Neptronic At000 2-way 1-2 Inch Globe Valve Instruction Manual

Neptronic At000 2-way 1-2 Inch Globe Valve Instruction Manual

neptronic LogoAT000 2-Way 1-2 Inch Globe Valve
Instruction Manual
neptronic AT000 2 Way 1 2 Inch Globe Valve

AT000/AT020/AT060/AT080

Feature:

  • Variable running time.
  • Manuel override.
  • Maintenance free.
  • Fail safe by Enerdrive System¹
    (on models 060 & 080).
  • Auxiliary switches.
    (on models 020 & 080).
Technical DataAT000AT020AT060AT080
Auxiliary switchesNoYes(2)NoYes(2)
FeedbackNoNoNoNo
Fail safe – EnerdriveNoYes
Power consumption6 VA20VA Peak. 6VA
Control signal3 wire / 2 position.
3 wire / 3 point floating
2 wire / 2 position.
4 wire / 3 point floating
Running time60 sec force dependant
Force100 lb. [450 N] at rated voltage
Power supply22 to 26 VAC or 28 to 32 VDC
Electrical connection18 AWG [0.8 mm²] minimum
Inlet bushing2 inlet bushing of 5/8 in [15.9 mm] & 7/8 in [22.2 mm]
Maximum Stroke0.5 in [12.7mm]
DirectionReversible. normally open or normally close (factory set with normally close direction)
Ambient temperature0°F to +122°F [-18°C to +50°C]
Storage temperature-22°F to +122°F [-30°C to +50°C]
Relative Humidity5 to 95 % non condensing.
Weight2 lbs. [0.9 kg]
Warning: Do not use automatic screw driver on manual override

Dimensions

neptronic AT000 2 Way 1 2 Inch Globe Valve - Figure 1

DimensionInchesMetric (mm)
A5.93150.6
B4.8121.9
C3.691.4

Caution
We strongly recommend that all neptronic® products be wired to a separate transformer and that transformer shall service only neptronic® products. This precaution will prevent interference with, and/or possible damage to incompatible equipment.
When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance.

¹ Enerdrive Fail-Safe System: US Patent #5,278,454
European Patent #0647366neptronic AT000 2 Way 1 2 Inch Globe Valve - Icon 1

Mechanical installation

Mounting of the actuator on valveneptronic AT000 2 Way 1 2 Inch Globe Valve - Figure 2

  1. Screw completely the valve shaft (C) unto the coupling of the actuator (A).
  2. Unscrew the coupling (A) for ½ of turn in order to leave a functional play.
  3. Screw the counter nut (B).

Warning:
Do not over tight coupling of the actuator on the shaft of the valve.
Mounting of the actuated valve on systemneptronic AT000 2 Way 1 2 Inch Globe Valve - Figure 3

  1. Pay attention to system particularity; be sure that the expansions, contractions of the system and its medium as well as operating pressures are within the tolerances.
  2. When plumbing, the motorized valve should be situated in an easily accessible place and sufficient space should be allowed for the removal of the actuator.
  3. To prevent moisture from collecting in the motor casing,install the motorized valve such that the actuator is superior to the valve, at 20-30º / at vertical. Avoid mounting the valve so that the valve stem is below horizontal.

Wiring Diagrams

Models AT000 & 020
3 wire/2 position (ON-OFF)neptronic AT000 2 Way 1 2 Inch Globe Valve - Figure 43 wire/3 point floating neptronic AT000 2 Way 1 2 Inch Globe Valve - Figure 6

Models AT060 & 080
2 wire/2 position (ON-OFF)neptronic AT000 2 Way 1 2 Inch Globe Valve - Figure 54 wire/3 point floatingneptronic AT000 2 Way 1 2 Inch Globe Valve - Figure 7PC Board 

neptronic AT000 2 Way 1 2 Inch Globe Valve - Figure 8Dip switch settingsneptronic AT000 2 Way 1 2 Inch Globe Valve - Figure 9*On AT model:
When switch #3 is “ON”, the running time will be 60 sec.

neptronic LogoAT-220119

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals