MIX-4045-M Multi-Relay Module
Product Information
The MIX-4045-M multi-relay module is a device designed for
installation and use with a fire alarm control panel. It provides 8
form C (SPDT) contacts rated at 2A @ 30VDC or 0.5A at 125VAC
resistive loads from power limited sources. The relays are
programmable and can be individually switched by a compatible
panel. The module also supports group activation capability for
fast reaction time. The SLC is power limited and the module does
not supervise circuit connections to the relay contacts. The relays
are power limited if wired to a power limited source. The
MIX-4045-M is compatible with FX-400, FX-401, and FleX-NetTM FX4000
fire alarm control panels and meets UL 864, 10th Edition and ULC
S527, 4th Edition requirements for devices. The SLC and power
connections are on opposite corners of the device for easy
installation. The address of each module is set using the MIX-4090
programmer tool, and up to 240 units may be installed on a single
loop. The module has LED indicators for each relay to signal
activation (red). A green LED shows SLC communication status, and
two yellow LEDs indicate if a short circuit has been isolated on
either side of the SLC connection.
Product Usage Instructions
- Ensure you have read and understood the compatible control
panel instructions for the device’s operation modes and
configuration requirements. - Before performing installation or service, it is recommended to
disconnect the SLC line. - To mount the multi-relay module onto a DIN rail, follow these
steps:- Hook the multi-module device onto the bottom of the DIN rail
with three teeth. - Push the mounting clip upward with a flat screwdriver.
- Push the multi-module device onto the DIN rail and release the
clip.
- Hook the multi-module device onto the bottom of the DIN rail
- Refer to the wiring diagram for connecting loads to the
module’s relay contacts. - For alarm mode, connect the load on alarm 24VDC. For load
disconnected on alarm mode, connect the load on supply 24VDC. - The module provides six sets of normally closed (NC), common
(C), and normally open (NO) contacts. Refer to the wiring diagram
for specific connections.
INSTALLATION AND MAINTENANCE INSTRUCTIONS
MIX-4045-M MULTI-RELAY MODULE
25 Interchange way, Vaughan Ontario. L4K 5W3 Phone: 905.660.4655; Fax: 905.660.4113 Web: www.mircomgroup.com
ABOUT THIS MANUAL This manual is included as a quick reference for installation. For further information on the use of this device with a FACP, please refer to the panel’s manual.
Note: This manual should be left with the owner or operator of this equipment.
DESCRIPTION The MIX-4045-M multi-relay module provides 8 form C (SPDT) contacts rated at 2A @ 30VDC or 0.5A at 125VAC resistive loads from power limited sources. The relays are programmable and a compatible panel can switch individual contacts as required. The module also supports group activation capability for fast reaction time.
The SLC is power limited and the module does not supervise circuit connections to the relay contacts. The relays are power limited if wired to a power limited source.
The MIX-4045-M is compatible with FX-400, FX-401 and FleX-NetTM FX4000 fire alarm control panels and is designed to meet UL 864, 10th Edition and ULC S527, 4th Edition requirements for devices.
The SLC and power connections are on opposite corners of the device for easy installation. The address of each module is set using the MIX-4090 programmer tool and up to 240 units may be installed on a single loop. The module has LED indicators for each relay to signal activation (red). A green LED shows SLC communication status and finally, two yellow LEDs indicate if a short circuit has been isolated on either side of the SLC connection.
Accessories BB-4002R
BB-4006R
Back Box and Red Door for 1 or 2 MIX-4000-M Series Modules Back Box and Red Door for up to 6 MIX-4000-M Series Modules
FIGURE 1: MODEL FRONT AND SIDE VIEW
93mm
3
11 16
”
26mm 1″
SPECIFICATIONS Normal Operating Voltage:
Alarm Current: Standby Current: Temperature Range: Humidity Range: Dimensions:
Terminal wire gauge
110mm
4
5 16
”
UL tested 15 to 30VDC UL rated 17.64 to 27.3 VDC 8.3 mA 1.9 mA 0°C to 49°C (32°F to 120°F) 10% to 93% non-condensing 110 mm x 93mm (4 5/16 x 3 11/16 in) 12-22 AWG
RELATED DOCUMENTS · LT-6736 BB-4002R and BB-4006R Installation Instructions · LT-6749 MGC-4000-BR DIN Rail Kit Installation Instructions
1
LT-6720 rev 0.1 5/5/23
KEY COMPONENTS
FIGURE 2:
MULTI-RELAY MODULE ASSEMBLY COMPONENTS
Mounting clip
Multi-relay module
DIN rail
Programmer interface
LEDs
Locking insert for M2 screw
The MIX-4045-M multi-relay module as shown in figure 2 is designed to fit on a DIN rail. The M2 screw can be used to lock its position. Note: This device must be installed as per applicable requirements of the authorities having jurisdiction.
MOUNTING Units in the multi module series can be mounted on a top-hat style 35mm wide DIN rail included in the MGC listed enclosures: · BB-4002R for 1 or 2 modules (see document LT-6736) or equivalent
Listed enclosure of the same size or larger (see document LT-6749) · BB-4006R for up to 6 modules (see document LT-6736) or equivalent
Listed enclosure of the same size or larger (see document LT-6749) 1. Hook the multi module device onto the bottom of the DIN rail with
three teeth. 2. Push the mounting clip upward with a flat screwdriver. 3. Push the multi module device onto the DIN rail and release the clip.
FIGURE 3: MOUNTING DIAGRAM
Step 1
Step 2
WIRING Before installing this device, seek guidance from the compatible control panel instructions for the device’s operation modes and the configuration requirements. It is recommended to disconnect the SLC line before performing installation or service.
FIGURE 4: DEVICE CONNECTION RELAY WIRING
Load connected on alarm 24VDC
Supply
Load disconnected on alarm 24VDC
Supply
2A max load @ 30VDC
2A max load @ 30VDC
Normally Closed 1 Common 1 Common 2 Normally Open 2
NC1 C1 NO1 NC2 C2 NO2 NC3 C3 NO3 NC4 C4 NO4 NC5 C5 NO5 NC6 C6 NO6
Relay 1 Relay 2 Relay 3 Relay 4 Relay 5 Relay 6
Relay 7 Relay 8
NC7 C7 NO7 NC8 C8 NO8 LEDs 1234 5 678
SLC Line
++ I O
Jumper on pins 1-2
6/&RXWï TO PANEL OR SLC + NEXT DEVICE
6/&LQï FROM PANEL OR SLC + PREVIOUS DEVICE
Note: A factory-installed jumper is required between pins 1 and 2 of the J1 connector (next to the programmer connector).
All connections to field wiring are done with plug-in terminal blocks.
Use the information in this document to determine the total current draw of the devices. In all cases, the installer should consider the voltage drop to ensure that the last device on the circuit operates within its rated voltage. Please consult the FACP documentation for more information.
POWER LIMITED WIRING Group all power limited wiring together. Connect either power limited wiring or non-power limited wiring to each of the groups shown in figure 5. Do not mix power limited wiring and non-power limited wiring within the same group.
FIGURE 5: POWER LIMITED WIRING
Do not mix power limited wiring and non-power
limited wiring within the same group.
Group 1
Group 2
Step 3
2
NC1 C1 NO1 NC2 C2 NO2 NC3 C3 NO3 NC4 C4 NO4 NC5 C5 NO5 NC6 C6 NO6
Relay 1 Relay 2 Relay 3 Relay 4 Relay 5 Relay 6
Relay 7 Relay 8
NC7 C7 NO7 NC8 C8 NO8 LEDs 1234 5 678
Group 3
SLC Line
++ I O
LT-6720 rev 0.1 5/5/23