Nvent Hoffman Operator Adapter Gev Instruction Manual

Operator Adapter GEV

Product Information

The Operator Adapter GEV is an installation accessory designed
for General Electric Types STDA Variable Depth Operating
Mechanisms. It is used for disconnect switches and circuit breakers
mounted in Hoffman wo-door, floor-mounted enclosures with the
disconnect on the right flange.

Parts List

Item No.DescriptionPart No.Qty.
1ADAPTER PLATE, VARIABLE DEPTH891127461
2PLATE GASKET891096131
3SCREW, 1/4-20X1/2 PAN HEAD994010314
4SLIDE ARM262500011
5SHOULDER COLLAR261490011
6SCREW, 1/4-20X7/8, HEX HEAD994010301
7LOCKWASHER, 1/4 SPRING994013181
8WASHER, FLAT221010032
9LOCKWASHER, 1/4 INTERNAL TEETH994013002
10NUT, 1/4-20 HEX994014062
11DOOR CATCH231010021
12SCREW, 10-32X3/8 PAN HEAD994010072
13LOCKWASHER, #10 INTERNAL TEETH994013072
14NYLON WASHER261320034
15INSTALLATION INSTRUCTIONS891146641

Product Usage Instructions

  1. Step 1: Install the operating plate (item 1) and plate gasket
    (item 2) on the inside of the enclosure, behind the rectangular
    opening provided. Attach the gasket side with PSA to the adapter
    plate. Secure in place with four screws (item 3) and four nylon
    washers (item 14).
  2. Step 2: Assemble the General Electric G.E. STDA operating
    handle to the mounting plate installed in step 1. Omit the cap
    screw and lockwasher that fits into the bottom hole of the G.E.
    operating handle. Also, omit the G.E. stiffening bracket, as it is
    not required.
  3. Step 3: Attach the bottom of the slide arm (item 4) to the
    offset arm of the lock release mechanism. Use two flat washers
    (item 8), two lockwashers (item 9), and two hex nuts (item 10). Do
    not tighten until parts are adjusted (see step 5B).
  4. Step 4: The handle safety lock release mechanism is adjustable.
    • (A) Check the adjustment of the factory-installed roller
      bracket. The door latch should hit against the latch stop portion
      of the roller bracket when the door is closed and latched. Adjust
      up or down if necessary.
    • (B) The attached mechanism will provide the necessary up-down
      motion required to operate the release mechanism in the G.E.
      operating handle.

Note: It is important to check the function, fits, and
clearances of all equipment both before and after installation to
ensure proper and safe operation. If the completed installation
does not function properly or fails to meet any applicable codes,
standards, or regulations, do not attempt to make alterations or
operate the equipment. Report any issues to Hoffman Customer
Service immediately.

Contact Information:

Hoffman Customer Service
2100 Hoffman Way
Anoka, MN 55303
Phone: 763.422.2211
Website: http://hoffman.nvent.com/contact-us

OPERATOR ADAPTER GEV
Installation Instructions for General Electric Types STDA Variable Depth Operating Mechanisms (For parts list, see Page 2)
)RUIORRUPRXQWHGHQFORVXUHVZLWK WKHGLVFRQQHFWRQWKHULJKWIODQJH
0DVWHU ‘RRU
)RURQHWKURXJKVL[GRRUIUHHVWDQGLQJHQFORVXUHV ZLWKWKHGLVFRQQHFWWKHWKHULJKWIODQJH 0DVWHU ‘RRU
)RUIORRUPRXQWHGHQFORVXUHVZLWK WKHGLVFRQQHFWRQWKHFHQWHUSRVW
0DVWHU ‘RRU

Rev. B

© 2018 Hoffman Enclosures Inc.

PH 763 422 2211 · nVent.com/HOFFMAN

P/N 89114663

89115502

The functions, fits and clearances of the installation described hereon are calculated from information supplied by the manufacturers of the equipment to be installed. Be certain to check the function, fits and clearances of all equipment both before and after installation to assure that it operates properly and safely and meets all applicable codes, standards and regulations.
In the event the completed installation does not function properly or fails to meet any such codes, standards or regulations, do not attempt to make alterations or operate the equipment. Report such facts immediately to:
Hoffman Customer Service 2100 Hoffman Way Anoka, MN 55303 763.422.2211
http://hoffman.nvent.com/contact-us

Parts List
Operator Adapter, Catalog Number GEV, for General Electric Disconnects

Item No. Description

Part No.

Qty.

1

ADAPTER PLATE, VARIABLE DEPTH

89112746

1

2

PLATE GASKET

89109613

1

3

SCREW, 1/4-20X1/2 PAN HEAD

99401031

4

4

SLIDE ARM

26250001

1

5

SHOULDER COLLAR

26149001

1

6

SCREW, 1/4-20X7/8, HEX HEAD

99401030

1

7

LOCKWASHER, 1/4 SPRING

99401318

1

8

WASHER, FLAT

22101003

2

9

LOCKWASHER, 1/4 INTERNAL TEETH

99401300

2

10

NUT, 1/4-20 HEX

99401406

2

11

DOOR CATCH

23101002

1

12

SCREW, 10-32X3/8 PAN HEAD

99401007

2

13

LOCKWASHER, #10 INTERNAL TEETH

99401307

2

14

NYLON WASHER

26132003

4

15

INSTALLATION INSTRUCTIONS

89114664

1

– 2 –

© 2018 Hoffman Enclosures Inc.

PH 763 422 2211 · nVent.com/HOFFMAN

89115502

INTRODUCTION
This installation instruction is for General Electric (variable depth) mechanisms. These mechanisms are for disconnect switches and circuit breakers mounted in Hoffman wo-door, floor-mounted, enclosures with the disconnect on the right flange.

INSTALLATION STEPS
Step 1 Install operating plate (item1) and plate gasket (item 2) on the inside of the enclosure, behind the rectangular opening provided. Gasket side with PSA should be attached to the adapter plate. Secure in place with four screws (item 3) and four nylon washers (item 14).

Step 2
Assemble the General Electric G.E. STDA operating handle to the mounting plate which was installed in the enclosure in step 1. Omit cap screw and lockwasher which fits into bottom hole of G.E. operating andle. Also omit G.E. stiffening bracket, which is not required.

Step 3
Install the slide arm (item 4) over the interlock part of the G.E. operating handle as shown. Note the the notch in the slide arm is positioned toward the door opening. Place the smaller diameter end of the shoulder collar (item 5) through the oval slot in the slide arm. Install long cap screw (item 6) with lockwasher (item 7) through shoulder collar into the bottom mounting hole of the G.E. operating handle and tighten. The slide arm should move up and down smoothly. Install G.E. interlock blade per G.E. instructions.

Step 4
Attach the bottom of the slide arm (item 4) to the offset arm of the lock release mechanism. Use two flat washer (item 8), two lockwashers (item 9), and two hex nuts (item 10). Do not tighten until parts are adjusted (see step 5B).

Step 5 The handle safety lock release mechanism is adjustable.
(A) Check the adjustment of the factory installed roller bracket. The door latch should hit against the latch stop portion of the roller bracket when the door is closed and latched. Adjust up or down if necessary. The attached mechanism will then provide the necessary up-down motion required to operate the release mechanism in the G.E. operating handle.
(B) Adjust the length of the slide arm assembly. With proper adjustment of the slide arm, the safety lock (in G.E. opating handle) should release just before the master door is fully latched. Lengthen slide arm if safety lock releases too soon. Shorten slide arm if safety lock releases too late.

Step 6
Attach the door catch (item 11), provided by Hoffman, to the tapped spacer on the door using the bottom set of mounting holes. Use two screws (item 12) and lockwashers (item 13). The door catch prevents the door from being opened when the G.E. operating handle is in the “ON” position.

Step 7
Drill and tap holes in panel per General Electric instructions. See General Electric instructions for locating holes for fuse blocks for 200 AMP switches.

Step 8 Install panel in enclosure.

Step 9
Mount disconnect switch or circuit breaker and operating mechanism on panel using General Electric instructions and parts. Attach G.E. handle return spring between drive link on G.E. operating handle and hole provided in Hoffman adapter plate as shown.

89115502

© 2018 Hoffman Enclosures Inc.

PH 763 422 2211 · nVent.com/HOFFMAN

– 3 –

For Floor-Mounted, Two-Door Enclosures with Disconnect on Right Flange

‘5,9(/,1.
,17(5/2&. ,17(5/2&.%/$'( +$1’/(5(7851635,1*

2))6(7$50
/2&.5(/($6( 0(&+$1,60

52//(5%5$&.(7
52//(5%5$&.(7 /$7&+6723

– 4 –

© 2018 Hoffman Enclosures Inc.

PH 763 422 2211 · nVent.com/HOFFMAN

89115502

INTRODUCTION
This installation instruction is for General Electric (variable depth) mechanisms. These mechanisms are for disconnect switches and circuit breakers mounted in Hoffman one through six door, free-standing enclosures with the disconnect on the right flange.

INSTALLATION STEPS
Step 1 Install adapter plate (item 1) and plate gasket (item 2) on the inside of the enclosure, behind the rectangular opening provided. Gasket side with PSA should be attached to adapter plate. Secure in place with four screws (item 3) and four nylon washers (item14).

Step 2
Assemble the G.E. STDA operating handle to the mounting plate which was installed the enclosure in tep 1. Omit cap screw and lockwasher which fits into bottom hole of G.E. operating handle. Also omit G.E. stiffening bracket which is not required.

Step 3
Install the slide arm (item 4) over the interlock part of the G.E. operating handle as shown. Note that he notch in the slide arm is positioned toward the door opening. Place the smaller diameter end of the shoulder collar (item 5) through the oval slot in the slide arm. Install long cap screw (item 6) with lockwasher (item 7) through shoulder collar into the bottom mounting hole of the G.E. operating handle and tighten. The slide arm should move up and down smoothly. Install G.E. interlock blade per G.E. instructions

Step 4
Attach the bottom of the slide arm (item 4) to the offset arm of the lock release mechanism. Use two flat washers (item 8), two lockwashers (item 9), and two hex nuts (item 10). Do not tighten until parts are adjusted (see step 5B)

Step 5 The handle safety lock release mechanism is adjustable in two places.
A) Check the adjustment of the factory installed roller bracket. The door latch should hit against the latch stop portion of the roller bracket when the door is closed and latched. Adjust up or down if necessary. The attached mechanism will then provide the necessary up-down motion required to operate the release mechanism in the G.E. operating handle.
B) Adjust the length of the slide arm assembly. With proper adjustment of the slide arm, the safety lock (in G.E. operating handle) should release just before the master door is fully latched. Lengthen slide arm if safety lock releases too soon. Shorten slide arm if safety lock releases too late.

Step 6
Attach the door catch (item 11) provided by Hoffman to the tapped spacer on the door using the bottom et of mounting holes. Use two screws (item 12) and lockwashers (item 13). The door catch prevents the door from being opened when the G.E. operating handle is in the “ON” position.

Step 7
Drill and tap holes in panel per General Electric instructions. See General Electric instructions for locating holes for fuse blocks for 200 AMP. switches.

Step 8 Install panel in enclosure.

Step 9
Mount disconnect switch or circuit breaker and operating mechanism on panel using General Electric instructions and parts. Install and adjust G.E. drive rod per G.E. instructions. Attach G.E. handle return spring between drive link on G.E. operating handle and hole provided in Hoffman adapter plate as shown.

89115502

© 2018 Hoffman Enclosures Inc.

PH 763 422 2211 · nVent.com/HOFFMAN

– 5 –

‘5,9(/,1.
,17(5/2&. ,17(5/2&.%/$'( +$1’/(5(7851635,1*

2))6(7$50
/2&.5(/($6( 0(&+$1,60

52//(5%5$&.(7
52//(5%5$&.(7 /$7&+6723

– 6 –

© 2018 Hoffman Enclosures Inc.

PH 763 422 2211 · nVent.com/HOFFMAN

89115502

INTRODUCTION
This installation instruction is for General Electric variable depth) mechanisms. These mechanisms are for disconnect switches and circuit breakers mounted in Hoffman two door, floor-mounted enclosures with the disconnect on the centerpost.
INSTALLATION STEPS
Step 1 Install adapter plate (item 1) and plate gasket (item 2) on the inside of the enclosure, behind the rectangular opening provided in the centerpost. Gasket side with PSA should be attached to the adapter plate. Secure in place with four screws (item 3), and four nylon washers (item14).
Step 2 Assemble the G.E. type STDA operating handle to the mounting plate which was installed in the enclosure in step1. Omit cap screw and lockwasher which fits into bottom hole of G.E. operating handle. Also omit G.E. stiffening bracket which is not required.
Step 3 Cut 2 1/2 inches off bottom end of slide arm (item 4). (bottom end of slide arm has rectangular holes only)
Step 4 Install the slide arm (item 4) over the interlock part of the G.E. operating handle as shown. Note that the otch in the slide arm is positioned toward the door opening. Place the smaller diameter end of the shoulder collar (item 5) through the oval slot in the slide arm. Install long cap screw (item 6) with lockwasher (item 7) through shoulder collar into the bottom mounting hole of the G.E. operating handle and tighten. The slide arm should move up and down smoothly. Install G.E. interlock blade per G.E. instructions.
Step 5 Attach the bottom of the slide arm (item 4) to the offset arm as shown. Use two flat washers (item 8), two lockwashers (item 9), and two hex nuts (item 10). Do not tighten until parts are adjusted.
Step 6 Adjust the length of the slide arm assembly. With proper adjustment of the slide arm, the safety lock (in G.E. operating handle) should release just before the master door is fully latched. Lengthen slide arm if safety lock releases too soon. Shorten slide arm if safety lock releases too late.
Step 7 Attach the door catch (item 11) provided by Hoffman to the tapped space on the door using the bottom set of mounting holes. Use two screws (item 12) and two lockwashers (item 13). The door catch prevents the door from being opened when the G.E. operating handle is in the “ON” position.
Step 8 Drill and tap holes in panel per General Electric instructions. See General Electric instructions for locating holes for fuse blocks for 200 AMP. switches.
Step 9 Install panel on collar studs in enclosure.
Step 10 Mount disconnect switch or circuit breaker and operating mechanism on panel using General Electric instructions and parts. Install and adjust G.E. drive rod per G.E. instructions. Attach G.E. handle return spring between drive link on G.E. operating handle and hole provided in Hoffman adapter plate as shown.
* NOTE: An optional General Electric flange stiffener kit (catalog number TDSR) is recommended when General Electric type STDA devices are installed in 72.12 inch high enclosures with operating handle mounted on centerpost. Use with TDOM1,2,3 operating mechanisms.

89115502

© 2018 Hoffman Enclosures Inc.

PH 763 422 2211 · nVent.com/HOFFMAN

– 7 –

‘5,9(/,1. ,17(5/2&. ,17(5/2&.%/$'( +$1’/(635,1*
5(7851

2))6(7$50

– 8 –

© 2018 Hoffman Enclosures Inc.

PH 763 422 2211 · nVent.com/HOFFMAN

89115502

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals