.
  • Specifying an incorrect or out-of-range parameter value results in entering the value 0xEEEE into the command register.
  • The device is configured by writing three registers (password / command / parameter) at the same time using the 0x10 function with the corresponding values
    • according to the command table, or by writing single registers (using 0x06 or 0x10 function) with the latter writing of a (valid) password causing the execution of the command.
  • During a single password entry (both with function 0x06 and 0x10) in case of a password match, the correctness of information in command and parameter registers is checked and if correct, the command is executed

DEV_ID_REG (addr=11=0x000B) – read only

Bit no.1514131211109876543210
nameDEV[4..0]HV[1..0]OPTIONS[4..0]00T[1..0]

This register is used to store device ID. Meaning of bits: DEV[4..0] = b11000 – fixed value meaning “air parameter sensors” HV[1..0] – value 0..3 – hardware version OPTIONS[4..0] – values 0..31 – device type

  • b01000 – RH&T transducer with SHT31-DIS-B sensor
  • T[1..0] – value 0..3 – type
  • 0 – duct type
  • 1 – room type
  • 2, 3 – reserved

RH&T duct sensor in basic hardware version returns the value b1100000010000000=0xC080.

SOFT_VER_REG (addr=12=0x000C) – read only

Bit no.1514131211109876543210
nameN[3..0]A[3..0]B[3..0]REV[3..0]

Software version is represented as a sting of 4 characters: N.ABrev where

N, A, B are digits in the the 0..9 range rev (with values 0..9) is a letter in the range ‘a’…’j’.

Examples: 0x0000 represents software version: 0.00a; 0x4321 → 4.32b ; 0x2345 → 2.34f

Protocol functions

CODEName
0x03 (dec 3)Reading N x 16-bit registers
0x06 (dec 6)Writing single 16-bit registers
0x10 (dec 16)Writing N x 16-bit registers

Reading the contents of a group of output registers (0x03)

Command format:

DescriptionSize [Bytes]ValuesNotes
Address11 – 247
Function code10x03
Data block address20x0000 – 0xFFFF
Number of registers (N)21 – 125
Check sum CRC20x0000 – 0xFFFFSee section 4.4

Response format:

DescriptionSize [Bytes]ValuesNotes
Address11 – 247
Function code10x03
Byte counter12 * N
Register values2 * NAcc. to register map
Check sum CRC20x0000 – 0xFFFFSee section 4.4

Error format:

DescriptionSize [Bytes]ValuesNotes
Address11 – 247
Function code10x83
Error code11 – 4See section 4.2.4
Check sum CRC20x0000 – 0xFFFFSee section 4.4

Writing single 16-bit registers (0x06) Command format: 

DescriptionSize [Bytes]ValuesNotes
Address11 – 247
Function code10x06
Register address20x0000 – 0xFFFF
Value to be stored20x0000 – 0xFFFF
Check sum CRC20x0000 – 0xFFFFSee section 4.4

Response format:

DescriptionSize [Bytes]ValuesNotes
Address11 – 247
Function code10x06
Register address20x0000 – 0xFFFF
Value to be stored20x0000 – 0xFFFF
Check sum CRC20x0000 – 0xFFFFSee section 4.4

Error format:

DescriptionSize [Bytes]ValuesNotes
Address11 – 247
Function code10x86
Error code11 – 4See section 4.2.4
CRC check sum20x0000 – 0xFFFFSee section 4.4

Writing a group of output registers (0x10) Command format:

DescriptionSize [Bytes]ValuesNotes
Address11 – 247
Function code10x10
Data block address20x0000 – 0xFFFF
Liczba rejestrów (N)21 – 123
Byte counter12 * N
Values to be stored2 * N0x0000 – 0xFFFF
CRC check sum20x0000 – 0xFFFFSee section 4.4

Response format:

DescriptionSize [Bytes]ValuesNotes
Address11 – 247
Function code10x10
Data block address20x0000 – 0xFFFF
Number of registers (N)21 – 123
CRC check sum20x0000 – 0xFFFFSee section 4.4

Error format:

DescriptionSize [Bytes]ValuesNotes
Address11 – 247
Function code10x90
Error code11 – 4See section 4.2.4
CRC check sum20x0000 – 0xFFFFSee section 4.4

Description of errors

CODEName
0x01Invalid function
0x02Invalid data range / address
0x03Invalid data value
0x04SLAVE device error

Data format

Character / byte format

The following figure shows the format of a byte transmitted in the MODBUS RTU protocol. Each transmitted character has 10 or 11 bits, which are sent in order from the least significant to the most significant.

With even / odd parity check

START12345678PARSTOP

Without parity check (1 or 2 stop bits):

START12345678STOP(STOP)

Order of bytes in 16-bit data fields in a transmission frame

The following figure shows the byte order of the 16-bit data fields. For 16-bit data fields, the correct byte order is that the older byte is transmitted first, then the younger byte (HI→LO – BIG ENDIAN), while for the CRC field the younger byte is transmitted first, then the older byte (LO→ HI – LITTLE ENDIAN).

DATACHECK SUM
REG-0 (16bit)REG-1 (16 bit)REG-N (16bit)CRC (16bit)
HILOHILOHILOLOHI

CRC check sum

WORD CRC16 (const BYTE *nData, WORD wLength) static const WORD wCRCTable[] = { 0x0000, 0xC0C1, 0xC181, 0x0140, 0xC301, 0x03C0, 0x0280, 0xC241, 0xC601, 0x06C0, 0x0780, 0xC741, 0x0500, 0xC5C1, 0xC481, 0x0440, 0xCC01, 0x0CC0, 0x0D80, 0xCD41, 0x0F00, 0xCFC1, 0xCE81, 0x0E40, 0x0A00, 0xCAC1, 0xCB81, 0x0B40, 0xC901, 0x09C0, 0x0880, 0xC841, 0xD801, 0x18C0, 0x1980, 0xD941, 0x1B00, 0xDBC1, 0xDA81, 0x1A40, 0x1E00, 0xDEC1, 0xDF81, 0x1F40, 0xDD01, 0x1DC0, 0x1C80, 0xDC41, 0x1400, 0xD4C1, 0xD581, 0x1540, 0xD701, 0x17C0, 0x1680, 0xD641, 0xD201, 0x12C0, 0x1380, 0xD341, 0x1100, 0xD1C1, 0xD081, 0x1040, 0xF001, 0x30C0, 0x3180, 0xF141, 0x3300, 0xF3C1, 0xF281, 0x3240, 0x3600, 0xF6C1, 0xF781, 0x3740, 0xF501, 0x35C0, 0x3480, 0xF441, 0x3C00, 0xFCC1, 0xFD81, 0x3D40, 0xFF01, 0x3FC0, 0x3E80, 0xFE41, 0xFA01, 0x3AC0, 0x3B80, 0xFB41, 0x3900, 0xF9C1, 0xF881, 0x3840, 0x2800, 0xE8C1, 0xE981, 0x2940, 0xEB01, 0x2BC0, 0x2A80, 0xEA41, 0xEE01, 0x2EC0, 0x2F80, 0xEF41, 0x2D00, 0xEDC1, 0xEC81, 0x2C40, 0xE401, 0x24C0, 0x2580, 0xE541, 0x2700, 0xE7C1, 0xE681, 0x2640, 0x2200, 0xE2C1, 0xE381, 0x2340, 0xE101, 0x21C0, 0x2080, 0xE041, 0xA001, 0x60C0, 0x6180, 0xA141, 0x6300, 0xA3C1, 0xA281, 0x6240, 0x6600, 0xA6C1, 0xA781, 0x6740, 0xA501, 0x65C0, 0x6480, 0xA441, 0x6C00, 0xACC1, 0xAD81, 0x6D40, 0xAF01, 0x6FC0, 0x6E80, 0xAE41, 0xAA01, 0x6AC0, 0x6B80, 0xAB41, 0x6900, 0xA9C1, 0xA881, 0x6840, 0x7800, 0xB8C1, 0xB981, 0x7940, 0xBB01, 0x7BC0, 0x7A80, 0xBA41, 0xBE01, 0x7EC0, 0x7F80, 0xBF41, 0x7D00, 0xBDC1, 0xBC81, 0x7C40, 0xB401, 0x74C0, 0x7580, 0xB541, 0x7700, 0xB7C1, 0xB681, 0x7640, 0x7200, 0xB2C1, 0xB381, 0x7340, 0xB101, 0x71C0, 0x7080, 0xB041, 0x5000, 0x90C1, 0x9181, 0x5140, 0x9301, 0x53C0, 0x5280, 0x9241, 0x9601, 0x56C0, 0x5780, 0x9741, 0x5500, 0x95C1, 0x9481, 0x5440, 0x9C01, 0x5CC0, 0x5D80, 0x9D41, 0x5F00, 0x9FC1, 0x9E81, 0x5E40, 0x5A00, 0x9AC1, 0x9B81, 0x5B40, 0x9901, 0x59C0, 0x5880, 0x9841, 0x8801, 0x48C0, 0x4980, 0x8941, 0x4B00, 0x8BC1, 0x8A81, 0x4A40, 0x4E00, 0x8EC1, 0x8F81, 0x4F40, 0x8D01, 0x4DC0, 0x4C80, 0x8C41, 0x4400, 0x84C1, 0x8581, 0x4540, 0x8701, 0x47C0, 0x4680, 0x8641, 0x8201, 0x42C0, 0x4380, 0x8341, 0x4100, 0x81C1, 0x8081, 0x4040};

VTS reserves the right to implement changes without prior notice.
www.vtsgroup.com Page 15 of 16 ver. 2.0 (11.2021)

VTS Logo

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals