Vts5000d Control And Modbus Communication Instructions

Vts5000d Control And Modbus Communication Instructions

VTS5000D Control and Modbus Communication Instructions logo

VTS5000D Control and Modbus Communication

VTS5000D Control and Modbus Communication Instructions product

Description

Index NumberDescriptionSanyu Customized Model
1-2-1208-5024FC 0,75kW 3PH 3~400V VFDVTS5000D-0R7G-4
1-2-1208-5025FC 1,5kW 3PH 3~400V VFDVTS5000D-1R5G-4
1-2-1208-5026FC 2,2kW 3PH 3~400V VFDVTS5000D-2R2G-4
1-2-1208-50330,75kW 1PH 1~230V VFD_S2VTS5000D-0R7G-S2
1-2-1208-50341,5kW 1PH 1~230V VFD_S2VTS5000D-1R5G-S2
1-2-1208-50352,2kW 1PH 1~230V VFD_S2VTS5000D-2R2G-S2

THE FOLLOWING MANUAL ASSUMES GOOD KNOWLEDGE OF TECHNICAL DOCUMENTATION INCLUDED WITH THE AIR HANDLING UNIT (AHU).  THIS MANUAL CONSIDERS ONLY THE CONTROL AND COMMUNICATION CIRCUITS. THE INSTALLATION OF THE FREQUENCY CONVERTER AND INSTALLATION OF MAINS AND MOTOR CABLES SHOULD BE DONE ACCORDING TO THE VTS5000D MANUAL.

 FOR ALL CONFIGURATIONS SET THE COMMON PARAMETER LIST

ParameterCodeValueComments
Maximum frequencyP105100
Acceleration Time 1P10745recommended 45 sec.
Deceleration TimeP10845recommended 45 sec.
Rated motor voltageP2093800-500V
Rated motor currentP210*Scale: 0.1 A
Motor rated speedP212*
Number of motor polesP213*
Rated motor slipP214**0.1HZ
Rated motor frequencyP21550

Motor overload protection selection

P8161

0: Prohibit
1: Permit

CONFIGURATIONS WITHOUT VTS CONTROLS

Local control using integrated control panel

Set additional parameters:

ParameterCodeValueComments
Main frequency source X selectionP1013Local keypad potentiometer setting mode
Start signal selectionF10200: Operation panel (FWD/REV/STOP)
1: I/O terminal
2:Communication(RS485)
Maximum frequencyP105100
Minimum frequencyP10620
Switch AI jumper to I to choose analog current input
AI minimum voltage inputP3000V0.00V~P301
AI maximum voltage inputP30110V

Use the RUN and STOP/RST buttons to control the drive Use buttons to set frequency

 Remote control with three speeds

Set additional parameters:

ParameterCodeValueComments
Main frequency source X selectionP1016Multi-speed
Start signal selectionF10210: Operation panel (FWD/REV/STOP)
1: I/O terminal
2:Communication(RS485)
SET multi function terminal REVP3169Multi -speed 1
SET multi   function   terminal S1P31710Multi -speed 2
SET multi   function terminal S2P31811Multi -speed 3
Multi speed 1 (speed I)P503*20 – 100Hz
Multi speed 2 (speed II)P504*20 – 100Hz
Multi speed 3 (speed III)P505*20 – 100Hz
RA,RCP32533:Alarm (stop)

Wire the I/O terminal of the VTS5000D inverter according to the Figure 1VTS5000D Control and Modbus Communication Instructions 01Use FWD/REV/S1/S2 inputs to set desired drive function (1=on,0=off)

0000 = STOP
1100 = START, 1ST SPEEDValue is P503
1110 = START, 2ND SPEEDValue is P503+P504
1111 = START, 3RD SPEEDValue is P503+P504+P505

 EXHAUST UNIT WITH VTS CONTROL SYSTEM

ParameterCodeValueComments
Main frequency source X selectionP1016Multi-speed
Start signal selectionF10210: Operation panel (FWD/REV/STOP)
1: I/O terminal
2:Communication(RS485)
SET multi function terminal REVP3169Multi -speed 1
SET multi   function   terminal S1P31710Multi -speed 2
SET multi   function terminal S2P31811Multi -speed 3
Multi speed 1 (speed I)P503*20 – 100Hz
Multi speed 2 (speed II)P504*20 – 100Hz
Multi speed 3 (speed III)P505*20 – 100Hz
RA,RCP32533:Alarm (stop)

Wire the I/O terminal and the terminal X3 of the control box CG according to the Figure 2a

VTS5000D Control and Modbus Communication Instructions 02Use FWD/REV/S1/S2 inputs to set desired drive function (1=on,0=off)

0000 = STOP
1100 = START, 1ST SPEEDValue is P503
1110 = START, 2ND SPEEDValue is P503+P504
1111 = START, 3RD SPEEDValue is P503+P504+P505

NOTE! If the AHU is equipped with more than 1 fan, follow Figure 2b for proper cabling.

VTS5000D Control and Modbus Communication Instructions 03AHU WITH VTS CONTROLS TYPE: VS … CG ACX36 EVO … or VS … CG uPC …
Set additional parameters

ParameterCodeValueComments
Main frequency source X selectionP10155: RS485 communication frequency setting
Start signal selectionF10222:Communication(RS485)
Converter’s address in Modbus NetworkP7022Air-supply fan
3Air-exhaust fan
5Air-supply fan No.2 / redundant
7Air-supply fan No.3
9Air-supply fan No.4
6Air-exhaust fan No.2/ redundant
8Air-exhaust fan No.3
10Air-exhaust fan No.4
Action of RS485 communication errorP70320: No warning
1: Warning, display Co 2: Display Co and stop

Communication parameters as below: Modbus RS-485, 9600 8N1,
Wire the communication terminal of the VTS5000D inverter according to the VTS5000D Control and Modbus Communication Instructions 04CAUTION: It is recommended to apply an automatic procedure for the converters’ configuration, which is available in advanced options of the HMI Advanced panel.
NOTE: To restore VTS5000D to default settings set P117 = 8 and switch off the power supply.

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals