Honeywell Home Ewa1xxc-mbus User Guide

Honeywell Home Ewa1xxc-mbus User Guide

logo

Honeywell Home EWA1xxC-MBUS

product

Introduction
EWA1xxC-MBUS are a range of clip on modules for EW110 and EW171 Series water meters. Meters fitted with this module have two configurable pulse out-puts for remote readout. Per meter one module is required. The module is ret-rofittable at any time, also when the meter is in operation. When the module is in place no other module can be fitted as EW110 and EW171 Series only pro-vide space for one module. Other available modules are Pulse out (EWA1xxC-PO). However, this document only includes in-structions for configuration of the M-Bus module.

Scope
These instructions are valid for the following modules:
Table 1. OS-Numbers covered

OS-NumberItem
EWA110C1520-MBUSM-Bus clip-on module for EW110 Series, DN15 and DN20
EWA110C2540-MBUSM-Bus clip-on module for EW110 Series, DN25 to DN40
EWA171C-MBUSM-Bus clip-on module for EW171 Series, DN50 to DN300

Preparation

Programming of M-Bus clip on modules is done via the M-Bus master EW535M. It is not possible to program the module before it has been connected to the M-Bus. For programming the second-ary address of the module must be known. If the actual volume should be included in the programming this data must also be known.image 1Standard Values
Before programming modules check if standard values are not sufficient and thus make programming needless:
Table 2. Standard values

OS-No.Baud rateVolumeBackward flowMin/max flowLeakagePrimary addressLack of flow
EWA110C1520-MBUS2,4000deactivateddeactivated, JS1.6deactivated0deactivated
EWA110C2540-MBUS2,4000deactivateddeactivated, JS6.3deactivated0deactivated
EWA171C-MBUS2,4000deactivateddeactivated, MWN40deactivated0deactivated

Required Parts
The following parts are required to change the programming of the module. The list is based on the assumption that programming will be done via an EW535M IzarCenter M-Bus master unit.
Table 3. Required parts

PartFunction
Serial cable

(supplied with Izar- Center)

Interface between PC and module
USB / serial adapterConnect serial cable to PCs without serial interface
Configuration software EWASET-MBUSProgram new values into moduleDownloadable free of charge from

https://homecomfort.resideo.com/sites/Europe/en-gb/Solu- tions/Metering/Pages/Metering.aspx

Wiring to PC
Wiring between PC and module is done via the M-Bus master EW535M. Connection between PC and M-Bus mas-ter must be done over the serial port, not the USB port, of the IzarCenter.image 2

Programming

Wake up
NOTE: This chapter applies only to modules produced before August 2015. After production the module is put into sleep mode to save battery life. When installed on a meter the module is woken up automatically. For programming before installation briefly place a magnet near the reed switch of the module. By this the module is woken up from sleep mode.image 3Softwareimage 4

Fields

Field No.Field nameField typeFunction
1Port COMPulldownSelect COM port over which the PC is con- nected to the M-Bus master.
2Module No.InputPut in secondary address of module which should be programmed.
3Baud ratePulldownSelect baud rate for communication. Standard baud rate is 2,400.
4Set new baud ratePulldownSelect new baud rate if required and program with “Set baud” button.
5Set baudExecute button
6Refresh COMsExecute button
7Events resetExecute button
8VolumeActivation / inputOptionally put in meter volume count
9Module typePulldownSelect module type to be addressed
10Set present timeActivationOptionally activate if PC time should be pro- grammed into module.
11Backward flowActivation / inputOptionally set backward flow threshold.
12Min/Max flowActivation / pulldownOptionally set minimum and maximum flow rates by selecting type of meter attached.
13Leakage durationActivation / inputOptionally set a threshold after which a leak- age alarm is generated.
14Primary addressActivation / inputOptionally set new primary address.
15Lack of flowActivation / 2 inputsOptionally set a threshold for time and volume after which an alarm is generated in case no flow took place.
16Set data buttonExecute buttonProgram values into module.
Field Description

Port COM
Required to select the correct COM port over which the PC is connected to the M-Bus master unit.
Module No.
The module number is the unique identification number of the module to be addressed. (It is also the secondary address of the module.) In this field the module number of the module to which the parametrisation data shall be sent is put in. The module number is printed on the label on the top of the module, see Figure 7image 5

Baud rate
In this field the actual baud rate of the module is entered. Standard value is 2,400.
Set new baud rate
In this field a new baud rate can be entered if the standard baud rate should be changed. Baud rate can be set to 300 or 2,400 baud.
Set baud
Upon execution baud rate of module will be set to value selected in field 4. Successful baud rate change is con-firmed by a system message.
Refresh COMs
Upon execution the list of COM ports currently recognised by the program will be updated.
Events reset
Upon execution the error log of the module is erased. Fields 8 and 10…16 are optional configuration items. They can be individually activated by setting a tick in the box before the input field and entering a value.

Volume
In this field the actual meter count should be entered to ensure that the meter reading and the value reported over the M-Bus are identical.
When the M-Bus module is installed onto the water meter the reading of the meter is never 0.000: in case of a ret-rofit the meter is likely to have been in operation already. But also in case of a new meter the reading is not zero due to qualification testing which is undertaken on every meter before it is released for shipment. The information in this field ensures that the reading over the M-Bus is identical with the count shown on the meter face. In below example (Figure 8) the reading is 290.35 litres. The input value is “290” as the field is populated with full litres, no decimal places.image 6

Module type
In this field the correct module must be selected by OS-Number. The OS-Number is printed on the label on the top of the module:image 7image 8

Set present time
When this field is active the computer time and date will be transmitted to the module and overwrite the value stored in the module.
Backward flow
When this field is activated a threshold for backward flow can be input in litres and an error message will be generated whenever this threshold is exceeded.

Min/Max flow
When this field is activated the type of meter can be selected in terms of flow. In this case an error message is generated whenever the flow values are outside of the approved meter range. The following values are available. OS-Number “EW110…0600” means all OS-Numbers starting with “EW110” and ending with “0600” are included.image 9

Table 5. Min/Max flow values

Field valueFor OS-NumbersMin flow valueMax flow value
EWA110, Q3=1.6EW110…060010 litres / hour2 m³ / hour
EWA110, Q3=2.5EW110…1100 EW110…1200 EW110…140016 litres / hour3.125 m³ / hour
EWA110, Q3=4EW110…200025 litres / hour5 m³ / hour
EWA110, Q3=6.3EW110…280032 litres / hour7.9 m³ / hour
EWA110, Q3=10EW110…390050 litres / hour12.5 m³ / hour
EWA110, Q3=16EW110…460080 litres / hour20 m³ / hour
EWA171, Q3=25EW1711AC50000.25 m³ / hour31 m³ / hour
EWA171, Q3=40EW1710AC5000 EW1711AC56000.4 m³ / hour50 m³ / hour
EWA171, Q3=63EW1710AC5600 EW1711AC65000,5 m³ / hour78 m³ / hour
EWA171, Q3=100EW1710AC6500 EW1711AC73000.63 m³ / hour125 m³ / hour
EWA171, Q3=160EW1710AC7300 EW1711AC81000.8 m³ / hour200 m³ / hour
EWA171, Q3=250EW1710AC8100 EW1711AC85001.6 m³ / hour313 m³ / hour
EWA171, Q3=400EW1710AC8500 EW1711AC89002 m³ / hour500 m³ / hour
EWA171, Q3=630EW1710AC8900 EW1711AC91005 m³ / hour788 m³ / hour
EWA171, Q3=1 000EW1710AC9100 EW1711AC920010 m³ / hour1,250 m³ / hour
EWA171, Q3=1 600EW1710AC920016 m³ / hour2,000 m³ / hour

NOTE:

  • For EW110 Series min flow of version with dynamic range of R160 is used.
  • For EW171 Series min and max flows of cold water meter are used.

Leakage duration

When this field is activated a threshold for leakage can be input in minutes where the threshold value is ten times the input value. Example: when “6” is input the threshold value will be “60 minutes” (6 x 10). An error message will be generated whenever this threshold is reached or exceeded, i.e. when there has been a continuous flow for sixty minutes or more.

Primary address
When this field is activated a new primary address can be set between 1 and 250. The module is supplied with primary address 0.

Lack of flow
When this field is activated a threshold for no flow can be input and an error message will be generated whenever this threshold is not reached in the given number of days. The threshold is defined in terms of days and total vol-ume. It means that whenever the defined volume is not reached within the number of days defined an error message is generated.

Set data
Upon execution parametrisation data will be written into the module. Successful transmission is confirmed by a system message.

Manufactured for and on behalf of Pittway Sarl, Z.A., La Pièce 4, 1180 Rolle, Switzerland
by its authorised representitive Ademco 1 GmbH

For more information
homecomfort.resideo.com/europe
Ademco 1 GmbH, Hardhofweg 40,
74821 MOSBACH, GERMANY
Phone: +49 6261 810
Fax: +49 6261 81039logo

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals