GSME-X22 Industrial Fire Gas Detector
Product Information
- Product Name: GSME-X22
- Language: EN (English)
- IP Rating: IP64
- Manufacturer: GTE Industrieelektronik GmbH
- Address: Helmholtzstr. 21, 38-40 41747 Viersen GERMANY
- Support Hotline: +49 2162 3703-0
- Email: [email protected]
The GSME-X22 is a fire gas detector that features four
parameterizable semiconductor gas sensors. These sensors monitor
and evaluate the concentration curve of gases using multi-criteria
technology. This enables the detector to distinguish real fires
from interference signals, especially in harsh industrial
environments where vehicle exhaust fumes, dust, mist, and vapor are
common.
The ADICOS GME-X22 detectors are specifically designed for
operation in hazardous dust atmospheres of ATEX zone 22.
Product Usage Instructions
1. Mounting:
- Follow the instructions provided in the manual to properly
mount the GSME-X22 detector.
2. Wiring:
- Refer to the cable assignment section in the manual for proper
wiring instructions.
3. Commissioning:
- Follow the commissioning instructions provided in the manual to
set up and activate the GSME-X22 detector.
4. Operation:
- Refer to the operation section in the manual for detailed
instructions on how to operate the GSME-X22 detector.
5. Maintenance:
- Regularly perform maintenance tasks as outlined in the manual
to ensure the optimal performance of the GSME-X22 detector. - If necessary, follow the instructions provided in the manual
for detector replacement.
6. Disposal:
- Dispose of the GSME-X22 detector according to the guidelines
provided in the manual.
For more technical data and additional information, refer to the
appendix section in the manual.
GSME-X22
EN
IP64
Supplementary Instruction Manual for GSME-X22
Fire Gas Detector
GTE Industrieelektronik GmbH | Helmholtzstr. 21, 38 40 41747 Viersen | Germany | +49 2162 3703-0 | [email protected]
Supplementary Instructions for GSME-X22 Article number: 400-2410-002 Index: EN24 Release date: 15.03.2023
Translation
Manufacturer: GTE Industrieelektronik GmbH Helmholtzstr. 21, 38-40 41747 Viersen GERMANY
Support hotline: +49 2162 3703-0 E-Mail: [email protected]
© 2023 GTE Industrieelektronik GmbH This document and all figures contained may not be copied, changed, or distributed without explicit approval by the manufacturer! Subject to technical changes!
ADICOS® and GSME® are registered trademarks of GTE Industrieelektronik GmbH.
2
400-2410-002 EN24
ADICOS GSME-X22
ABSTRACT
Abstract
The Advanced Discovery System (ADICOS®) is used for early detection of fires in industrial environments. It is comprised of various, separate detector units. By parameterizing and arranging the detectors appropriately, the system fulfills a predefined detection goal. The ADICOS system ensures reliable early detection of embers and smoldering fires even in adverse environments.
ADICOS GSME fire gas detectors detect at an early stage gases that are characteristic for developing fires. They detect both open and concealed smoldering fires. Highly sensitive and at the same time robust, they are ideal for fire gas detection in industrial environments and already in the incipient stage. With the ADICOS software, all detector states and concentration curves can be displayed graphically. Sensitivities as well as alarm thresholds can be parameterized individually for each detector. The GSME fire gas detectors can be used in almost any indoor plant area, taking into account the air flow conditions.
Four parameterizable semiconductor gas sensors monitor and evaluate the concentration curve of these gases according to multi-criteria technology. This enables the GSME detectors to distinguish real fires from interference signals. In industrial environments, this often occurs under harsh conditions, e.g. due to vehicle exhaust fumes, dust, mist and vapor.
ADICOS GME-X22 detectors are designed for operation in hazardous dust atmospheres of ATEX zone 22.
ADICOS GSME-X22
400-2410-002 EN24
3
CONTENTS
Contents
1 About this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.1 Objective. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.2 Explanation of Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.3 Storing the Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2.1 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2.2 Standards and regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2.3 Personnel Qualification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2.4 Handling Electrical Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2.5 Modifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2.6 Accessories and Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3 Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 3.1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 3.2 Cable Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 4.1 Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 4.2 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 6 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 7 Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
7.1 Detector replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 8 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 9 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
9.1 ID Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 10 Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
10.1 ADICOS mounting plate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4
400-2410-002 EN24
ADICOS GSME-X22
About this mAnuAl
1 About this manual
1.1 Objective This manual describes the special requirements on installation, wiring, commissioning, and operation of ADICOS detectors for explosive atmospheres of ATEX zone 22. They are exclusively addressed to knowledgeable specialist personnel (> Chap. 2, Safety instructions). 1.2 Explanation of Symbols This manual features a continuous structure for best possible comprehension. The following labels are used.
Warning signs The following types of notes are used through this manual.
DANGER! This combination of symbol and signal word indicates an immediately dangerous situation that will lead to death or severe injuries if not avoided.
WARNING! This combination of symbol and signal word indicates a possibly dangerous situation that could lead to death or severe injuries if not avoided.
Explosion Protection This information type signals measures that must be implemented for maintaining the Explosion protection.
Tips and recommendations Helpful tips and recommendations as well as information to ensure efficient and uninterrupted use.
1.3 Storing the Manual Store this manual easily reachable and in direct vicinity of the detector system to enable use as needed.
ADICOS GSME-X22
400-2410-002 EN24
5
sAfety instructions
2 Safety Instructions
ADICOS GSME-X22 detectors for explosive atmospheres up ATEX zone 22 ensure operational safety assuming proper installation, commissioning, operation, and maintenance. For this purpose, it is absolutely required to completely read, understand, and follow this manual and the safety information contained.
WARNING! Personal injury and property damage! Incorrect installation and operating errors can cause death, serious injury and damage to industrial equipment. · Read the entire manual and follow the instructions!
Explosion protection When using ADICOS detectors in potentially explosive atmospheres, follow the specifications of the ATEX operating directive.
2.1 Intended use
ADICOS GSME-X22 are designated for the detection of fire scenarios in explosive atmospheres of ATEX zone 22. In this context, the operating parameters described in Chap. 9, »Technical Data« must be met. Any deviating use requires prior consultation with the manufacturer.
Compliance with this manual as well as all applicable country-specific provisions is also part of the intended use.
2.2 Standards and regulations
The safety and accident prevention regulations applicable for the specific application must be observed during detector installation, commissioning, maintenance, and test.
The following standards and directives in their current version are of particular importance when handling potentially explosive atmospheres:
Standards and Regulations EN 60079-0 EN 60079-31 EN 60529 2014/34/EU
1999/92/EG
Description
Explosive atmospheres – Part 0: Equipment General requirements
Explosive atmospheres – Part 31: Equipment dust ignition protection by enclosure ,,t”
Degrees of protection provided by enclosures (IP Code)
ATEX product directive (about equipment and protective systems intended for use in potentially explosive atmospheres)
ATEX operating directive (on safety and health protection of workers potentially at risk from explosive atmospheres)
6
400-2410-002 EN24
ADICOS GSME-X22
sAfety instructions
2.3 Personnel Qualification
Any work on ADICOS systems may only be performed by qualified personnel. Persons, who can perform work on electrical systems and recognize possible dangers based on their professional education, knowledge, and experience as well as knowledge of the applicable provisions, are considered qualified personnel.
WARNING! Personal injury and property damage! Improperly performed work on and with the device can lead to malfuctions. Installation, startup, parameterization and maintenance may be
performed only by authorized and properly trained personnel.
2.4 Handling Electrical Voltage DANGER! Risk of explosion by electrical voltage in potentially explosive atmospheres! The electronics of ADICOS GSME-X22 detectors requires an electrical voltage that can trigger an explosion in potentially explosive atmospheres. · Do not open enclosure! · De-energize the entire detector system and secure against unintentionally reactivation for all wiring work!
2.5 Modifications
WARNING! Property damage or detector failure by any form of unauthorized modification! Any form of unauthorized modification or extension can lead to a failure of the detector system. The warranty claim expires. Never make unauthorized modifications on your own authority.
2.6 Accessories and Spare Parts
WARNING! Property damage due to short circuit or failure of the detector system The use of parts other than the manufacturer’s original spare parts and original accessories may result in property damage due to short circuits. Only use original spare parts and original accessories! Original spare parts and accessories may only be in-
stalled by trained specialist personnel. Qualified personnel are persons as described in Chap. 2.3.
ADICOS GSME-X22
400-2410-002 EN24
7
100
structure
3 Structure 3.1 Overview
3 2
1
100
No. Description Enclosure Display elements Spray protection Sinter metal filter Cable gland
4 5
28
8
400-2410-002 EN24
ADICOS GSME-X22
3.2 Cable Assignment
3.2.1 12-pin cable; LEONI KERPEN ICONBASE
Wire
1 1 2 2 3 3 4 4
Color
black white black white black white black white
Signal
Operating voltage DC 21.6 … 40 V non-polarised
Relay output X6 e Relay output X6 a Relay output X7 a Relay output X7 e
M-Bus max. 40 V non-polarised
Option fire panel interface
Wire
Color
Siemens FDnet
5
black FDnet (+)
5
white FDnet-A (-)
6
black FDnet (+)
6
white FDnet-B (-)
Bosch LSNi
LSN a in LSN b1 in LSN a out LSN b2 out
Option auxiliary relay
Wire
Color
5
black
5
white
6
black
6
white
Auxiliary relay Normally closed Normally open Common
structure
Limit value contact
Alarm NO1 Alarm NO1 Fault NC Fault NC
1 with series resistor
ADICOS GSME-X22
400-2410-002 EN24
9
structure
3.2.2 12-pin cable OELFLEX 415CP
Wire
1 2 3 4 5 6 7 8
Signal
Operating voltage DC 21.6 … 40 V non-polarised
M-Bus max. 40 V non-polarised
Relay output X6 e Relay output X6 a Relay output X7 a Relay output X7 e
Limit value contact
Alarm NO1 Alarm NO1 Fault NC Fault NC
1 with series resistor
Option fire panel interface
Wire
Siemens FDnet
9
FDnet-A (-)
10
FDnet (+)
11
FDnet-B (-)
12
FDnet (+)
Bosch LSNi
LSN b1 in LSN a in LSN b2 out LSN a out
Option auxiliary relay
Wire
Auxiliary relay
9
Normally closed
10
11
Common
12 Normally open
10
400-2410-002 EN24
ADICOS GSME-X22
instAllAtion
4 Installation
4.1 Mounting
DANGER! Risk of explosion due to electrical voltage in hazardous areas. The electronics of ADICOS GSME-X22 works with an electrical voltage that can trigger an explosion in potentially explosive atmospheres. · Do not open enclosure! Mount the device with closed housing! · Use ADICOS mounting plate, if necessary!
ADICOS GSME-X22
400-2410-002 EN24
11
commissioning
4.2 Wiring
Wiring according to chapter 3.2. DANGER! Risk of explosion due to electrical voltage in hazardous areas. The electronics of ADICOS GSME-X22 works with an electrical voltage that can trigger an explosion in potentially explosive atmospheres. · Do not open enclosure! Mount the device with closed enclosure. · De-energize the entire detector system and secure against unintentionally reactivation for all wiring work! · In the case of wiring within potentially explosive atmospheres, only use Ex-protected connection boxes with respective approval! · Do not bend connection cable! Observe minimum bending radius! (> Chap. 9, Technical Data)
5 Commissioning
DANGER! Risk of explosion due to electrical voltage in hazardous areas. The electronics of ADICOS GSME-X22 detectors works with an electrical voltage that can trigger an explosion in potentially explosive atmospheres. · Prior to switching on, check that all detectors are properly mounted and
wired!
6 Operation
DANGER! Risk of explosion due to electrical voltage in hazardous areas. The electronics of ADICOS GSME X22 detectors works with an electrical voltage that can trigger an explosion in potentially explosive atmospheres. · Never open the enclosure or loosen the cable gland during operation!
7 Maintenance 7.1 Detector replacement
DANGER! Risk of explosion due to electrical voltage in hazardous areas. The electronics of ADICOS GSME-X22 works with an electrical voltage that can trigger an explosion in potentially explosive atmospheres. · Do not open enclosure! · De-energize the entire detector system and secure against unintentionally
reactivation for all wiring work! · Replace the closed detector including connection cable only!
12
400-2410-002 EN24
ADICOS GSME-X22
DisposAl
8 Disposal
Return the device to the manufacturer when it reaches the end of its serviceable life. The manufacturer will ensure that the components are disposed of properly, in an environmentally friendly manner.
9 Technical Data
General Model Item No. Enclosure dimensions
Weight (7 meter cable incl.) Degree of protection Enclosure
GSME-X22
408-2001-251
mm
128 x 100 x 100 (Length x Width x Depth)
(Length: cable gland incl.)
kg
2
IP64 Aluminum die-cast, powder-coated
Electrical properties
Voltage range
Power consumption without heating with heating
M-Bus voltage (signal):
V
VA VA V/mA
DC 21,6 … 40
4 14 max. 40 V non-polarized / max. 30 mA
Thermal, physical data
Ambient temperature
°C
20 … +50
Relative humidity
%
95 (non-condensing)
Optional communication modules (input parameters)
Interface module Siemens FDnet
V
ADICOS
V
Interface module 4…20 mA
Interface module Bosch LSN
V
Pre-alarm relaiy module
V
V
DC 33 V; max. 10 mA DC 35 V; max. 20 mA
DC 36 V; max. 20 mA DC 40 V; max. 10 mA DC 24 V; max. 20 mA
ADICOS GSME-X22
400-2410-002 EN24
13
technicAl DAtA
Sensor Data
Sensor combination
Reaction time
s
Detection szenarios
Information regarding explosion protection
Explosion protection class
Max. surface temperature
°C
Device group
Other
Bending radius connection cable
mm
CO H2 HC NOx > 30 Smoldering fires according to EN 54-7 Fires emerging from smoldering coals
II 3D Ex tc IIIC T 80 °C Dc 80
II, Kategorie 3D
> 91,5
9.1 ID Plate
Model: Device model
ART-Nr: Article number (variable)
COM-Nr: Communication number (variabel)
CE marking
SERIAL: Serial number (variable)
YR: Year of production (variable)
TEMP: VDC/VA:
Ambient
IP:
temperature
Voltage range / maximum pow-
I
0 :
er consumption
(heating incl.)
Degree of protection
Internal fusing (Short-circuit current)
Information on explosion protection
14
400-2410-002 EN24
ADICOS GSME-X22
10 Appendix
10.1 ADICOS mounting plate 150 130
AppenDix
A
A
150 130
6,4 A-A
ADICOS GSME-X22
400-2410-002 EN24
15