RBM-HY1043E Branching Header
Product Information: Branching Header (For R410A and R32)
The Branching Header is an essential component for the
installation of air conditioners that use R410A and R32
refrigerants. It is designed to branch the gas and liquid pipes
from the indoor unit to the outdoor unit, and it is available in
four models: RBM-HY1043E, RBM-HY1083E, RBM-HY2043E, and
RBM-HY2083E. The Branching Header comes with heat insulators for
both the gas and liquid sides.
Parts
The Branching Header package includes:
- Branching pipe gas side
- Branching pipe liquid side
- Heat insulator (gas side/liquid side) – 1pc each
The dimensions of all parts are in millimeters. In the tables
provided, ( ) indicates the diameter of the indicated position, and
others indicate the diameter of the connecting pipe. Please note
that the socket side with a projection (51, 52, 54, 58, 59, 61, 62,
70, 89) should be connected to the pipe.
Connecting Method
To connect the Branching Header to the indoor and outdoor
units:
- Select and install the socket that matches the diameter of the
pipe to be connected to the indoor unit. - Connect the outlet sealed pipe at the gas side to the outdoor
unit. - Connect the header sealed pipe at the liquid side to the indoor
unit. - Connect the outlet sealed pipe at the liquid side to the
Branching Header.
Make sure to install the Branching Header horizontally and do
not use T-type pipes for the branching section.
Requirement
Condensation may occur on the heat insulator due to the
atmosphere inside the ceiling. If the inside of the ceiling is
subject to high temperature and high humidity, it is recommended to
add glass wool (16 to 20 kg/m3, 10mm thick or more) on the heat
insulator for perfect heat insulation.
INSTALLATION MANUAL
Branching Header (For R410A and R32)
Please read “Safety Cautions” described in the Installation Manual of the Air Conditioner. · Check the following parts in the package. · For piping material and size of the refrigerant pipes, refer to the
Installation Manual of the Air Conditioner.
MODEL: Branching Header RBM-HY1043E RBM-HY1083E RBM-HY2043E RBM-HY2083E
PARTS
NOTE : 1. All dimensions are in millimeters. In the following tables, ( ) indicates diameter of the indicated position, and others indicate diameter of the connecting pipe.
2. Please connect pipe to the side with a projection of the socket. ( 51 , 52 , 54 , 58 , 59 , 61 , 62 , 70 , 89 : without projection)
projection
diameter of the connecting pipe
socket
NAME
MODEL
Branching pipe gas side
Branching pipe liquid side
RBM-HY1043E
Ø22.2
Ø9.5 Ø15.9
Ø15.9 1pc
Ø15.9 1pc
RBM-HY1083E
Ø22.2
Ø9.5 Ø15.9
Ø15.9 1pc
Ø15.9 1pc
RBM-HY2043E
Ø31.8
Ø9.5 Ø15.9
Ø15.9 1pc
Ø15.9 1pc
RBM-HY2083E
Ø31.8
Ø9.5 Ø15.9
Ø15.9 1pc
Ø15.9 1pc
Heat insulator (gas side/liquid side)
1pc each
1pc each
1pc each
1pc each
diameter of the connected pipe
No.
No.
No.
No.
No.
No.
No.
No.
14 Ø15.9×(Ø22.2) 1pc 18 Ø19.1×(Ø22.2) 1pc 70 Ø28.6×(Ø22.2) 1pc 85 Ø12.7×(Ø22.2) 1pc
06 Ø 9.5 ×(Ø15.9) 4pcs 14 Ø15.9×(Ø22.2) 1pc 09 Ø12.7×(Ø15.9) 4pcs 18 Ø19.1×(Ø22.2) 1pc
70 Ø28.6×(Ø22.2) 1pc 85 Ø12.7×(Ø22.2) 1pc
06 Ø 9.5 ×(Ø15.9) 8pcs 27 Ø28.6×(Ø31.8) 1pc 09 Ø12.7×(Ø15.9) 8pcs 59 Ø34.9×(Ø31.8) 1pc
23 Ø22.2×(Ø31.8) 1pc
06 Ø 9.5 ×(Ø15.9) 2pcs 27 Ø28.6×(Ø31.8) 1pc 09 Ø12.7×(Ø15.9) 2pcs 59 Ø34.9×(Ø31.8) 1pc
23 Ø22.2×(Ø31.8) 1pc
06 Ø 9.5 ×(Ø15.9) 7pcs 09 Ø12.7×(Ø15.9) 7pcs
external diameter of socket
06 Ø 9.5 ×(Ø15.9) 1pc 01 Ø 6.4 ×(Ø 9.5) 4pcs 06 Ø 9.5 ×(Ø15.9) 1pc 01 Ø 6.4 ×(Ø 9.5) 8pcs 51 Ø 19.1 ×(Ø15.9) 1pc 01 Ø 6.4 ×(Ø 9.5) 2pcs 51 Ø 19.1 ×(Ø15.9) 1pc 01 Ø 6.4 ×(Ø 9.5) 7pcs
09 Ø12.7×(Ø15.9) 1pc
09 Ø12.7×(Ø15.9) 1pc
91 (Ø15.9)ר12.7ר9.5 1pc
91 (Ø15.9)ר12.7ר9.5 1pc
Socket Liquid side Gas side
Outlet sealed pipe at gas side Header sealed pipe at liquid side
Outlet sealed pipe at liquid side
(Ø15.9) 1pc (Ø15.9) 1pc
(Ø 9.5) 1pc
(Ø15.9) 3pcs (Ø15.9) 1pc
(Ø 9.5) 3pcs
(Ø15.9) 1pc (Ø15.9) 1pc
(Ø 9.5) 1pc
(Ø15.9) 3pcs (Ø15.9) 1pc
(Ø 9.5) 3pcs
CONNECTING METHOD
Select and install the socket that matches the diameter of a pipe to be connected to the indoor unit.
<Gas side>
Pipe in use on the site
Socket Pipe in use on the site
<Liquid side>
Pipe in use on the site
Socket Pipe in use on the site
To outdoor unit Socket
To indoor unit
To outdoor unit
To indoor unit Socket
· If the number of indoor units to be connected is fewer than the maximum number of units that can be connected to the branching header, attach a sealed pipe to the unused connectors.
Outlet sealed pipe (Provided with branch header)
A
B
C D
· Install the branching header so that it branches horizontally.
<Gas side>
(Horizontal line)
(A view)
<Liquid side>
Within ±15 degrees
(Horizontal line)
(Horizontal line)
(B view)
Within ±10 degrees
(C view)
Outlet sealed pipe (Provided with branch header) Within ±15 degrees
When arranging the branching header at the liquid side, attach a header sealed pipe on the sealing side of the header as shown in the fiqure at right. Be sure to install the branch pipe downward. Horizontal viewed from D point should be within ±10 degrees same as view B. · Supporting branching header
After applying the insulation, set the hanging metals as support. (in use on the site).
Inlet socket Branching Header Header sealed pipe
Pipe in use on the site
(D view) Sealing side
Within ±10 degrees
NOTE : 1. Install the branching header so that it branches horizontally. It cannot be used in a vertical position. 2. Do not use T-type pipe for the branching section.
REQUIREMENT
Condensation may occur on the heat insulator according to the atmosphere inside of the ceiling. If the inside of the ceiling is subject to high temperature and high humidity,please add the glass wool (16 to 20 kg/m3, 10mm thick or more) on the heat insulator described above for the perfect heat insulation.