Baxi 424 Combi 2 - 430 Combi 2 High Efficiency Wall Hung Condensing Gas Boiler User Guide

Baxi 424 Combi 2 - 430 Combi 2 High Efficiency Wall Hung Condensing Gas Boiler User Guide

BAXI-LOGO

BAXI 424 Combi 2 – 430 Combi 2 High Efficiency Wall Hung Condensing Gas Boiler

BAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-PRODUCT

Product Information

The High-efficiency wall-hung condensing gas boiler is a safe and efficient appliance designed for heating purposes. The boiler is available in different models such as 424 Combi 2, 430 Combi 2, 424 Combi LPG 2, and 430 Combi LPG 2. The product comes with a user manual that contains detailed instructions for safe usage and maintenance.
The product is suitable for use by children aged 8 years and above, and by persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge when they have been given supervision or instruction concerning the safe use of the device and understand the resulting risks. Children must not be allowed to play with the appliance. Cleaning and user maintenance must not be carried out by children without supervision.

Product Usage Instructions

Before using the product, please read through the manual carefully and keep it in a safe place for later reference. In order to ensure continued safe and efficient operation, we recommend that the product is serviced regularly. Our service and customer service organization can assist with this.

Accessing USER Parameters

To access USER parameters, follow these steps:

  1. Go to Settings.
  2. Select Access to USER parameters.

List of USER Parameters

The following are the USER parameters:

  • Filling the installation
  • Venting the installation

Maintenance Message

The product comes with a maintenance message that appears when it needs servicing. When you see this message, please contact our service and customer service organization for assistance.

Fault Finding

If you experience any issues with the product, please refer to the Fault Finding section in the manual for assistance.

Decommissioning Procedure

If you need to decommission the product, please follow the procedure outlined in the manual. This includes shutting off the gas supply and disconnecting the electrical supply.

Disposal and Recycling

Please dispose of the product in accordance with local regulations. Contact your local authority for information on recycling options.

Please keep these instructions in a safe place. If you move house, please hand them over to the next occupier.

Dear Customer,
Thank you very much for buying this appliance. Please read through the manual carefully before using the product, and keep it in a safe place for later reference. In order to ensure continued safe and efficient operation we recommend that the product is serviced regularly. Our service and customer service organisation can assist with this.
We hope you enjoy years of problem-free operation with the product

Safety

General safety instructions

This boiler can be used by children aged 8 years and above and by persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge when they have been given supervision or instruction concerning the safe use of the device and understand the resulting risks. Children must not be allowed to play with the appliance. Cleaning and user maintenance must not be carried out by children without supervision.

If you smell gas:

  1. Turn off the gas supply at the meter.
  2. Open windows and doors in the hazardous area.
  3. Do not operate light switches.
  4. Do not operate any electrical equipment.
  5. Do not use a telephone in the hazardous area.
  6. Extinguish any naked flame and do not smoke.
  7. Warn any other occupants and vacate the premises.
  8. Telephone the National Gas Emergency Service on:- 0800 111 999.

Important
If a water or gas leak occurs or is suspected, the boiler can be isolated at the inlet valves by turning their taps through 90° (1/4 turn) downwardsBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (1)

  • A ON
  • B OFF

For advice please contact your Installer, Annual Service Provider or Baxi Customer Support – The Service Division of Baxi. You can contact Baxi Customer Support on telephone number 0344 871 1545.
When contacting Baxi Customer Support it will be useful to have the “Benchmark Checklist ” at the back of the Installation & Service Manual to hand as it includes details relevant to the boiler and installation.

Warning

  • Do not touch flue/chimney pipes. Depending on the settings of the appliance, the temperature of flue/chimney pipes may exceed 60 °C.
  • Do not touch radiators for long periods. Depending on the settings of the appliance, the temperature of radiators may reach 85 °C.
  • Take precautions with domestic hot water. Depending on the settings of the appliance, domestic hot water temperature may reach 65 °C.

Caution
Do not neglect to service the appliance. Contact a qualified professional or take out a maintenance contract for the annual servicing of the appliance.

Recommendations
  • Only qualified professionals are authorised to work on the boiler and the installation.
  • The appliance has an integral frost protection mode as long as there is power to the boiler

Important

  • Regularly check the water pressure in the system (recommended pressure is 1.5 bar).
  • Keep the appliance accessible at all times.
  • Do not remove or cover the user information and serial number labels affixed to the boiler control flap. They must remain legible throughout the lifetime of the boiler

The Benchmark Scheme

Baxi Heating UK Ltd is a licensed member of the Benchmark Scheme which aims to improve the standards of installation and commissioning of domestic heating and hot water systems in the UK and to encourage regular servicing to optimise safety, efficiency and performance. Benchmark is managed and promoted by Heating and Hotwater Industry Council. For more information visit www.centralheating.co.uk

Benchmark Commissioning Checklist

  • Please ensure that the installer has fully completed the Benchmark Checklist on the inside back pages of the installation instructions supplied with the product and that you have signed it to say that you have received a full and clear explanation of its operation. The installer is legally required to complete a commissioning checklist as a means of complying with the appropriate Building Regulations (England and Wales).
  • All installations must be notified, by the installer, to Local Area Building Control either directly or through a Competent Persons Scheme. A Building Regulations Compliance Certificate will then be issued to the customer who should, on receipt, write the Notification Number on the Benchmark Checklist.
  • This product should be serviced annually to optimise its safety, efficiency and performance. The service engineer should complete the relevant section of the Benchmark Service Record in the Installation & Service manual after each service.
  • The completed Benchmark Checklist & proof of annual servicing (where applicable) will be required in the event of any warranty work.
Liabilities

User’s liability

  • To guarantee optimum operation of the system, you must abide by the following instructions:
  • Read and follow the instructions given in the manuals provided with the appliance.
  • Call on a qualified professional to carry out installation and initial commissioning.
  • Get your installer to explain your installation to you.
  • Have the required inspections and maintenance carried out by a qualified installer.
  • Keep the instruction manuals in good condition close to the appliance.

Installer’s liability

  • The installer is responsible for the installation and initial commissioning of the appliance. The installer must observe the following instructions:
  • Read and follow the instructions given in the manuals provided with the appliance.
  • Install the appliance in compliance with prevailing legislation and standards.
  • Carry out initial commissioning and any checks necessary.
  • Explain the installation to the user.
  • If maintenance is necessary, warn the user of the obligation to check the appliance and keep it in good working order.
  • Give all the instruction manuals to the user.

Manufacturer’s liability

  • Our products are manufactured in compliance with the requirements of the various Directives applicable. They are therefore delivered with the marking and any documents necessary. In the interests of the quality of our products, we strive constantly to improve them. We therefore reserve the right to modify the specifications given in this document.
  • Our liability as manufacturer may not be invoked in the following cases:
  • Failure to abide by the instructions on installing and maintaining the appliance.
  • Failure to abide by the instructions on using the appliance.
  • Faulty or insufficient maintenance of the appliance.

About this manual

General

  • Installation, repair and maintenance must only be carried out only by a competent person.
  • All Gas Safe registered engineers carry an ID card with their licence number and a photograph. You can check your engineer is registered by telephoning 0800 408 5500 or online at www.gassaferegister.co.uk
  • This manual is intended for the user of the Baxi 400 Combi 2 boiler. If the appliance is sold or transferred, or if the owner moves leaving the appliance behind you should ensure that the manual is kept with the appliance for consultation by the new owner and their installer.
  • The appliance is designed as a boiler for use in residential domestic environments on a governed meter supply only. The selection of this boiler is entirely at the owner’s risk. If the appliance is used for purposes other than or in excess of these specifications, the manufacturer will not accept any liability for resulting loss, damage or injury.
  • The manufacturer will not accept any liability whatsoever for loss, damage or injury arising as a result of failure to observe the instructions for use, maintenance and installation of the appliance.

Additional documentation

Various timers, external controls, etc. are available as optional extras. Fulldetails are contained in the relevant sales literature

Symbols used

This manual uses various danger levels to draw attention to special instructions. We do this to improve user safety, to prevent problems and to guarantee correct operation of the appliance.

  • Danger
    Risk of dangerous situations that may result in serious personal injury.
  • Danger of electric shock
    Risk of electric shock.
  • Warning
    Risk of dangerous situations that may result in minor personal injury.
  • Caution
    Risk of material damage.
  • Important
    Please note: important information.
  • See
    Reference to other manuals or pages in this manual.

Abbreviations/glossary

  • CH Central heating
  • DHW Domestic hot water
  • PCU PCB for managing burner operation
  • Pnc Condensing output
  • SU Safety PCB

Technical specifications

Homologations

UKCA certificate number748363
NOx class6
Boiler typeC13, C33

Important
All data in these sections are nominal and subject to normal pro duction tolerances.

Technical data

Baxi Combi 2424430424 LPG430 LPG
Gas Council numbers47-077-5147-077-5247-077-5347-077-54
Condensing boilerYesYesYesYes
Low-temperature boiler(1)NoNoNoNo
B1 boilerNoNoNoNo
Cogeneration space heaterNoNoNoNo
Combination heaterYesYesYesYes
Rated heat outputPratedkW20202020
Useful heat output at rated heat output and high temperature setting (2)P4kW20202020
Useful heat output at 30% of rated heat out-put and low temperature setting(1)P1kW6.76.76.76.7
Seasonal space heating energy efficiencyƞs%93939393
Useful efficiency at rated heat output and high temperature setting(2)ƞ4%88.288.088.288
Useful efficiency at 30% of rated heat output and low temperature setting(1)ƞ1%97.997.897.997.8
Auxiliary electricity consumption
Full loadelmaxkW0.0370.0260.0370.026
Partial loadelminkW0.0140.0140.0140.014
Standby modePSBkW0.0040.0040.0040.004
Other items
Heat loss on standbyPstbykW0.040.040.040.04
Ignition burner power consumptionPignkW
Annual energy consumptionQHEGJ62626262
Sound power level, indoorsLWAdB50495049
Nitrogen oxide emissionsNOxmg/kWh24212121
Domestic hot water parameters
Declared load profileXLXLXLXL
Daily electricity consumptionQeleckWh0.1760.1890.1760.189
Annual electricity consumptionAECkWh39423942
Water heating energy efficiencyƞwh%88898889
Daily fuel consumptionQfuelkWh22.0321.6622.0321.66
Annual fuel consumptionAFCGJ17171717
(1)   Low temperature means for condensing boilers 30°C, for low temperature boilers 37°C and for other heaters 50°C return temperature (at heater inlet).

(2)   High temperature setting means 60 °C return temperature at boiler inlet and 80 °C flow temperature at boiler outlet

General

424430424 LPG430 LPG
Rated heat input (Qn) for domestic hot waterkW24.73024.730
Rated heat input (Qn) with domestic hot water tankkW
Rated heat input (Qn) for heatingkW20.620.620.620.6
Reduced heat input (Qn) 80/60 °CkW4.96.04.96
Rated heat output (Pn) for domestic hot waterkW2429.12429.1
Rated heat output (Pn) with domestic hot water tankkW
Rated heat output (Pn) 80/60 °C for heatingkW20202020
Rated heat output (Pn) 50/30 °C for heatingkW21.821.821.821.8
Reduced heat output (Pn) 80/60 °CkW4.85.84.85.8
Reduced heat output (Pn) 50/30 °CkW5.26.35.26.3
Rated efficiency 50/30 °C (Hi)%105.8105.8105.8105.8

Characteristics of the heating circuit

424430424 LPG430 LPG
Maximum pressurebar2.52.52.52.5
Minimum pressurebar0.50.50.50.5
Temperature range for heating circuit°C25 – 8025 – 8025 – 8025 – 80
Water capacity of expansion vessell7777

Characteristics of the domestic water circuit

424430424 LPG430 LPG
Minimum pressurebar0.80.80.80.8
Maximum pressurebar8.08.088
Minimum dynamic pressurebar0.150.150.150.15
Minimum water flowl/min2.02.022
Specific flow (D)l/min11.51411.514
Temperature range for domestic water circuit°C35 – 6035 – 6035 – 6035 – 60
Domestic water production with ΔT = 25 °Cl/min13.816.713.816.7
Domestic water production with ΔT = 35 °Cl/min9.811.99.811.9

Combustion characteristics

424430424 LPG430 LPG
G20 gas consumption (Qmax)m3/h2.613.172.613.17
G20 gas consumption (Qmax) with domestic hot water tankm3/h
G20 gas consumption (Qmin)m3/h0.520.630.520.63
G31 propane gas consumption (Qmax)kg/h1.922.33
G31 propane gas consumption (Qmin)kg/h0.380.47
Diameter of separate discharge pipesmm80/8080/8080/8080/80
Diameter of coaxial discharge pipesmm60/10060/10060/10060/100
Flue gas mass flow rate (max)kg/sec0.0110.0140.0110.014
Flue gas mass flow rate (max) with domestic hot water tankkg/sec
Flue gas mass flow rate (min)kg/sec0.0020.0030.0020.003

Electrical characteristics

424430424 LPG430 LPG
Power supply voltageV230230230230
Power supply frequencyHz50505050
Rated electric powerW90909090
Rated electrical output with domestic hot water tankW

Other characteristics

424430424 LPG430 LPG
Humidity protection rating (EN 60529)IPX5DX5DX5DX5D
Net weight when empty/filled with waterkg28/3029/3128/3029/31
Dimensions (height/width/depth)mm700/395/285700/395/285700/395/285700/395/285
Dimensions and connections/clearancesBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (2)
  1. Safety valve
  2. Heating circuit flow fitting (G3/4”)
  3. Fitting for condensate discharge 4567
  4. DHW (Domestic Hot Water) outlet fitting (G1/2”)
  5. Gas inlet fitting (G3/4”)
  6. Domestic cold water inlet fitting (G1/2”)
  7. Heating circuit return fitting (G34″)
Description of the product

General description

The purpose of this gas-fuelled condensing boiler is to heat water to a temperature that is lower than boiling point at atmospheric pressure. It must be connected to a heating installation and to a domestic hot water distribution system that is compatible with its power and performance ratings. Features of this boiler:

  • Low pollutant emissions,
  • High-efficiency heating,
  • Front control panel with display,
  • Lightweight and compact
Operating principle

Air-gas adjustment
The air is drawn in by the fan and gas injected directly at the height of the venturi. The fan revolution speed is regulated automatically by the electronic board based on the adjustment settings. The gas and air are mixed in the manifold. The gas/air ratio ensures that the quantity of gas and air are adjusted correctly to always obtain optimal combustion. The gas/air mixture is fed into the burner at the front of the exchanger. Here, the electric igniter triggers the mixture with a series of sparks that burn, producing thermal energy.

Combustion
The burner heats the heating water circulating in the heat exchanger. When the temperature of the combustion gas is lower than the dew point (around 55 °C), the water vapour contained in the combustion gas condenses in the flue gas side of the heat exchanger. The heat recovered during this condensation process (the latent heat or condensing heat) is also transferred to the heating water. Once cooled, the combustion gases are discharged through the exhaust pipe. The condensed water is discharged through a siphon.

Heating and domestic hot water production
In boilers used for heating and for producing domestic hot water, an integrated plate heat exchanger heats the domestic water. The heated water is then channelled to the heating installation or to the plate heat exchanger via a three-way valve. A flow sensor detects that a hot water tap has been turned on and communicates this to the PCB, which switches the three-way valve to the hot water position and activates the pump. The three-way valve is spring-loaded and only consumes electricity when switching from one position to another. Precedence is given to a heat request in domestic water mode.

Control panel description

Description of the control panelBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (3)

Knobs

  • BAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (4) HEATING: Using this knob you can modify the flow temperature for the heating installation (heating setpoint 25-80 °C). turn the knob anti-clockwise to reduce the temperature or to the left to scroll through the menus. With an outside sensor connected it is possible to limit the setpoint value; turn the knob clockwise to increase the temperature or to the right to scroll through the menus.
  • BAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (5)DOMESTIC HOT WATER: Using this knob you can modify the domestic hot water temperature (DHW setpoint 35-60 °C) or scroll through the menus to the left and right: turn anti-clockwise to reduce the temperature. turn clockwise to increase the temperature

IconsBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (6)

BAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (7)

  • Chimney sweep mode is enabled (forced full load or low load for CO2 measurement).
  • The burner is on.
  • Display of the system water pressure.
  • DHW operation is enabled.
  • CH operation is enabled.
  • Information menu: read out various current values.
  • User menu: user-level parameters can be configured.
  • Installer menu: installer-level parameter can be configured.
  • Error menu: errors can be read out.
  • Counter menu: various counters can be read out.

Buttons

BAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (8)

  • Back (previous menu)
  • Manual reset
  • Menu
  • Confirms selection or value.
  • Chimney sweep mode: Press the Back and Manual reset keys simultaneously

Accessories & options

Consult the sales catalogue for all available accessories and options.

Operation

Start-up

Procedure for first start-up

The following information appears on the display when the boiler is electrically powered:

  1. The message “INIT”” appears, indicating that the “Initialisation” phase is active (a few seconds);
  2. The software version “Vxx.xx.” appears (two seconds);
  3. The software version for boiler settings “Pxx.xx.” appears (two seconds);
  4. The boiler and heating installation venting phase has started. During operation, the display shows in alternate mode “– – – – – – – –”, the word “DEAIR” and the pressure value for the heating circuit. This phase lasts 6 minutes and 20 seconds, at the end the boiler is ready for operation;
  5. TheBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (9) symbol and the “x.x” installation water pressure value appear.
  6. In the event of a power outage the procedure will be repeated from the beginning.
  7. To activate a heating request, the room thermostat must be set to a temperature above the current temperature (or open a domestic water tap.)

Changing the heating flow temperatureBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (10)

  1. Use the knobBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (4) to adjust the flow temperature in heating mode.
    1. Turn the knob anti-clockwise to reduce the temperature value.
    2. Turn the knob clockwise to increase the temperature value.
      Important
      With an outside sensor connected it is possible to lower the setpoint value.
  2. Press the F4 key to confirm the value or wait a few seconds until the value is automatically saved.

Important
The flow temperature on the display automatically matches the temperature set when using a:

  • Weather-dependent regulator.
  • OpenTherm regulator

Changing the domestic hot water (DHW) temperatureBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (10)

  1. Use theBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (5) knob to adjust the domestic hot water temperature.
    1. Turn the knob anti-clockwise to reduce the temperature value.
    2. Turn the knob clockwise to increase the temperature value.
  2. Press the F4 key to confirm the value or wait a few seconds until the value is automatically saved
Shutdown

Switching off the heating and domestic hot water (DHW)

Heating mode can also be disabled by turning the until the word OFF appears on the display.

  • Important
    • When heating mode is re-enabled check, by turning theBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (4) knob, that the comfort temperature is that requested.
  • Important
    • Heating is disabled but the frost protection function remains activated.
    • Domestic hot water mode can also be disabled by turning theBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (5) knob anti-clockwise until the word OFF appears on the display.
    • To switch the boiler off completely, switch off the power supply to the appliance and close the gas cock.
  • Important
    • In this condition, the boiler and the heating installation are not protected against frost.

Frost protection

It is a good idea to prevent the heating installation from draining completely, as changing the water can result in unnecessary and damaging limescale deposits from forming inside the boiler and heating elements. If the thermal installation is not intended to be used during the winter months and there is a risk of frost, we recommend mixing suitable antifreeze solutions designed for a specific purpose (e.g. propylene glycol,which contains limescale and corrosion inhibitors) into the water in the installation. The boiler’s electronic control system is equipped with an “antifreeze” function for the heating system. This function activates the boiler pump when the heating system flow temperature falls below 7 °C. If the water temperature reaches 4 °C, the burner is switched on, bringing the system water to a temperature of 10 °C. When this value is reached the burner switches off and the pump continues to operate for another 3 minutes.

Important
The frost protection function will not work if there is no power being supplied to the boiler or if the gas supply cock is closed.

Settings

Access to USER parametersBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (12)

To display/modify the list of USER parameters, proceed as follows:

  1. press the BAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (13) keys simultaneously, the symbol BAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (14)on the menustarts to flash;
  2. turn theBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (5) Eknob until theBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (15) appears. Press theBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (16)key to confirm;
  3. turn the Fknob until you reach the required setting. Press the BAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (16) key to confirm;
  4. modify the value of the parameter usingBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (5) knob;
  5. the Press theBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (16)key to confirm;
  6. Press the BAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (16)key to exit.

List of USER parameters

NameDescriptionFactory valueMini­ mumMaxi­ mumLevel
AP016CH operation 0: Off

1: On

1User
AP017Domestic hot water (DHW) 0: Off

1: On

1User
AP073Average external temperature [°C] when switching from summer/ winter mode (with outside sensor)221030User
AP074Force summer mode (with outside sensor) 0: Auto according to AP073

1: Summer

0User
 

DP004

Anti-legionella function 0: Disabled

1: Weekly

2: Daily (only available with Room Unit)

 

0

 

 

 

User

DP070Domestic hot water temperature setpoint.

In the case of operation with a calorifier tank and programming via room unit corresponding to the comfort setpoint [°C]

603560User
 

DP200

DHW mode:

0: Domestic hot water programming (only available with Room Unit) 1: Manual (boiler with calorifier tank) – Preheating active (instanta­ neous boiler)

2: Antifreeze (boiler with calorifier tank) – No preheating (instantane­ ous boiler)

 

2

 

 

 

User

NameDescriptionFactory valueMini­ mumMaxi­ mumLevel
CP060Required ambient temperature (°C) in the zone in the holiday/anti­ freeze period6520User
CP070Maximum ambient setpoint temperature (°C) in reduced mode that enables switching to comfort mode with climate control (with outside sensor)16530User
CP080Temperature (°C) set by SLEEP activity in the zone16530User
CP081Temperature (°C) set by HOME activity in the zone20530User
CP082Temperature (°C) set by AWAY activity in the zone6530User
CP083Temperature (°C) set by MORNING activity in the zone21530User
CP084Temperature (°C) set by EVENING activity in the zone22530User
CP085Temperature (°C) set by CUSTOM activity in the zone20530User
CP200Required ambient temperature (°C) for the zone in manual mode20530User
CP250Correct the temperature measured by the room unit0-5+5User
 

CP320

Zone operating mode 0: Scheduling

1: Manual

2: Off

 

0

 

 

 

User

CP510Temporary room setpoint per zone20530User
CP550Fireplace mode 0: Disabled

1: Enabled

0User
 

CP570

Timer programme selected by User 0: Program 1

1: Program 2

2: Program 3

 

0

 

 

 

User

 

DP060

Timer programme selected for DHW 0: Program 1

1: Program 2

2: Program 3

 

0

 

 

 

User

DP080Reduced temperature setpoint for the domestic hot water tank [°C]351060User
DP337Domestic hot water temperature setpoint for the holiday period [°C]101060User

Important
The factory values of some parameters may differ according to the target market of the product

Maintenance

General

The boiler does not require any special maintenance. However, the boiler must be serviced annually in accordance with the Installation and Service
Manual and the relevant section of the Benchmark Service Record completed in order to maintain the warranty.

Note
Taking out a maintenance contract is recommended.

Caution
Maintenance operations must be performed by a qualified competent person.

Use only BAXI genuine spare parts.
The painted panels should be wiped with a damp cloth and then dried completely. DO NOT USE ABRASIVE CLEANING AGENTS.

Maintenance instructions

To ensure continued safety, functionality and efficiency, the boiler must be inspected annually by the installer/service engineer in order to ensure the performance of the product constant over time, we recommend having the boiler’s energy efficiency checked annually by a qualified technician. Accurate maintenance is always a reason for safety and savings in the management of the system.
Periodically check that the pressure shown on the display with the system cold is between 1 – 1.5 bar. If it is lower, act on the system filling tap. It is advisable that the opening of this tap is carried out very slowly in order to facilitate degassing.

Important
The boiler is equipped with a hydraulic pressure switch which does not allow the boiler to operate in case of low pressure. If frequent pressure drops should occur, call the installer/ service engineer

Filling the installationBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (17)

  • If the water pressure is too low, the system must be re-pressurized.
  • The normal operating water pressure is between 1 and 2 bar. If the pressure exceeds 3 bar the safety pressure valve will operate and a fault is indicated.
  • Ensure that the temporary filling loop is disconnected. Contact your installer.
  • It may be necessary to repressurize the system occasionally (when the water pressure falls below 0.7). A filling device (the filling loop) will be fitted on the system. This will be on the boiler itself, or on pipework near to the boiler. Seek advice from your installer.

Note
If the water pressure requires regular re-pressurising a fault or leak is indicated. Seek advice from your installer.

Filling loopBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (18)

  1. Fully open one of the taps first, and then while watching the pressure gauge, carefully open the second tap.
    Note
    The system pressure is shown at all times on the display when there is power to the boiler.
  2. When the figures on the display indicate between 1 and 1.5 bar turn both taps off.
  3. Disconnect the filling pipe from the taps (a small amount of water may be present) and remove it. Keep the pipe in a safe place for future use.
  4. If blanking caps are available fit them to the taps.
    Note
    Go to the “How to videos” section of the “Advice” page at www.baxi.co.uk for further details.
  5. When the correct pressure is restored the boiler will reset automatically.

Venting the installation

It is essential to eliminate any air in the boiler, pipes or fittings because this can cause irritating noise during heating or the intake of water. To do this, proceed as follows:BAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (19)

  1. Open the valves (A & B) of all the radiators connected to the central heating system.
  2. Set the ambient thermostat as high as possible.
  3. Wait for the radiators to heat up.
  4. Set the ambient thermostat as low as possible.
  5. Wait about 10 minutes until the radiators have cooled down.
  6. Vent the radiators. Start with the lower floors.
  7. Open the vent valve (C & C1) holding a cloth (D) against the valve.
  8. Wait until water comes out of the vent valve and then tighten it again.
  9. After venting, check that the system is still at sufficient pressure

Important
Take care as the water might still be hot.
Important
If the hydraulic pressure of the water in the central heating system is below 0.8 bar, it is advised to increase the pressure (the recommended hydraulic pressure is 1.0 – 1.5 bar).

Maintenance messageBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (20)

  1. The purpose of this function is to warn the user that the boiler requires maintenance
  2. When the letters SVC appear on the screen and the symbolBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (21) flashes, the boiler requires maintenance. Contact your installer.

Troubleshooting

Temporary and permanent faults

The codes on the display indicate two types of fault: volatile and permanent. The first item shown on the display is a letter followed by a two-digit number. The letter indicates the type of fault: temporary (H) or permanent (E). The number indicates the group in which the fault that has occurred is classified according to its impact on safe and reliable operation. The second item shown flashes alternately with the first and consists of a two-digit number that indicates the type of fault which has occurred (see the following fault tables).

TEMPORARY FAULT (A/H.x.x.)

  • A temporary fault is shown on the display by the letter “A” or “H” followed by a number (group). A temporary fault is a type of fault that does not cause a permanent stoppage of the boiler. It has the following characteristics:
  • A: The appliance continues to operate. It disappears as soon as the cause has been resolved.
  • H: Disappears when the error condition is removed, in some cases even after 10 minutes. PERMANENT FAULT (E.x.x)
  • A permanent fault is shown on the display by the letter “E” followed by a number (group). Press the RESET button for one second. If faults are shown frequently, contact our authorised technical assistance centre.
  • E: Stoppage, reset required..
Error codes

Tab.11 List of temporary faults

DISPLAY 

DESCRIPTION OF TEMPORARY FAULTS

CAUSE – Check/Solution

An installer is required for most checks and solu­ tions.

Group codeSpecific code
H.00.42Pressure sensor open/faultySENSOR/CONNECTION PROBLEM

Check the operation of the pressure sensor Check the sensor/PCB connection

H.01.00Temporary communication failure in the PCBThe error is resolved automatically
 

 

H.01

 

 

.05

 

 

Maximum temperature difference value between flow and return reached.

INSUFFICIENT CIRCULATION

Check the boiler/installation circulation Activate a manual venting cycle Check the installation pressure OTHER CAUSES

Check the cleanliness of the exchanger

Check the operation of the temperature sensors Check the temperature sensor connection

 

 

H.01

 

 

.08

 

 

Flow temperature increase in heating mode too quick.

INSUFFICIENT CIRCULATION

Check the boiler/installation circulation Activate a manual venting cycle Check the installation pressure

Check the operation of the pump OTHER CAUSES

Check the cleanliness of the exchanger

Check the operation of the temperature sensors Check the temperature sensor connection

H.01.14Maximum flow or return temperature value reached.INSUFFICIENT CIRCULATION

Check the boiler/installation circulation Activate a manual venting cycle

DISPLAY 

DESCRIPTION OF TEMPORARY FAULTS

CAUSE – Check/Solution

An installer is required for most checks and solu­ tions.

Group codeSpecific code
 

 

H.01

 

 

.18

 

 

No water circulation (temporary).

INSUFFICIENT CIRCULATION

Check the installation pressure Activate a manual venting cycle Check the operation of the pump Check the boiler/installation circulation TEMPERATURE SENSOR ERROR

Check the operation of the temperature sensors Check the temperature sensor connection

 

 

H.01

 

 

.21

 

 

Flow temperature increase during domestic hot water operation too fast.

INSUFFICIENT CIRCULATION

Check the installation pressure Activate a manual venting cycle Check the operation of the pump Check the boiler/installation circulation TEMPERATURE SENSOR ERROR

Check the operation of the temperature sensors Check the connection of the temperature sensors

H.02.00Reset in progress.It resolves itself
H.02.02Waiting for configuration settings to be entered (CN1,CN2).CN1/CN2 CONFIGURATION MISSING

Configure CN1/CN2

H.02.03Configuration settings (CN1,CN2) not entered correc­ tly.Check configuration CN1/CN2 Configure CN1/CN2 correctly
H.02.04PCB settings cannot be read.MAIN PCB ERROR

Configure CN1/CN2 Replace the main PCB

H.02.05Setting memory not compatible with the boiler PCB ty­ pe.Contact the Service Network
H.02.07Low pressure in heating circuit (water filling required).Check the installation pressure and restore Check the expansion vessel pressure Check for boiler/installation leaks
H.02.09Partial stoppage of the boiler (antifreeze function acti­ ve)SIGNAL INDICATING BLOCKING INPUT

Contact X15 open, check connected devices Parameter configuration error: Check AP001

H.02.10Total stoppage of the boiler (antifreeze function not active)SIGNAL INDICATING BLOCKING INPUT

Contact X15 open, check connected devices Parameter configuration error: Check AP001

H.02.70External unit heat recovery test failedPCB accessory error SCB-09

Check the device connected to contact X9

H.03.00No identification data for boiler safety device.MAIN PCB ERROR

Contact the Service Network

 

 

H.03

 

 

.02

 

 

Temporary flame loss

ELECTRODE PROBLEM

Check the electrode connection and wiring Check the condition of the electrode

GAS SUPPLY

Check the gas supply pressure Check the gas valve calibration FLUE GAS PIPES

Check the pipes and the terminal

H.03.05Power supply voltage too lowCheck the mains voltage
 

 

 

H.03

 

 

 

.54

 

 

Temporary flame loss

Shutdown due to the power supply voltage being too low

ELECTRODE PROBLEM

Check the electrode electrical connections Check the condition of the electrode

GAS SUPPLY

Check the gas inlet pressure Check the gas valve calibration FLUE GAS EXHAUST PIPE

Check the air intake and flue gas exhaust termi­ nal

Check the power supply voltage

DISPLAY 

DESCRIPTION OF PERMANENT FAULTS (RESET)

CAUSE – Check/Solution

An installer is required for most checks and solu­ tions.

Group codeSpecific code
E.00.04Return temperature sensor disconnectedSENSOR/CONNECTION PROBLEM

Check the operation of the temperature sensor Check the sensor/PCB connection

E.00.05Return temperature sensor short circuitedSENSOR/CONNECTION PROBLEM

Check the operation of the sensor Check the sensor/PCB connection

 

E.00

 

.16

 

DHW tank temperature sensor not connected

SENSOR OPEN

Check the operation of the sensor Check the sensor/PCB connection

When removing a domestic hot water tank, set parameter DP150=1

E.00.17DHW tank temperature sensor short-circuitedSENSOR CLOSED

Check the operation of the sensor Check the sensor/PCB connection

E.00.20The flue gas temperature sensor is not connected or measured a temperature below the rangeSENSOR OPEN

Check the operation of the sensor Check the sensor/PCB connection

E.00.21The flue gas temperature sensor has short-circuited or measured a temperature above the rangeSENSOR CLOSED

Check the operation of the sensor Check the sensor/PCB connection

 

 

 

E.01

 

 

 

.04

 

 

 

Flame loss detected five times in 24 hours

GAS SUPPLY

Check the gas supply pressure Check the gas valve calibration ELECTRODE PROBLEM

Check the electrode connection and wiring Check the condition of the electrode

FLUE GAS PIPES

Check the air intake and flue gas exhaust pipes EXCHANGER ON FLUE GAS SIDE BLOCKED

Check the cleanliness of the exchanger MAINS VOLTAGE

Check the power supply voltage

 

E.01

 

.12

 

Temperature measured by return sensor greater than flow temperature

SENSOR/CONNECTION PROBLEM

Check that the sensors are positioned the correct way around

Check that the flow sensor is in the correct posi­ tion Check the return temperature in the boiler Check the operation of the sensors

 

 

E.01

 

 

.17

 

 

No water circulation (permanent)

INSUFFICIENT CIRCULATION

Check the installation pressure Activate a manual venting cycle Check the operation of the pump Check the boiler/installation circulation SENSOR ERROR

Check the operation of the temperature sensors Check the temperature sensor connection

E.01.20Maximum flue gas temperature reachedEXCHANGER ON FLUE GAS SIDE BLOCKED

Check the cleanliness of the exchanger

 

E.02

 

.13

 

Total stoppage of the boiler (antifreeze function not active)

SIGNAL INDICATING BLOCKING INPUT

Contact X15 open, check connected devices Parameter configuration error: Check setting AP001

E.02.17Permanent communication failure in the PCBMAIN PCB ERROR

Check for any electromagnetic interference Contact the Service Network

DISPLAY 

DESCRIPTION OF PERMANENT FAULTS (RESET)

CAUSE – Check/Solution

An installer is required for most checks and solu­ tions.

Group codeSpecific code
E.02.35Critical safety device disconnectedCOMMUNICATION FAULT

Start the auto-detect function (parameter AD) Check the devices connected to contact X9

E.02.39Minimum pressure not reached after 6 minutes of au­ tomatic fillingAUTOMATIC FILLING ERROR

Check automatic filling is working

 

E.02

 

.47

 

Connection to external device unsuccessful

ELECTRICAL CONNECTION ERROR

Start the auto-detect function (parameter AD)) Check the electrical connections of external devi­ ces.

E.04.01Flow temperature sensor short circuitedSENSOR/CONNECTION PROBLEM

Check the sensor/PCB connection Check the operation of the sensor

E.04.02Flow temperature sensor disconnectedSENSOR/CONNECTION PROBLEM

Check the sensor/PCB connection Check the operation of the sensor

 

E.04

 

.03

 

Maximum flow temperature exceeded or flow tempe­ rature sensor short circuited

INSUFFICIENT CIRCULATION

Check the boiler/installation circulation Activate a manual venting cycle Check the operation of the sensors

 

 

E.04

 

 

.08

 

 

Maximum safe temperature value reached

INSUFFICIENT CIRCULATION

Check the pressure in the installation Switch on the manual degassing function Check that the pump is working

Check the circulation in the boiler/installation OTHER POSSIBLE CAUSES

Check the safety thermostat connection

Check that the safety thermostat is working cor­ rectly

 

 

 

E.04

 

 

 

.10

 

 

 

Burner failed to ignite after 4 attempts

GAS SUPPLY

Check the gas supply pressure

Check the gas valve electrical connection Check the gas valve calibration

Check the operation of the gas valve ELECTRODE PROBLEM

Check the electrode electrical connections Check the electrode condition

OTHER CAUSES

Check the operation of the fan

Check the condition of the flue gas exhaust (bloc­ kages)

E.04.12Ignition failure for monitoring parasitic flameCheck the ground circuit

Check the power supply voltage Check the electrode conditions

E.04.13Fan blade blocked or maximum rpm exceededFAN/PCB PROBLEM

Check the PCB-fan connection Check the fan operation

E.04.17Fault in gas valve control circuitMAIN PCB ERROR

Check the electrical connections for the gas valve

E.04.18The flow temperature is below the minimum tempera­ ture or the flow temperature sensor is not connectedSENSOR/CONNECTION PROBLEM

Check the sensor/PCB connection Check the operation of the sensor

E.04.23Communication internal stoppageSwitch the power supply off and on again and then RESET
E.04.29Communication internal stoppageSwitch the power supply off and on again and then RESET
E.04.254Fault in gas valve control circuitMAIN PCB ERROR

Check the electrical connections

DISPLAYDESCRIPTION OF WARNINGS BEFORE A FAULT IS DETECTED 

CAUSE – Check/Solution

Group codeSpecific code
A.00.28Solar temperature sensor is either removed or measures a temperature below rangeCheck the solar temperature sensor wiring. Re­ place the sensor if necessary. In case of removal of the solar tank, set the parameter DP150=1.
A.00.29Solar temperature sensor is either shorted or measures a temperature above rangeCheck the solar temperature sensor wiring. Re­ place the sensor if necessary.
 

A.00

 

.34

 

Outdoor temperature sensor expected but not detec­ ted

OUTDOOR SENSOR NOT DETECTED

Enter the correct value of the parameter AP091 Connect the outdoor sensor

Outdoor sensor is not connected correctly

 

A.02

 

.06

 

Low pressure in heating circuit

Check the installation pressure and restore Check the expansion vessel pressure Check for boiler/installation leaks
A.02.36Functional device disconnectedCOMMUNICATION FAULT

Start the auto-detect function (parameter AD) Check the devices connected to contact X9

A.02.37Passive functional device disconnectedCOMMUNICATION FAULT

Start the auto-detect function (parameter AD) Check the devices connected to contact X9

A.02.45Connection errorCOMMUNICATION FAULT

Start the auto-detect function (parameter AD))

A.02.46Device priority errorCOMMUNICATION FAULT

Start the auto-detect function (parameter AD))

A.02.48Unit function configuration errorELECTRICAL CONNECTION ERROR

Start the auto-detect function (parameter AD)) Check electrical connections of external devices

A.02.49Failed node initialisationELECTRICAL CONNECTION ERROR

Start the auto-detect function (parameter AD)) Check electrical connections of external devices

A.02.54Open Therm bus power supply errorCheck the devices connected to contact X17 – Terminal board M2 (7-8)
A.02.55Incorrect or missing serial numberContact the Service Network
A.02.76Internal memory reserved for full customisation of set­ tings.

No further changes can be made

Contact the Service Network

Important
When connecting a Room Unit/Control Unit to the boiler, the code “254” is always shown in the event of a fault.. Read the fault code shown on the boiler display.

Fault finding

Tab.14 Problems and solutions

ProblemPossible causesSolution
 

 

There is no domestic hot wa­ ter.

 

The boiler is not working.

Check that the boiler is being supplied with power. Check fuses and the switches.

Check whether the gas isolation cock is properly open.

If the property has a prepayment meter ensure it has sufficient credit.

The DHW function is switched off.Activate the DHW mode.
The water pressure is too low (< 0.5 bar).Re-pressurise the system.
Insufficient flow.Flow must be at least 2 litres per minute.
 

 

 

 

The radiators are cold.

The temperature set point for the heating is too low.Increase the value with the CH temperature knob or if a room thermostat is connected, increase the temperature on the room thermostat.
The heating mode is deactivated.Activate the heating mode.
The radiator valves are not open.Open the valves of all radiators connected to the system.
The boiler is not working.Check that the boiler is being supplied with power. Check fuses and switches.

Check whether the gas isolation cock is properly open.

If the property has a prepayment meter ensure it has sufficient credit.

The water pressure is too low (< 0.5 bar).Re-pressurise the system.
 

 

 

 

 

The boiler is not working.

The temperature set point for the heating is too low.Increase the value with the CH temperature knob or if a room thermostat is connected, increase the temperature on the room thermostat.
No demand for heating.Ensure that timers & thermostats are calling for heat.
No power supply.Check that the boiler is being supplied with power. Check the fuses and switches.
The water pressure is too low (< 0.5 bar).Re-pressurise the system.
The boiler is indicating an error.Press the Reset button. Correct the error, if possible.
The gas pressure is too low.Check whether the gas isolation cock is fully open. Open the gas isolation cock.
Condensate drain blocked.Check drain, especially any external runs in freez­ ing temperatures.

If the boiler is not working also check section “Operation checking procedure and basic fault identification” or contact your Installer.

Decommissioning

Decommissioning procedure

Caution
Only qualified persons are authorised to work on the appliance and system to decommission.
If your boiler needs to be decommissioned either temporarily or permanently the following should be performed:

  • Switch off the boiler’s electrical connection.
  • Close the gas isolation tap.
  • Drain the central heating system. Seek the advice of your installer

Disposal

Disposal and recycling

The appliance is composed of multiple components made from various different materials, such as steel, copper, plastic, fibreglass, aluminium, rubber, etc..
These materials may be highly pollutant. This means that the boiler must be disposed of correctly by contacting staff at the nominated disposal facility or by taking it to a centre that is authorised to dispose of bulky waste (domestic appliances).

Warning
Removal and disposal of the boiler must be carried out by a qualified installer in accordance with local and national regulations.

Environmental

Energy saving

Tips on saving energy:

  • Do not cover radiators. Do not hang curtains in front of radiators.
  • Install reflective panels behind the radiators to prevent heat loss.
  • Insulate the pipes in rooms that are not heated (cellars and lofts).
  • Install loft insulation & double glazing.
  • Use draught excluders where necessary.
  • Upgrade any older boiler external controls.
  • Turn down room thermostats by 1°.
  • Turn off radiators in rooms not in use.
  • Do not run hot (or cold) water pointlessly.
  • Fit a water-saving shower head to save up to 40 % energy.
  • Take showers rather than baths. A bath consumes twice as much water and energy.

Room thermostats and settings

Various models of room thermostat are available. The thermostat type and setting affect the total energy consumption.

A few tips:

  • A modulating thermostat in combination with thermostatic radiator valves saves energy and offers considerable comfort. This combination gives you flexibility with the temperatures. Do not fit thermostatic radiator valves in the room in which the room thermostat is installed.
  • Completely closing and opening thermostatic valve radiators causes undesirable temperature fluctuations. Open and close thermostatic valves in small steps.
  • Lower the thermostat to around 20°C. This reduces heating costs and energy consumption.
  • Lower the room thermostat temperature temporarily if opening windows to air the rooms.
  • If you are using an ON/OFF type thermostat, reduce the water temperature value in summer (e.g. 60°C in summer and 80°C in winter).
  • When setting an hourly programmable thermostat, consider days when you are absent or on holiday. Electricity production and energy savings reach their optimum level with a programmed and activated timer programme.

Warranty

General

To make sure your boiler warranty is activated and maintained, it is essential that the:

  1. Benchmark checklist is completed by your installer
  2. Warranty is registered within 30 days
  3. Boiler has an annual service

Important
Please note that failure to adhere to terms and conditions will invalidate your warranty

Standard warranty terms and conditions

Warranty registration, service & repair

For full terms and conditions, visit www.baxi.co.uk/terms.

Benchmark checklist

The Benchmark Checklist will be completed by your installer and records that the boiler has been installed and commissioned correctly. It can be found at the back of the installation and service manual and should be kept in a safe place for the life of the boiler. We will check that the Benchmark Checklist has been completed on an in-warranty visit.

Ways to register your warranty

If your boiler is eligible for an extended warranty, your installer may register the product on your behalf and provide you with the relevant documentation. Please check with your installer.
Should this not be the case, you can register your warranty online at www.baxi.co.uk/registration

Annual service
A service must be completed every 12 months from the date of installation to maintain your warranty.

This service must be completed by one of the following:

  • A Gas Safe registered installer/engineer
  • Baxi Customer Support; call us 0344 871 1545

Please make sure that your engineer has logged the service information at the back of the installation and service manual. You will be asked for your service history on any in-warranty repair visit.

If you experience a problem with your boiler

For any in or out of warranty repair, Baxi Customer Support is on hand to help you. Call our award-winning team to arrange for one of our nationwide team of Gas Safe registered engineers to visit.
If your product is in warranty, everything is free of charge, subject to our warranty terms and conditions. If it is out of warranty, we can still help and offer a range of options you can choose from to suit your needs.

Contact Baxi Customer Support 0344 871 1545

  • Opening hours
  • Monday – Friday, 8.00am – 6.00pm
  • Weekends and Bank Holidays, 8.30am – 2.00pm
  • Please note calls may be recorded for training and monitoring purposes.

When contacting Baxi Customer Support, please have the following information to hand:

  • Boiler serial number.
  • Proof of purchase if you do not have the boiler serial number

Please note that for in-warranty repairs, our engineers will ask to see your service history record, completed Benchmark Checklist and details of your installer. These can all be found in the Installation and Service manual

Appendix

Product fiche – Combination boilers

424430424 LPG430 LPG
Space heating – Temperature applicationMediumMediumMediumMedium
Water heating – Declared load profileXLXLXLXL
Seasonal space heating energy efficiency classBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (22)BAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (22)BAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (22)BAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (22)
Water heating energy efficiency classBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (22)BAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (22)BAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (22)BAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (22)
Rated heat output (Prated or Psup)kW20202020
Space heating – Annual energy consumptionGJ62626262
Water heating – Annual energy consumptionkWh(1)

GJ(2)

39

17

42

17

39

17

42

17

Seasonal space heating energy efficiency%93939393
Water heating energy efficiency%88898889
Sound power level LWA indoorsdB50495049
(1)   Electricity

(2)   Fuel

See
For specific precautions about assembling, installing and maintaining: Safety, page 5

Package fiche – boilers

Package fiche for boilers indicating the space heating energy efficiency of the packageBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (23)BAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (24)

The energy efficiency of the package of products provided for in this fiche may not correspond to its actual energy efficiency once installed in a building, as this efficiency is influenced by further factors such as heat loss in the distribution system and the dimensioning of the products in relation to building size and characteristics

  1. The value of the seasonal space heating energy efficiency of the preferential space heater, expressed in %.
  2. The factor for weighting the heat output of preferential and supplementary heaters of a package as set out in the following table.
  3. The value of the mathematical expression: 294/(11 · Prated), whereby ‘Prated’ is related to the preferential space heater.
  4. The value of the mathematical expression 115/(11 · Prated), whereby ‘Prated’ is related to the preferential space heater

Weighting of boilers

Psup / (Prated + Psup)(1)(2)II, package without hot water storage tankII, package with hot water storage tank
000
0.10.30.37
0.20.550.70
0.30.750.85
0.40.850.94
0.50.950.98
0.60.981.00
≥ 0.71.001.00
(1)   The intermediate values are calculated by linear interpolation between the two adjacent values.

(2)   Prated is related to the preferential space heater or combination heater.

Package efficiency

Baxi Combi424430424 LPG430 LPG
Temperature control X%
Temperature control Y%

Package fiche – Combination heaters (boilers or heat pumps)

Package fiche for combination heaters (boilers or heat pumps) indicating the water heating energy efficiency of thepackageBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (25)BAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (26)

The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed in a building, as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the products in relation to building size and characteristics

  1. The value of the water heating energy efficiency of the combination heater, expressed in %.
  2. The value of the mathematical expression (220 · Qref)/Qnonsol, where Qref is taken from Regulation EU 811/2013, Annex VII Table 15 and Qnonsol from the product fiche of the solar device for the declared load profile M, L, XL or XXL of the combination heater.
  3. The value of the mathematical expression (Qaux · 2,5)/(220 · Qref), expressed in %, where Qaux is taken from the product fiche of the solar device and Qref from Regulation EU 811/2013, Annex VII Table 15 for the declared load profile M, L, XL or XXL.

Copyright
All technical and technological information contained in these technical instructions, as well as any drawings and technical descriptions supplied, remain our property and shall not be multiplied without our prior consent in writing. Subject to alterations.

Baxi Customer Support

  • 0344 871 1545
  • Opening hours
  • Monday – Friday, 8.00 am-6.00 pm
  • Weekends and Bank Holidays, 8.30 am-2.00 pm
  • Please note calls may be recorded for training and monitoring purposes

baxi.co.uk
Register now to activate your warranty:
www.baxi.co.uk/registration

For the warranty to be maintained, please make sure…

  • Benchmark checklist is completed
  • Warranty is registered within 30 days
  • The boiler has an annual service

For full terms and conditions, visit www.baxi.co.uk/terms. Failure to adhere to terms and conditions will void your manufacturer’s warrantyBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (27)

Baxi Brooks House, Coventry Road, Warwick, CV34 4LLBAXI 424-Combi 2 - 430-Combi-2-High-Efficiency-Wall-Hung-Condensing-Gas-Boiler-FIG- (28)
Please ensure the boiler is installed in accordance with these installation instructions and that you adhere to the Building Regulations.
e&oe
All descriptions and illustrations provided in this document have been carefully prepared but we reserve the right to make changes and improvements in our products which may affect the accuracy of the information contained in this leaflet. All goods are sold subject to our standard Conditions of Sale which are available on request.

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals