Clipsal 755psma4 Smoke Alarm Photo, Surface, 230v Instruction Manual

Clipsal 755psma4 Smoke Alarm Photo, Surface, 230v Instruction Manual

CLIPSAL Logo755PSMA4 Smoke Alarm Photo, Surface, 230v
Instruction Manual
CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v

240 V a.c. Mains Power Photoelectric Smoke Alarm with 9 V d.c. Battery Backup

CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Icon More information is available

CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Qr Codehttps://download.schneider-electric.com/files?p_Doc_Ref=EAV8159103

Scan the QR code for more information about your Clipsal smoke alarm:

  • What smoke alarms can and cannot do
  • Developing and practising a plan of escape
  • What to do if an alarm sounds.

Operating the smoke alarm CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Icon 9

CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Figure 12

CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Icon 1 Operating elements

CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Figure 1

CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Icon 2 Installation location

Install more than 1 m away from air conditioner/heater vents and fans, electrical sources, appliances and fittings.CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Figure 2

Example: Class 1a building
slide barSmoke alarm
POWERADD T18 Wireless Earbuds - icon 2Recommended additional alarms (or as required by legislation)CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Figure 5

Do not install in garages, kitchens, bathrooms or any area with high levels of moisture, dirt or insects.
For garages: A heat alarm is more suitable as it is not affected by particulates.CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Figure 3

Example: Class 1b building
slide barSmoke alarm
CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Icon 4 Smoke alarm with evacuation lightingCLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Figure 6

CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Icon 3 Dead air space (do not install in these locations
CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Figure 4Storeys with bedrooms:
slide barAlarm in hallway connecting bedroomsCLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Figure 7

Storeys with no bedrooms:
slide barAlarms located in the area of the stairway.

CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Icon 5 Installation

CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Figure 8Note: Ensure that the alarm base is mounted flat against the mounting surface.CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Figure 9

Single alarm
Terminal markings:
A: Active/Line
E-Loop: Earth or Loop
N: Neutral
I-Connect: InterconnectCLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Figure 10

Interconnected alarmsCLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Figure 11

General information

  • Paulmann Ceiling Lighting Accessories - Icon 1 Leave these instructions with the occupant, to be retained for the life of the alarm.
  • This smoke alarm must be installed by a licenced electrician.
  • Do not remove dust cover until 24 hours after all construction has been completed. Construction dust and chemicals can cause contamination and false alarms.
  • Important: Dust cover must be removed before smoke alarm will operate correctly.

For your safety
Electric Warning IconWarning iconDANGER
RISK OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

  • This product must only be installed and serviced by appropriately qualified and/or licenced electrical personnel.
  • This product must only be used for the purposedescribed in these instructions and must be installed in accordance with the wiring rules and regulations in that location.
  • Isolate the electrical supply before doing any work on this product.
  • Ensure the product has been correctly installed and tested for safe operation before reconnecting the electrical supply.

Failure to follow these instructions will result in death or serious injury.
Warning-icon.png CAUTION
EQUIPMENT INSTALLATION HAZARD

  • Ensure active and neutral from mains power are wired to the correct terminals.
  • Ensure the green LED is ON when mains power is supplied.
  • Ensure the red LED is not flashing quickly.
  • Test each interconnected unit 1 by 1. Press and hold the Test button until second burst of 3 beeps has finished. If any unit fails to alarm, check all wiring and connections.

Failure to follow these instructions may result ininjury or equipment damage.
Operating elements CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Icon 1
Installing/replacing the backup battery
CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Icon 6

  • Paulmann Ceiling Lighting Accessories - Icon 1The backup power to the smoke alarm is supplied by a 9 V d.c. carbon zinc or alkaline battery. The battery should last at least one year under normal operating conditions.
  • An audible beep every 40 seconds indicates the battery needs to be replaced. It is recommended to replace the battery annually on a memorable day using the calendar reminder stickers provided.
  • Recommended batteries include: Energizer 522, Duracell MN1604, Eveready A522 or 1222, GP 1604A.
  • To snooze a low battery beep for 10 hours, press the Test/Hush button for 3 seconds.

Choosing the installation location CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Icon 2
Paulmann Ceiling Lighting Accessories - Icon 1Prior to installing, ensure there are no obstructions in ceiling mounting locations, such as pipes or cables.
NOTICE
EQUIPMENT INSTALLATION COMPLIANCE
This smoke alarm must be installed in accordance with the National Construction Code and any local state legislation requirements.
Failure to follow these instructions may result in a non-compliant installation.
Installing the smoke alarm CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Icon 5

  • Paulmann Ceiling Lighting Accessories - Icon 1Only install smoke alarm indoors in a stand-alone or interconnected set up (see Interconnecting smoke alarms).
  • Use minimum cable width 1 mm for all wiring, including interconnect wiring where used.
  • Do not remove the dust cover until you are ready to test the unit. See CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Icon 7

Mounting the smoke alarm
CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Icon 8
Connecting the smoke alarm
CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Icon 8 (see Single alarm)
Interconnecting smoke alarms
CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Icon 8 (see Interconnected alarms)
Warning-icon.png CAUTION
EQUIPMENT INSTALLATION HAZARD

  • All interconnected smoke alarms must be supplied from the same circuit.
  • A common Neutral must be used for the Interconnect to operate.
  • DO NOT connect the Interconnect wire to Active or Neutral.
  • Maximum of 40 interconnected smoke alarms.
  • Only Clipsal smoke alarms are compatible forinterconnection with this alarm.

Failure to follow these instructions may result in injury or equipment damage.
Paulmann Ceiling Lighting Accessories - Icon 1Maximum wire length between first and last alarm is 150 m.
Wireless interconnection
An optional wireless base (Catalogue No. 755RFB2) may be purchased separately if wired interconnection is not possible.
Paulmann Ceiling Lighting Accessories - Icon 1A maximum of 40 smoke alarms can be interconnected using wireless bases.

Operating the smoke alarm CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Icon 9

Testing the smoke alarm
CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Icon 7
Warning-icon.png CAUTION
DO NOT USE OPEN FLAME
Never use an open flame of any type to test your alarm.
Failure to follow this instruction may result in injury or equipment damage.

  • Paulmann Ceiling Lighting Accessories - Icon 1Test the smoke alarm once per month to ensure proper operation.
  • If no alarm sounds, check the battery orientation or replace the battery (see CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Icon 6). If the battery is new, installed in the correct orientation and the alarm still doesn’t sound, replace the smoke alarm.
  • If the smoke alarm is installed in a mobile home, test weekly and before every journey.
  • IMPORTANT: If premises are unoccupied for a more than a few days, a battery test must be undertaken upon return. If the low battery warning sounds, replace with new battery and test again.
  • Check that all interconnected smoke alarms operate during the test.

Interconnected smoke alarms

  • Paulmann Ceiling Lighting Accessories - Icon 1Test each alarm in an interconnected group.
  • For each alarm test, ensure that all interconnected alarms operate.

Silencing the smoke alarm (Hush feature)
CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Icon 10

  • Paulmann Ceiling Lighting Accessories - Icon 1When the Test/Hush button is pressed during an alarm event, the smoke alarm is not sensitive to smoke for 10 minutes, after which the alarm resumes normal operation. During this hush time, the red LED flashes once every 8 seconds.
  • Wait 10 minutes before performing any additional testing to avoid any abnormal alarm responses.

Snoozing low battery, fault and alarm memory indications
CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Icon 11
Low battery
Paulmann Ceiling Lighting Accessories - Icon 1When the backup battery gets low, the red LED flashes once every 40 seconds, together with a beep sound. You can snooze the low battery indication for 10 hours by pressing the Test/Hush button for 3 seconds.
Replace the backup battery as soon as possible.
Alarm fault
Paulmann Ceiling Lighting Accessories - Icon 1When an alarm fault is detected, the red LED flashes once every 40 seconds, together with 2 beeps. You can snooze the alarm faultindication for 10 hours by pressing the Test/Hush button for 3 seconds.
Alarm memory
Paulmann Ceiling Lighting Accessories - Icon 1In an interconnected alarm group, the red LED on the triggered alarm flashes once every2 seconds for 72 hours after the alarm beeping has stopped, so that you can identify the unit as the alarm that was triggered. Press the Test/Hush button for 3 seconds to snooze the flashing LED for 10 hours. The snooze function for the alarm memory can be repeated as often as desired up to the 72 hour limit.

LED and sound indications

Operating modeRed LEDSoundDuration
Normal mode / Standby mode1 flash every 40 sOFF
ALARM MODELocal alarm1 flash every 1 sContinuous siren
Interconnected alarmOFFContinuous siren
Test mode1 flash every 1 sSiren (3 s)
Hush mode1 flash every 8 sOFF10 min
ALARM MEMORY (triggered alarm only)Normal1 flash every 2 s after alarm stopsOFFTotal 72 hrs
Hushed during alarm1 flash every 2 s after Hush startedOFFTotal 72 hrs
SnoozeSee Snooze Mode
Low battery mode1 flash every 40 s1 beep every 40 sUntil backup battery is replaced
Fault mode2 flashes every 40 s2 beeps every 40 sUntil fault has been cleared
SNOOZE MODELow battery1 flash every 24 sOFF10 hrs
Fault1 flash every 24 sOFF10 hrs
Alarm memory1 flash every 40 sOFF10 hrs
Green LED
Mains power ONON

Troubleshooting

ProblemCause and Resolution
ALERTS AND SILENCINGAlarm sounds and the red LED is blinking rapidlySmoke has activated the smoke alarm.
Vacate the building immediately and call the Fire and Emergency Services. See False Alarm section.
Alarm sounds but the red LED is OFFSmoke has activated an interconnected alarm, located somewhere else in the building.
Vacate the building immediately and call the Fire and Emergency Services. See False alarm section.
Smoke alarm is sounding, it stops when Test/Hush is pressedHush or silence feature has been activated for 10 minutes providing the smoke density does not increase.
Ensure you are safe and have put out the source of the smoke. See False alarm section.
Red LED is flashing every 2 secondsAlarm memory has been activated, indicating that this alarm was the triggered alarm in the group.
LED stops flashing after 72 hours. Press Test/Hush to snooze the LED indication for 10 hours.
Smoke alarm is sounding and does not stop when Test/ Hush is pressedSmoke density is too high for the Hush or Silence feature to activate.
Vacate the building immediately and call the Fire and Emergency Services. See False alarm section.
When Test/Hush button is pressed for three seconds alarm sounds brieflyThe smoke alarm horn is indicating that all electronic circuitry, horn and battery are working.
Normal test condition.
Test regularly to ensure proper operation.
When Test/Hush button is pressed for three seconds alarm does not soundsThe smoke alarm may not be operating correctly.
Check and ensure that the green LED is ON and the red LED flashes once every 40 seconds. If the problem persists contact an electrician for replacement.
BEEPINGOne audible beep every 40 secondsLow battery warning.
Replace the 9 V d.c. battery with a new one.
Two audible beeps every 40 secondsThe smoke alarm may not be operating correctly.
Clean smoke alarm according to the Maintenance, Repairs and Service section. If problem persists, contact an electrician for replacement.
POWER AND BATTERYSmoke alarm body will not close on the base9 V d.c. backup battery is not installed.
Insert a new 9 V d.c. battery.
Red LED not flashing every 40 secondsBattery may be reversed, not present or completely flat.
Check and re-install or replace the battery.
Red LED flashes very quickly (3 times per second)Neutral connection is bad or wiring is wrong.
Check wiring and connection of smoke alarms with flashing red LED and rectify wiring issue immediately.
Green LED offMains power may be disconnected.
Check mains power ON. Main circuit breaker may have tripped. Wiring could be wrong.

False Alarm

In the event of a false alarm in an interconnected group, it is important to identify the triggering alarm(s). These alarms may need to be cleaned, serviced or replaced if necessary.
When alarms are sounding without any smoke present:

  • Identify which smoke alarm(s) are being triggered – Look for the alarm(s) with sound and red LED flashing.
  • Unclip all identified smoke alarms. Any remaining interconnected alarms will stop alarming in 1 minute.
  • If the alarming stops before you have identified the alarms that are being triggered, look for any alarms with the red LED flashing once every 2 seconds. This flashing can be snoozed for 10 hours by pressing the Test/Hush button for 3 seconds. The snooze function can be repeated as often as desired up to the 72 hour limit.
  • Clean affected smoke alarms in accordance with the Maintenance, Repairs and Service section.
  • Re-install and test all the smoke alarms.

If all of the above fails, contact a licenced electrician for replacement.

Maintenance, Repairs and Service

Maintenance
It is recommended that the smoke alarm is inspected monthly to ensure it is free from dirt, dust and insects. The alarm can be vacuumed or brushed with a soft brush to remove dust, dirt or kitchen grease that has accumulated. Apply a small amount of insect surface spray to a cloth and wipe around alarm/s every 3-6 months to mitigate insect ingress.
ALWAYS TEST THE SMOKE ALARM AFTER CLEANING
Repairs and Service
NOTICE
EQUIPMENT MAINTENANCE INSTRUCTIONS

  • Test this smoke alarm regularly to ensure the unit is functional and that the battery is in good condition.
  • Replace the backup battery every year.
  • Replace the smoke alarm 10 years after date of manufacture.
  • Do not open the smoke alarm casing or repair the smoke alarm yourself. The only user-serviceable part is the replaceable backup battery. There are no other user-serviceable parts inside.

Failure to follow these instructions may result in equipment malfunction or failure.
Disposal
As the smoke alarm does not contain any radioactive material, disposal with normal rubbish is permitted in Australia and New Zealand.
Before disposal, move the battery disconnect switch to the disconnect position. This will prevent the low battery warning beep when the battery eventually discharges.

Technical data

Main Power Source220–240 V a.c., 50 Hz
Secondary Power Source9 V d.c. carbon zinc or alkaline battery
Operating Current≤40 mA
Battery Life1 year
Sensing TypePhotoelectric. This alarm contains NO radioactive material.
Operating Temperature0 °C to 45 °C
Ambient Humidity5% to 95%
InterconnectingWired: 40 alarms over 150 metres maximum
Wireless: 40 alarms maximum
Terminal ProvisionsActive, Neutral, Loop and Interconnect terminals, each accommodates 2 × 1.5 mm2
Horn Level85 dB at three metres minimum
ApprovalsActivfire      SAI Global     RCM
Complies withAS 3786: 2014, AS/NZS 60065 and AS/NZS 60950.1

WEE-Disposal-icon.png It is recommended to dispose of this device at an authorised electronic waste collection point. Professional recycling protects people and the environment against potential negative effects.
Trademarks and certifications
Schneider Electric acknowledges that the Australian Standard Certified Product logo is a trademark of SAI Global, and that the Activfire Certified logo is a trademark of CSIRO.CLIPSAL 755PSMA4 Smoke Alarm Photo, Surface, 230v - Logo

Warranty

We warrant this product to be free from defects in materials and workmanship for a period of 5 (five) years from the date of installation.
Customer care
If you have technical questions, please contact the Customer Care Centre in your country.
Australia
Schneider Electric (Australia) Pty Ltd
33-37 Port Wakefield Road, Gepps Cross SA 5094
Customer Care Australia: 13 73 28
e: [email protected]
www.schneider-electric.com.au
New Zealand
Schneider Electric (NZ) Ltd
Building 6, 60 Highbrook Drive, East Tamaki,
Auckland, 2013
After hours service: 0800 735 4357 (NZ only)
Customer Care NZ: 0800 652 999
e: [email protected]
www.schneider-electric.com

CLIPSAL LogoQGH8213701_02

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals