Munters Cx24p1 Cx Circulation Fan 24 Inch Instruction Manual

Munters Cx24p1 Cx Circulation Fan 24 Inch Instruction Manual

Munters CX24P1 CX Circulation Fan 24 Inch Instruction Manual
Munters CX24P1 CX Circulation Fan 24 Inch

Unpacking the Equipment

Before beginning installation, check the overall condition of the equipment. Remove packing materials, and examine all components for signs of shipping damage. Any shipping damage is the customer’s responsibility and should be reported immediately to your freight carrier. Fan is shipped complete with all accessories.

Parts List

Each CX24P1/CX24P3/CX24PW1/CX24PW3 Fan includes:
1 – Direct Drive Circulation Fan

Each CX24P1G/CX24P3G/CX24PW1G/CX24PW3G Fan with Guard includes:
1 – Direct Drive Circulation Fan
1 – Guard, Inlet/Outlet Pair, PWDCTD
1 – Hardware Package as follows:

HP1246 – Fan with Guard

ID Qty. Cat. No. Description
[A] 4 KS0650 1 ⁄4”-20 x ⁷⁄₈” Truss Head Bolt, SS
[B] 8 KN1705 1 ⁄4”-20 Hex, Nylock Nut, ZP
Parts List

Fan Dimensions

Fan Specifi cations:
Hertz: 60 50 – 60
Voltage: 115/230VAC or 190 – 208-230/380 – 460VAC
Phase: 1 or 3
Dimensions

CAT. NO. FAN DIA.
NO. OF BLADES A B C D – Dia. (O.D.)
CX24 24” 3 303 ⁄4” 127 ⁄8” 81 ⁄4” 243 ⁄4”

Installation Instructions

Fan Installation

Step 1
For Horizontal Airflow attach chain to 2 of the Eye Bolts on the fan and then hang the fan from truss. See Figure 1A. Chain and hanging hardware not provided. If it is desired to pull the fan up out of the way when not in use for cleaning, then attach a cable or rope to the Lift Bracket and use a winch or actuator to pull the fan up. See Figure 1B.

Instruction

Step 2
For Vertical Airflow attach chain to 4 of the Eye Bolts on the fan and then hang the fan from trusses. See Figure 2. Chain and hanging hardware not provided.
Instruction

IMPORTANT
If installing fans near heaters, it is recommended to install the CX24 Fan at a location far enough from heaters that will give a maximum temperature of 150°F. This should be approximately 2-3 ft. from the heater.

Optional Guard Installation

Step 3
The Inlet Guard is the one with the large inner hole to go over the motor. With the eyelets on the guard pointing into the fan slip the eyelets over the shaft of the Eye Bolts and fasten using (4) Nuts [B]. See Figure 3.

Instruction

Step 4
The Outlet Guard is the one with the small inner hole. With the eyelets on the guard pointing toward the fan, align the eyelets with the holes in orifice on the outside of the fasten using (4) Bolts [A] and Nuts [B]. The head of the bolt goes on the inside of the orifice and the nut goes on the outside. See Figure 4.

Instruction

Electrical Wiring

All wiring should be installed in accordance with National, State, and Local electrical codes. Fans used to ventilate livestock buildings or other rooms where continuous air movement is essential should be connected to individual electrical circuits, with a minimum of two circuits per room. For electrical connection requirements, refer to diagram on motor nameplate and to information enclosed with the Munters environmental control to be used. After wiring check for proper motor rotation.
Single Phase Fans: motor overload protection should be provided for each fan. A Circuit Breaker Switch or slow blow motor type fuses must be used, See Figure 5A. See form QM1400 for proper size. Three Phase Fans: motor overload protection should be provided for each fan. A three-pole motor starter or slow blow motor fuses must be used. See Figure 5B.
If a frequency drive (inverter) is used, confirm that motors are rated for inverter duty at the voltage used. Shielded power cable between frequency drive and each motor is highly recommended. Installation of line reactors is recommended to reduce voltage spikes and harmonic distortion. Supplemental motor overload protection is also recommended.

NOTE: A safety cut-off switch should be located adjacent to each fan.

Instruction

Single Phase – Motor Overload Protection with Disconnect (SY2000 or Equivalent)

Instruction
Three Phase – Motor Overload Protection with Disconnect

KEY:
L1=Line 1
L2=Line 2
L3=Line 3
H=Hot
N=Neutral
G=Ground

NOTE: Information in parenthesis refers to 120 VAC control.

Recommended Wire Routing:

As the power cable exits the back of motor form a drip loop and then run power cable up along leg of motor mount and “Zip” tie the cable to leg to prevent cable from getting tangled. See Figure 6. Then run the cable out the back of fan to the circuit breaker or control panel.

Recommended Wire Routing

Three Phase Fans:

  1. The use of a quality frequency drive and the installation of line reactors is recommended to reduce voltage spikes and harmonic distortion.
  2. Minimum operating frequency of 30 Hz.
  3. Will require three pole contractors with overload protection (by others).

Operation

INITIAL START-UP: With electrical power off, verify that the fan propeller turns freely and that all fasteners are secure. Turn on electrical power and confirm that the fan operates smoothly.
Warning Instruction
ADJUSTMENTS: Set the fan control to the temperature shown on your ventilations system drawing, or to a value which will provide the desired environmental conditions.
Warning Instruction
Single Phase Fans: When variable speed controls are used, the fan’s idle speed will need to be set to the recommended minimum airflow rate. Refer to the procedures included with each control. The table below provides airflow rates at various propeller speeds for fans wired for 240 VAC.
Warning Instruction

Maintenance

The following inspection and cleaning procedures should be performed monthly:

  1. INSPECT PROPELLER: Check that propeller is secure on motor shaft and that there are no signs of damage. The blades are of a self-cleaning design and should not require maintenance.
    Warning Instruction
  2. CLEAN regularly for best results:
    • FAN MOTOR: Remove any dust accumulation from motor using a brush or cloth. (DO NOT use a pressure washer). A clean motor will run cooler and last longer. At the same time, verify that the motor is secure in its mount.
    • GUARD: Clean any dust or feathers from fan guards using a brush. Dirty guards can reduce airflow.
      Warning Instruction
  3. CHECK FASTENERS: For safety, all fasteners should be inspected 1 month after initial operation and yearly thereafter. Tighten any loose connections.
    Warning Instruction
  4. INSPECT FAN CONTROL: With power disconnected, inspect all electrical connections. Wiring should be secure and in good condition. Remove any dust build-up from control case and sensor using a soft brush or cloth. NEVER CLEAN ELECTRICAL EQUIPMENT WITH A PRESSURE WASHER!

Troubleshooting

Warning InstructionWarning Instruction

SYMPTOMPOSSIBLE CAUSESCORRECTIVE ACTION
Fan Not Operating1.Fan control set above room1.Set to a lower temperature
temperature2.Replace fuse or reset breaker
2.Blown fuse or open circuit breaker3.Realign motor in fan housing
3.Propeller blade contacting fan housing4.Repair or replace control
4.Fan control defective5.Repair or replace motor
5.Motor defective
Fan Operating-1.Variable speed control improperly1.See Operation, Step 2 for adjustment guidelines
Insufficientadjusted2.Clean guard
Airflow2.Guard dirty
Excessive Noise1.Propeller blade contacting fan housing1.Sand fan housing to remove high spot
2.Motor bearing defective2.Repair or replace motor bearings
3.Frequency drive improperly adjusted3.See operation, Step 2 for adjustments guidelines
Excessive1.Motor loose on mount1.Tighten fasteners
Vibration2.Propeller damaged2.Replace propeller
3.Motor shaft bent3.Repair or replace motor
Fan never turns off1.Override thermostat set incorrectly1.Set to the correct temperature
2.Control set for continuous operation2.Set speed control correctly

Exploded View

Instruction

1FH1624Guard Inlet/Outlet Pair, PWDR CTD (Guard Kit)1
2FP1724Propeller, 24”DD, 3-Blade, CX24, GZ1
3FH4224BOrifice Panel, 24″ CX Fan, PP, BLK1
FH4224WOrifice Panel, 24″ CX Fan, PP, WHT1
4KS2757¼”-20 x 2.5″ Closed Eye Bolt, SS4
5KW3012¼” x 1″ O.D. Flat Washer, SS2
6KS10297⁄₁₆”-18 x 1.75″ Hex Head Bolt, SS1
7FH2524Motor Mount, 24″ CX Fan, PWDR CTD1
8KN1705¼”-20 Nylock Nut, SS (Fan/Guard Kit)4/8
9FM1108C24” DD, Motor w/ capacitor, ¹⁄₃ HP, 1075 RPM, 48 Fr., 1 ph., 115/230V1
FM107424” DD, Motor, ¹⁄₃ HP, 1140 RPM, 48 Fr., 3 ph., 230/460V
10KN07047⁄₁₆”-18 Hex, Serrated Flange Nut, SS1
11KW30047⁄₁₆” Narrow Type-A Flat Washer, SS2
12FH1324Lift Bracket, 2 Point Conn,CX24 Fan, PWDR CTD1
13KS06501⁄4”-20 x ⁷⁄₈” Truss Head Bolt, SS (Guard Kit)4

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals