Emerson Bettis Rts Extension Board Instruction Manual

Emerson Bettis Rts Extension Board Instruction Manual

EMERSON logo

Bettis RTS Extension Board
Instruction Manual
EMERSON Bettis RTS Extension Board

Installation, Operation, and Maintenance Manual
VCIOM-16741-EN Rev. 0 November 2021
Bettis RTS
Extension Board for Modbus RTU

Section 1: Extension Board for Modbus RTU on RTS Control Unit

1.1 General Information
For Bettis RTS actuators, the standardized Fieldbus interface Modbus RTU is available.
This interface is a product option represented in hardware on the device, thus making it beneficial to advertise intended use upon ordering. Although enabling Modbus RTU a posterior is possible, such upgrades should only be performed by authorized Emerson engineers or specially trained personnel.
Modbus RTU determines the technical and functional characteristics of the serial Fieldbus system used to connect distributed autonomous devices. Modbus RTU distinguishes Master- and Slave-Devices and has been designed for data transmission at the field level, hence, the communication of central control units – as SPS or PC – with decentralized field devices over a fast serial connection. Communication functionality is standardized by the MODBUS Organization (modbus.org).
The physical communication layer is based on an RS-485 interface connected through a shielded twisted two-wire cable.
Bettis RTS control units are always slave devices.
1.1.1 Communication Settings

The detection of the settings of the Modbus RTU communication is done automatically in the Bettis RTS Modbus RTU slave module during communication start-up.

The supported baud rates are:

· 4800 bps
· 7200 bps
·9600 bps
· 14400 bps
· 19200 bps
· 28800 bps
·38400 bps
· 57600 bps
· 76800 bps
· 115200 bps

The byte frame has the following bits:
· 1 start bit
· 8 data bits, LSB first
· 1 parity bit (even, odd or mark)
· 1 stop bit

If mark parity is not supported by the Modbus RTU master, you can use no parity and 2 stop bits instead.

Section 2: Connection

Depedning on the order, here are the following connections possible:

  • standard design: connection board
  • explosionproof design: terminals

Standard Design

Connecting the actuator to the fieldbus system is accomplished through connecting the bus cable to the connection print in the connection compartment of the actuator. Thus for convinience, the Modbus RTU connector is pluggable like every other external connector for signal or power on our actuators. Disconnecting a device will have no effect on the communication of other devices in the same strand. Meaning, the network maintains full functionality if a device is disconnected while the network is in operation. But beware, at the end of each strand Modbus RTU has to be terminated. This termination can either be performed by RTS control unit or a separate active bus termination device. Note that the power for the termination resistors of RTS control unit comes from the actuator. Hence, disconnecting the terminating RTS control unit renders the bus in this strand inoperational. Therefore, it is advised to use active bus termination through a dedicated device. The single-channel version of RTS control unit is connected to Modbus RTU via channel I. The dual channel version (Option: redundant) is connected via channel I and II.

Connection Board (Customer End)
The connection board is situated in the connection compartment under the topmost cover.
Figure 1 Connection BoardEMERSON Bettis RTS Extension Board - fig 6

Connecting to Modbus RTU
Recommended Cable Confectioning
Prior to connection the bus lines are to be confectioned as seen in the Figure 2 below:
Figure 2EMERSON Bettis RTS Extension Board - fig 5

The clamps on the connection board are designed for a maximum line cross-section of 1.5 mm 2
. The line diameter has to be in the range of 5 to 8 mm.
Connecting to a Strand between Devices
Other devices are connected to the bus in front and behind of the new Slave-Device.
Line configuration:
Figure 3 EMERSON Bettis RTS Extension Board - fig 4

Connecting at the End of a Strand, Bus Termination
There is either no device connected to the bus in front or behind of the new Slave-Device.
Line configuration:
Figure 4EMERSON Bettis RTS Extension Board - fig 3

Bus termination:
Modbus RTU has to be terminated on both ends of every strand. Termination can be accomplished through the termination resistor implemented in your RTS control unit. Bus termination is activated when the respective switch on the connection board is switched to “ON” as seen in Figure 4 (A. Single Channel).

Explosionproof Design
Normally, in explosionproof design, there is no termination available in the control unit.
That means, the bus termination must be done seperate outside of the control unit.
Optionally, a bus termination in the control unit is possible as well, this must be specified by the order.
In this case, you can activate the bus termination by connecting the following terminals:

  • A with AT and B with BT (single channel version) or
  • A1 with A1T, B1 with B1T, A2 with A2T and B2 with B2T (dual channel version)

WARNING
The shield must be connected to the shielding connection clamp (windowcut), see Figure 5 or Figure 6.
Design with Binary Inputs and Outputs Figure 5EMERSON Bettis RTS Extension Board - FIG 1

  1. Shielding connection clamp
  2. Additional frame
  3. Metallic cable glands (closed with blind screw connections at delivery) 4xM20x1.5
  4. Terminal strip
    Design without Binary Inputs and Outputs Figure 6

EMERSON Bettis RTS Extension Board - FIG

  1. Shielding connection clamp
  2. Terminal strip
    An additional frame with 4xM20 holes is possible on special request.

Section 3: Setup
If Modbus RTU is activated, the following additional parameters will be visible in the control menu of your Bettis Electric Actuator. Each device connected to a Modbus RTU- network has to receive a unique address during setup.
Table 1.

Menu itemSub-itemOptionsExplanation/Comments
P15.1ModbusModbus0: not activeModbus RTU deactivated.
1: activatedModbus RTU activated.
P15.2ModbusAddress Channel A0 bis 247Set the bus address of the first/primary channel.
P15.3ModbusAddress Channel B0 bis 247Set the bus address of the second/secondary channel (only for option “Modbus RTU redundant”).
P15.4ModbusWatchdogtime0.0 -10.0 s [0.0 s]Monitoring period of the togglebit. (Bit 7 in Master’s command). This bit has to toggle in the specified time or a buswatchdog error is detected. If Watchdogtime is set to 0.0 s, the watchdog is deactiveted. Toggling the respective bit can now be ommited.
P15.5ModbusSetpoint Source[0]: StandardSetpoint specified by Modbus RTU (effective only if positioner is activated).
1: Analog.Setpoint specified by analogue signal (effective only if positioner is activated).
2: Bus/AnalogSetpoint specified by Modbus RTU. In case of bus error, setpoint specified by analogue signal (effective only if positioner is activated).
P15.6ModbusStatus 2[0]Standard value for Status 2.
1 – 2Reserved for future use.
P15.7ModbusStatus 3[0]Standard value for Status 3 (current event).
1 – 2Reserved for future use.
P15.8ModbusStatus 4[0]Standard value for Status 4.
1 – 2Reserved for future use.

Section 4: Specification of Input and Output Data

General requirement: Depending on the Master it is possible that the Lowbyte (Bit 0 – 7) and the High byte (Bit 8 – 15) are to be switched. Generally speaking, the mode of transmission (Big Endian / Little Endian) has to be set in a way that ensures the correct transmission of the analogue information. Only after this has been accomplished, the  binary data can be transmitted.

Input Data Modules (Master to Slave Communication)
Input data can be handled with following Modbus functions:
Table 2.

Function

06 (06 hex)Preset Single RegisterWrites data to one single register in the slave.
16 (10 hex)Preset Multiple RegistersWrites data to multiple consecutively registers in the slave.
03 (03 hex)Read Holding RegisterReads back one single register from the slave.
04 (04 hex)Read Input RegisterReads back one single register from the slave.
23 (17 hex)Read/Write Multiple RegistersWrites data to multiple consecutively registers in the slave and reads multiple consecutively  registers from the slave.
If the reading and writing addresses the same  egisters, a read back of the written data is performed. The write operation is performed  before the read operation.

Setpoint
Register number: 1, address 0000Hex
Data format: 16 bit, only the lowest 10 bit (0 – 1023) are in use.
Other bits are reserved for future use and have to be set to zero.
Table 3.

ValueFunctionDescription
0 (0Hex)0%
512 (200Hex)50%
1023 (3ffHex)100%

Command
Register number: 2, address 0001Hex
Data format: 16 bit (Bitfield)
Table 4.

Bit no.FunctionDescription Bit=0 Bit=1
OPENOPEN in REMOTE mode.
1CLOSECLOSE in REMOTE mode.
2STOPSTOP in REMOTE mode.
3EMERGENCY-OPENEMERGENCY-OPEN in REMOTE and LOCAL mode.
4EMERGENCY-CLOSEEMERGENCY-CLOSE in REMOTE and LOCAL mode.
5BLOCKBlocking the actuator in REMOTE and LOCAL mode. Actuator can neither be controlled through the switch on the device nor through commands over REMOTE nor Modbus RTU.
6POSITIONER OFFDeactivating the positioner in REMOTE mode.
7WATCHDOGTogglebit for buswatchdog. Bit has to toggle before specified time-out or a buswatchdog error will be detected.
8OPEN-SHLatched OPEN in REMOTE mode. Release with STOP.
9CLOSE-SHLatched CLOSE in REMOTE mode. Release with STOP.
10LOCK-OPENLocks OPEN (in REMOTE and LOCAL mode)
Actuator carries out a latched OPEN command with highest priority which can only be released with LOCK-OFF, power-off or mode OFF.
11LOCK-CLOSELocks CLOSE (in REMOTE and LOCAL mode)
Actuator carries out a latched CLOSE command with highest priority which can only be released with LOCK-OFF, power-off or mode OFF.
12LOCK-OFFReleases the lock.
13BLOCK LOCALBlocking the actuator in mode LOCAL.
Actuator cannot be moved with selection switch.
14FAILSAFETrigger FAILSAFE-Unit (if available).
15OVERRIDEBinary inputs will not be processed.c

Command 2
Register number: 3, address 0002Hex
Data format: 16 bit (Bitfield)
Table 5.

Mee EQ,Function ,Description
Has (I)Lets T
0Bus Bit 1These binary outputs can be assigned to the bus.
The assignment can be done arbitrarily, including the assignment of a single bit to mulitple outputs. (Available with Firmware 1.323)
1Bus Bit 2
2Bus Bit 3
3Bus Bit 4
4Bus Bit 5_
5Bus Bit 6
6Bus Bit 7
7Bus Bit 8
8reservedReserved for future use
9reserved
10reserved
11reserved
12reserved
13reserved
14reserved
15reserved

Setpoint Revolution Speed
Register number: 4, address 0003Hex
Data format: 16 bit, only the lowest 8 bit (Bit 7: Direction OPEN; Bit 6 – 0 : 0 – 100 corresponding to 0 – 100%) are in use.
Other bits are reserved for future use and have to be set to zero.

Output Data Modules
(Slave to Master Communication)
Output data can be handled with following Modbus functions:
Table 6.
Function

03 (03 hex)Read Holding RegisterReads one single register from the slave.
04 (04 hex)Read Input RegisterReads one single register from the slave.
23 (17 hex)Read/Write Multiple Registers

Actual Position Value
Register number: 257, address 0100 Hex
Data format: 16 bit, only the lowest 10 bits (0 – 1023) are in use.
Other bits are reserved for future use and have to be set to zero.
Table 7.

ValueFunctionDescription
0 (0Hex)0%
512 (200Hex)50%
1023 (3ffHex)100%

Status
Register number: 258, address 0101Hex
Data format: 16 bit (Bitfield)
Table 8.

Bit no.FunctionDescription
Bit = 0Bit=1
0READYActuator is ready.
1END POSITION OPENEnd position mode (torque OPEN reached or travel dependent)).
(under consideration of switch-off
2END POSITION CLOSEEnd position mode (torque CLOSE reached or travel dependent)).
(under consideration switch-off
3TRAVEL OPENEnd travel mode (torque OPEN reached (under or travel dependent)).
consideration of switch-off
4TRAVEL CLOSEEnd travel CLOSE reached (travel dependent).
5TORQUE OPENPower-off torque in opening direction exceeded.
6TORQUE CLOSEPower-off torque in closing direction exceeded.
7MOTORTEMP.Motor temperature sensor signal (overheat).
8OPENINGActuator moving in OPEN direction.
9CLOSINGActuator moving in CLOSE direction.
10LOCALSwitch in LOCAL mode position.
11REMOTESwitch in REMOTE mode position.
12LOCK OPENLatched OPEN command with highest priority. (Refer to Command bit 10 und 12)
13LOCK CLOSELatched CLOSE command with highest priority. (Refer to Command bit 10 und 12)
14LIVEBIT 1Livebitl toggles with 1 Hz.
15LIVEBIT 2Livebit2 is a copy of the watchdog toggle-bit. (Refer to command Bit 7).

