Siemens Fc901 Addressable Fire Alarm Control Panel System Instruction Manual

Siemens Fc901 Addressable Fire Alarm Control Panel System Instruction Manual

siemens-logo

SIEMENS FC901 Addressable Fire Alarm Control Panel System

SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-PRODUCT-IMAGE

Accessories and separate parts

AccessoriesContentInstallation instructionQuantity
1SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-01Cable between batteries, refer to figure 11
2SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-02Cable between batteries and main board, refer to figure 1 and figure 21
3SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-03Cable between City tie board and main board, refer to figure 21
4SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-04Earth cable between enclosure and main board, refer to figure 1 and figure 21
5SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-05Grounding cable for front door and power supply, refer to figure 12
6SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-06Battery bracket left, refer to figure 11
7SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-07Battery bracket right, refer to figure 11
8SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-08Cable ties10
9No.8 screws, refer to figure 112
10SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-10No.4 screws, refer to figure 22
11Spacer for City tie board, refer to figure 22
12SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-12Power supply MOV (Metal Oxide Varistor), refer to figure 21
S1SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-13
Battery cell, refer to figure 12
S2SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-14Power supply, refer to power supply installation instruction sheet delivered with power supply1
S3SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-15Front door hinge axis lock pin, refer to Detail A2
S4SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-16Front door hinge axis, refer to Detail A2
S5SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-17EOL for NAC, refer to Detail C2

Note: Item 3,6,7,11,S1and S2 are not delivered with the FC901 and FC2005, and should be ordered separately.

Assembling notes
  1. Mount the batteries with battery brackets.
  2. Mount the power supply MOV, then mount the power supply to the enclosure.
  3. Mount the City tie module onto the main board according to the Figure 2 (City tie module is optional).
  4. Connect the cables to the corresponding position marked on the drawing. (The power supply input cable and output cable are not included in the FC901 and FC2005 package.)
  5. Mount the Main board assembly onto the Enclosure according to Figure 3.
  6. Mount the Lock pin to the Front door axis. (Both are included in the Enclosure package.)

NOTICE
Pay attention to the battery polarity at 2.1 and 2.2

SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-18Figure 1: Installation instruction (Front view with front door open)

SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-19Detail A: Front door hinge and lock pin installation instruction

SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-20

Figure 2: Installation instruction (Main board assembly back view) SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-21

SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-22Figure 3: Main board assembly installation instruction

SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-23Detail C: NAC EOL installation instruction

Steps:

  1. Bend the MOV connector pin according to the figure below. SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-24
  2. Fix or weld the MOV onto the power input connector. SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-25
  3. Fix the AC input cable and screws on the connector. SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-26
Installation instruction with trim kit

SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-27

SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-28

Technical data

Environmental
Operating temperature -32-120°F (0-49°C)
Relative humidity – Up to 93% @ 90°F (32°C)
To be installed in an indoor dry protected environment only

Primary Power Supply (FP2011-U1)
Input: 120 VAC, 60 Hz or 240 VAC, 50 Hz
@ 2.0 A max.
Supervised
Output: 26 VDC @ 6.5 A max.
Max current: 6.5 A (2 hours max.)
Filtered and Regulated

Secondary Power Supply
24 V lead-acid battery set
Max. charged voltage: 27.8 VDC
Automatic low battery disconnect voltage: 19.2±0.1 VDC Max. charge current: 0.45 A
Battery capacity:12 AH internally to 18 AH with separate enclosure FH2072-UA
Supervised

Auxiliary Power Outputs

Non-resettable power outputResettable power output
Power limitedPower limited
Current: 0.75 ACurrent: 0.75 A
Voltage: 19 to 28 VDCVoltage: 19 to 28 VDC
Ripple: 0.1 VACRipple: 0.1 VAC
Special ApplicationSpecial Application

Status Relays
Non-power limited
One programmable relay
Three non-programmable relays: Trouble, Supervisory, Alarm
Contact rating: 2 A, 30 VDC maximum
Form C contact

Notification Appliance Circuits
Power limited Supervised

Current DrawMaximum Line Resistance
2.5 A3.2 Ω
2.0 A4.0 Ω
1.5 A5.3 Ω
1.0 A8.0 Ω
0.5 A16.0 Ω

Alarm voltage: 16 to 32 VDC
Maximum ripple: 0.1 VAC
Used for special application only
Two Class B or one Class A
Total Max. Current: 2.5 A

Serial Interface Circuit (UFP)
Power limited
Supervised
Maximum wire loop resistance: 50 Ω total Physical layer: RS485

SLC Addressable Device Circuits
Max. 32 VDC
Power limited
Supervised
Max. current: 0.07 A (RMS)
Maximum wire loop resistance: 50 Ω
Two Class B or one Class A circuit
Max. 50 addressable devices

City Tie Circuits
Supply Input:
Voltage: 26 VDC / 18 – 28 VDC for battery
Current: Max. 0.4 A
Supervised

Output

City Tie-Output 1
Normal output voltage: 19-28 VDC (open circuit condition) Supervisory current: 1 mA
Maximum trip current: 400 mA
Maximum coil plus wire resistance: 22.5 Ω

Leased line-Output 1
Normal output voltage: 19-28 VDC (open circuit condition) Trouble output voltage: 0 V
Alarm output voltage: -(19-28) VDC (open circuit condition) Maximum wire resistance: 2-5 KΩ
Maximum short circuit current: 25 mA

Leased line-Output 2
Normal output voltage: 19-28 VDC (open circuit condition) Supervisory output voltage: -(19-28) VDC (open circuit condition)
Maximum wire resistance: 2-5 KΩ
Maximum short circuit current: 25 mA

DACT Circuits
Power limited
Supervised for short or open circuit conditions Compliance to FCC part 68

Support RJ31X connection
Compatible Digital Alarm Communication Receiver (DACR) list,

Device ModuleManufacture
MX8000Honeywell

CAUTION:

  • To reduce the risk of fire, use only No. 26 AWG or larger telecommunication line cord.
  • Only to a loop start telephone circuit and not to a ground start telephone circuit.
  • To verify the integrity of the call forwarding feature every 24 hours.
FC901/FC2005 system connection diagram

SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-29NOTICE
All the wiring must be in accordance with local codes and the National Electric Code.

SLC loop connections
Supervised and power limited. Refer to the user manual (A6V10333722 and A6V10336754) Appendix B to get detailed device compatibility list for FC901 and FC2005. SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-30

 

Auxiliary power
Non-supervised and power limited

Auxiliary power output 2 (Resettable, power limited) SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-31

Auxiliary power output 1 (Non-resettable, power limited) SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-32

Series interface circuit

Power limited SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-33

City tie or lease line
Power limited SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-34

SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-38

Notification application circuits
Supervised, power limited, max. current (NAC A + NAC B) = 2.5 A SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-35

DACT
Power limited

DACT compatibility list

Device moduleManufacture
MX8000Honeywell

SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-36

Relays
Non power limited, 2.0 A @ 30 VDC (resistive), 0.5 A @ 30 VAC (resistive) SIEMENS-FC901-Addressable-Fire-Alarm-Control-Panel-System-37

Issued by
Siemens Industry, Inc. Smart Infrastructure
8 Fernwood Road Florham Park, NJ 08932 Tel. +1 973-593-2600 www.sbt.siemens.com/FIS

© Siemens Industry, Inc., 2019
Technical specifications and availability subject to change without notice.

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals