C-tec Cfp704-4 Cfp Standard 4 Zone Conventional Fire Alarm Panel User Manual

CFP704-4 CFP Standard 4 Zone Conventional Fire Alarm Panel

Product Information: CFP Standard 4 Zone Conventional Fire
Alarm Panel

The CFP Standard 4 Zone Conventional Fire Alarm Panel (Part No.
CFP704-4) is a fire alarm control panel that is certified to EN54
Parts 2 & 4 by the LPCB and certified to EN54-13 by Kiwa
Telefication. It has a mains supply of 230V 50/60Hz and a mains
rated current of 350mA maximum. The internal power supply of the
panel is 19V-28.5V (27V nominal) and has a ripple of 7V maximum in
case of battery fault. The total output current is limited to 1.5A
@ 230Vac (ImaxA eq 146mA). The quiescent current is 25mA (mains
failed, internal sounder active, PSU & gen fault LED lit). The
panel can accommodate two 12V 3.2Ah VRLA batteries connected in
series with a minimum battery size of 1.2Ah.

The panel has 4 detector zone circuits with a maximum length per
circuit of 500m. The call point resistor value is between 470 to
680 and the maximum number of devices per detector zone is 25
detectors (or 32 detectors/manual call points combined). There are
also 4 conventional sounder circuits with a maximum length per
circuit of 500m and an EOL resistor value of 6800 5% Tol. 0/25W
(blue, grey, red, gold). The alarm voltage is 27V max, 20V min
(final battery voltage) and the maximum sounder output current is 4
x 200mA (800mA total).

The panel has two auxiliary relays – Aux. Fire and Fault, which
are volt-free single pole changeover with a maximum switch current
of 1A and a maximum switch voltage of 30Vdc. It also has two open
collector outputs – Reset (Active during reset cycle) and Remote
(Active during any unsilenced fire condition provided all relevant
delays have expired). The maximum sink current is 30mA and the
maximum open circuit voltage is 27V.

The panel has two auxiliary inputs – Class Change (constant
sounders) and Alert (pulsed sounders). These inputs can be
connected to 0V to trigger and have a maximum input voltage of 27V
(non-latching). The panel also has engineer (AL3) functions such as
program coincidence (double knock), invoke One Man Walk Test,
program delays, set up zones for non-latching operation, program
sounders to resound (or not resound) when a new zone enters
alarm.

The panel has expansion connections and product dimensions of
380 W x 235 H x D 96mm (hole required for flush mounting = 367 W x
220 H x 75 D mm. No bezel required). It has a plastic lid and base
with RAL7035 textured finish and an IP Rating of IP30. The weight
of the panel without batteries is 1.75kg.

Product Usage Instructions

1. Connect the mains supply of 230V 50/60Hz to the panel.

2. Connect the two 12V 3.2Ah VRLA batteries in series to the
panel.

3. Connect the detectors and manual call points in the four
detector zone circuits with a maximum length per circuit of
500m.

4. Set the call point resistor value between 470 to 680.

5. Connect the sounders in the four conventional sounder
circuits with a maximum length per circuit of 500m and an EOL
resistor value of 6800 5% Tol. 0/25W (blue, grey, red, gold).

6. Connect the auxiliary relays – Aux. Fire and Fault, which are
volt-free single pole changeover with a maximum switch current of
1A and a maximum switch voltage of 30Vdc.

7. Connect the two open collector outputs – Reset (Active during
reset cycle) and Remote (Active during any unsilenced fire
condition provided all relevant delays have expired). The maximum
sink current is 30mA and the maximum open circuit voltage is
27V.

8. Connect the two auxiliary inputs – Class Change (constant
sounders) and Alert (pulsed sounders). These inputs can be
connected to 0V to trigger and have a maximum input voltage of 27V
(non-latching).

9. Use the engineer (AL3) functions such as program coincidence
(double knock), invoke One Man Walk Test, program delays, set up
zones for non-latching operation, program sounders to resound (or
not resound) when a new zone enters alarm as required.

10. The panel has expansion connections available for use as
required.

11. Mount the panel using the product dimensions of 380 W x 235
H x D 96mm (hole required for flush mounting = 367 W x 220 H x 75 D
mm. No bezel required).

12. Ensure that the panel has an IP Rating of IP30 and a plastic
lid and base with RAL7035 textured finish.

13. The weight of the panel without batteries is 1.75kg.

CFP Standard 4 Zone Conventional Fire Alarm Panel
Part No. CFP704-4
Overview
Certified to EN54 parts 2, 4 and 13, C-TEC’s CFP 4 zone conventional fire alarm panel offers an array of user and installer-friendly features at a very competitive price. Supplied in an attractive flush or surface mountable plastic enclosure, it includes two detector zones, four conventional sounder circuits, class change and alert inputs, on-board fire and fault relays and combined keypad/keyswitch entry. A wide range of engineering functions are also provided including selectable zone delays, coincidence and non-latching zone facilities. Comprehensive test and fault finding facilities are also provided. Optional repeaters and relay expansion boards also available.
More Information
Third-party certified to EN54 parts 2 and 4 by the Loss Prevention Certification Board (LPCB) and EN54 part 13 certified by Kiwa Telefication. Intuitive user-friendly interface with colour-coded buttons and combined keypad/keyswitch entry. Manufactured by C-TEC in the UK. Four detector zone circuits. Four conventional sounder circuits. Integral 1.5A EN54-4/A2 compliant switch mode PSU. Wide range of engineering functions including zone test, coincidence, zone delay and non-latching zones. Two on-board relays (Fire and Fault). Two open-collector outputs (Remote and Reset).

‘Class change’ and alert inputs. Installer-friendly design. Attractive flush or surface mountable plastic lid and enclosure – no bezel required. Low 25mA quiescent current. Multiple indicators. System expansion connections provided for up to eight two-wire repeaters (one CFP761 network card required per system), optional CFP relay boards and optional EN54-13 compliant sounder circuit boards. Space for two x 12V 3.3Ah VRLA batteries. Fully compatible with C-TEC’s ActiV fire detectors, sounders and visual alarm devices.

Technical Specifications

Approvals/certifications

Certifed to EN54 Parts 2 & 4 by the LPCB., Certified to EN54-13 by Kiwa Telefication.

Mains supply

230V 50/60Hz.

Mains rated current

350mA maximum.

Internal power supply

19V-28.5V (27V nominal). Ripple 7V maximum (battery fault).

Total output current limited to

1.5A @ 230Vac (ImaxA eq 146mA).

Quiescent current

25mA (mains failed, internal sounder active, PSU & gen fault LED lit)

Max battery size and type

2 x 12V 3.2Ah VRLA connected in series. Min. battery size 1.2Ah.

No. of detector zone circuits

4 (Max. length per circuit is 500m).

Call point resistor value

470 to 680.

Max. devices per detector zone

25 detectors (or 32 detectors/manual call points combined).

No. of conventional sounder circuits 4 (Max. length per circuit is 500m).

EOL resistor value

6800 5% Tol. 0/25W (blue, grey, red, gold).

Alarm voltage

27V max, 20V min (final battery voltage)

Max. sounder output current

4 x 200mA (800mA total).

Auxiliary relays

Two: (1) Aux. Fire; (2) Fault. Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc.

Open collector outputs

Two: (1) Reset (Active during reset cycle); (2) Remote (Active during any unsilenced fire condition provided all relevant delays have expired). Max. sink current 30mA, Max. open circuit voltag

Other outputs

24V Aux. Power (Protected by a resettable fuse. 100mA min. hold current. Resets when fault removed).

Auxiliary inputs

Two: (1) `Class Change’ (constant sounders); (2) Alert (pulsed sounders). Connect to 0V to trigger, Max. input voltage 27V (non-latching)

Engineer (AL3) functions

Program coincidence (double knock); Invoke One Man Walk Test; Program delays; Set up zones for nonlatching operation; Program sounders to resound (or not resound) when a new zone enters al

Expansion connections

Yes ­ for optional network driver cards (one required per repeater system), relay output cards and EN54-13 sounder circuit interface boards.

Product dimensions (mm)

380 W x 235 H x D 96mm (hole required for flush mounting = 367 W x 220 H x 75 D mm. No bezel required).

Construction & finish

Plastic lid and base; RAL7035 textured

IP Rating

IP30.

Weight

1.75kg (without batteries)

Operating conditions/temperature -5ºC to +40ºC. Max relative humidity: 95%.