Actual Torque Value
Register number: 259, address 0102Hex
Data format: 16 bit, only the lowest 8 bit (Bit 7: Direction OPEN; Bit 6 – 0 : 0 – 100 corresponding to 0 – 100%) are in use.
Other bits are reserved for future use and have to be set to zero.

Actual Speed Value
Register number: 260, address 0103Hex
Data format: 16 bit, only the lowest 8 bit (Bit 7: Direction OPEN; Bit 6 – 0 : 0 – 100 corresponding to 0 – 100%) are in use.
Other bits are reserved for future use and have to be set to zero.

External Actual Value
Only with Option PID-Controller
Register number: 261, address 0104Hex
Data format: 16 bit, only the lowest 10 bit (0 – 1023) are in use.
Other bits are reserved for future use and have to be set to zero.

Status 2
Register number: 262, address 0105Hex
Data format: 16 bit (Bitfield)

Table 9.
Structure 

Bit no.Function
Descripti n
Bit = 0Bit=1
0Dig. Output 1Corresponding binary output enabled.
1Dig. Output 2
2Dig. Output 3
3Dig. Output 4
4Dig. Output 5
5Dig. Output 6
6Dig. Output 7
7Dig. Output 8
8Dig. Input 1Corresponding binary input enabled.
9Dig. Input 2
10Dig. Input 3
11Dig. Input 4
12Dig. Input 5
13PHASE SEQUENCEPhase Sequence Error: wrong phase order, phase failure, total failure, asymmetry.
14FC ERRORFC Error: Error in power supply or frequency converter (if present).
15FAILSAFE ERRORFailsafe-Unit not ready (if present).

NOTE:
Using parameter P15.6 it is possible to assign alternative output-functions to “Status 2”.

Status 3
Register number: 263, address 0106Hex
Data format: 16 bit, error codes
Table 10.

Error CodeCorresponds
3Motor temperature warning.
4Motor temperature power-off.
5Phase order error or phase failure.
9Power supply error or frequency converter error.
11Failsafe-Unit error (if available).
17Travel sensor error.
22Torque sensor error.

NOTE:
Using parameter P15.7 it is possible to assign alternative output-functions to “Status 3”.

Status 4
Register number: 264, address 0107Hex
Data format: 16 bit (Bitfield)
Reserved for future use.
NOTE:
Using parameter P15.8 it is possible to assign alternative output-functions to “Status 4”.

NORTH & SOUTH AMERICA
19200 Northwest Freeway
Houston TX 77065
USA
T +1 281 477 4100
Av. Hollingsworth
325 Iporanga Sorocaba
SP 18087-105
Brazil
T +55 15 3413 8888ASIA PACIFIC
No. 9 Gul Road
#01-02 Singapore 629361
T +65 6777 8211
No. 1 Lai Yuan Road
Wuqing Development Area
Tianjin 301700
P. R. China
T +86 22 8212 3300
MIDDLE EAST & AFRICA
P. O. Box 17033
Jebel Ali Free Zone
Dubai
T +971 4 811 8100
P. O. Box 10305
Jubail 31961
Saudi Arabia
T +966 3 340 8650
24 Angus Crescent
Longmeadow Business Estate East
P.O. Box 6908 Greenstone
1616 Modderfontein Extension 5
South Africa
T +27 11 451 3700EUROPE
Holland Fasor 6
Székesfehérvár 8000
Hungary
T +36 22 53 09 50
Strada Biffi 165
29017 Fiorenzuola d’Arda (PC)
Italy
T +39 0523 944 411

For complete list of sales and manufacturing sites, please visit www.emerson.com/actuationtechnologieslocations or contact us at [email protected]

www.emerson.com/bettis
VCIOM-16741-EN ©2021 Emerson. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co. BettisTM is a mark of one of the Emerson family of companies.
All other marks are property of their respective owners.

The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals