Siemens 5128 Digital Fire Communicator Instruction Manual

Siemens 5128 Digital Fire Communicator Instruction Manual

SIEMENS-logo

SIEMENS 5128 Digital Fire Communicator

SIEMENS -5128-Digital-Fire-Communicator-PRODUCT

OPERATION

The SIEMENS MXL reports system conditions to a Central Station using the Silent Knight Model 5128/ 5129, a four-channel digital communicator that reports alarm, trouble, supervisory, and miscellaneous status. When used with the MXL, the Silent Knight Model 5128/5129 uses the alarm, trouble, and supervisory channels. The miscellaneous status channel may be used to annunciate conditions other than fire at the Central Station.

ELECTRICAL CHARACTERISTICS

  • Supervisory: 60mA, 18-40 VDC
  • Alarm: 130mA, 18-40 VDC

INSTALLATION

Remove all system power before installation, first battery and then AC. (To power up, connect the AC first and then the battery.)

Mounting

Silent Knight Model 5128

Mount the Silent Knight Model 5128 within the MXL enclosure. Alternate mounting for the Silent Knight 5128 may include double-sided tape, velcro, or snaptrack.

Silent Knight Model 5129

The Silent Knight Model 5129 must be mounted adjacent to the MXL Control Panel and within 20 feet of it using an electrical conduit.

Electrical

The MXL Control Panel connects to the Silent Knight Model 5128/5129 Digital Fire Communicator using the Alarm, Trouble, and Supervisory dry contacts on the MXL Main Board (See Figure 1) Refer to the Silent Knight 5128/5129 Fire Slave Communicator Installation Manual, P/N 150805, provided with the Silent Knight Model 5128/5129 for dialer instructions.

The Silent Knight Model 5128/5129 monitors all System troubles through the MXL trouble relay. The MXL delays the AC fail trouble signal in accordance with NFPA and UL requirements. In NFPA 72 Remote Station install batteries to provide 60 hour standby capacity. For signalling service DACT wire according to the Figure 1. In NFPA 72 Central Station connections AC fail reporting is delayed. The delay is typically 6 hours (25% of 24 hours). Only the reporting of the trouble is delayed. AC power must be present for a full minute before the system switches back to AC power from the battery.

Using the optional AC monitor input (See Figure 1), the Silent Knight Model5128/5129 monitors AC fail trouble. When the MXL System reports an AC fail trouble, the Slent Knight Model 5128/5129 sends a specific code to the Central Station that identifies the trouble as AC fail. Refer to the MXL/MXLV Manual, P/N 315-092036 for MXL System information.

PROGRAMMING

The Silent Knight Model 5230 LCD Keypad Program mer can be connected temporarily to Pin P4 on the Silent Knight 5128 Main Board (See Figures 1 and 2) for on-site programming or troubleshooting of the communicator. English language messages assist in entering data, changing the 24-hour test time, and describing conditions currently in effect.

Table 1 lists the recommended program for the Silent Knight 5128/5129 Digital Fire Communicator. Before you begin programming, read the Step Program- ming Form in the Silent Knight Model 5128/5129 Fire Slave Communicator Installation Manual, PlN 150805, provided with the Silent Knight 5128/5129.

Silent Knight Model 5128/5129 Programming Table

Step No. 

Option Name

 

Select

Step No. 

Option Name

 

Select

1ZONE ACTIVE021RINGSSKIP See Note 2
2ZONE SUPERVISEDyes223/1 ALARM CODE
3ALARM CHANNEL INPUT0233/1 TROUBLE CODE
4TROUBLE CHANNEL INPUT0243/1 RESTORE CODE
5SUPERVISORY CHANNEL0253/1 TEST CODE
6ZONE RESPONSE 10263/1 SPRINKLER SUPERVISORY
7ZONE RESPONSE 2SKIP See Note 227ALARM 1 FIRSTyes
8ZONE RESPONSE 3028TROUBLE 1 FIRSTyes
9ZONE RESPONSE 4029TEST 1 FIRSTyes
10RELAY 1130ACCOUNT 1
11INSTALLERS CODE31ATTEMPTS 13
12OPERATORS CODE32FORMAT 1
13DIALER TYPE033PHONE 1
14COMPUTER ENABLEno34ACCOUNT 2
15TOUCHTONE LINE 1yes35ATTEMPTS 23
16TOUCHTONE LINE 2yes36FORMAT 2
17MUST REPORT 1yes37PHONE 2
18MUST REPORT 2yes38COMPUTER ACCOUNTSKIP See Note 2
19AC MONITORING239COMPUTER PHONESKIP See Note 2
20AC LOSS HOURSSee Note 440TEST TIME
41CURRENT TIME

NOTES

  1. If the selection is left blank, the user must fill in the proper information.
  2. Skip= No selection is required.
  3. After each selection is made, press the ENTER key to proceed to the next step.
  4. For Systems Configured as NFPA 72 Local, enter 6 hours.
    • For Systems Configured as NFPA 72 Auxiliary or Remote Station, enter 15 hours.

NOTESSIEMENS -5128-Digital-Fire-Communicator-FIG-1

  1. TRI-60RI-B6RI-R input must be programmed in CSG-M as trouble causing.
  2. TRI-6ORI-B6RI-R output must be programmed in CSG-M to transfer on loss of AC Mains.
  3. All wiring supervised except as noted.
  4. For Remote Station, provide 60-hour battery capacity.

ADDRESS

Siemens Building Technologies, Inc.

  • 8 Fernwood Road
  • Florham Park, New Jersey 079332 P/N 315-093294-4

Siemens Building lechnologies, Ltd

  • 2 Kenview Boulevard
  • Brampton, Ontario L6T 5E4 CN

Technical Manuals Online: http://www.tech-man.com

firealarmresources.com

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals