Product Description

The TOSHIBA Air Conditioning VN Unit Heater Controls is a system
designed to control the heating function of VN unit heaters. It
consists of the RBC-VNMC-HE1 Controller and the RBC-VNMH1,
RBC-VNMH2, RBC-VNMH3, and RBC-VNMH4 Duct Heaters. The controller
enables the pre-heater if the temperature falls below a set value
and operates for a fixed period of time. The heater batteries are
available in different sizes and can be used as pre-heaters.

Product Contents

  • RBC-VNMC-HE1 Heater Controller
  • RBC-VNMH1, RBC-VNMH2, RBC-VNMH3, and RBC-VNMH4 Heater
    Batteries
  • Airflow Pressure Switch Installation/Operating Manual
  • Control Panel Installation/Operating Manual

Installation Instructions

  1. The controller must be used with the correct RBC-VNMHX heater
    battery for the selected Heat Exchange unit.
  2. Mount the controller adjacent to the Heat Exchange unit and
    duct heater.
  3. The controller is Class 1 and must be Earthed.
  4. Connect the controller as per the wiring diagram on page
    8.
  5. Connect a remote controller and set the DN codes as
    required.
  6. Set DN Code 67 to the required on temperature (refer to Table
    1).
  7. Set DN Code 68 to the required heater operation time (refer to
    Table 2).

Usage Instructions

  1. To access the DN codes, press the Test Set and Cl buttons on
    the remote controller.
  2. Use the temperature up and down arrows to select the code to be
    modified.
  3. Once the selected code has been updated, press the SET button
    to register the change and then the Spanner button to exit.
  4. When the unit air on sensor reaches the value set in Table 1,
    the heater will be enabled.
  5. The heater will operate for the time set in Table 2. At the end
    of this time, the heater will switch off.
  6. If the unit air on value is still below the set value in Table
    1, the process starts again. If it is above, the heater remains
    off.
  7. If the unit is switched off on the remote controller, the fan
    will run on for approximately 30 seconds.

TOSHIBA
Air Conditioning VN Unit Heater Controls

RBC-VNMC-HE1 Controller

Installation and operating Instructions

3

RBC-VNMH1, 2 ,3 and 4 Duct Heaters

Installation Instructions

4

THE CONFIGERATION CODES AS DETAILED IN THIS MANUAL MUST BE SET FAILURE TO DO THIS COULD
RESULT IN BUILDING DAMAGE

VN Unit Heater Controls Description and Contents
This manual covers the VN unit heater options. Each of the components are ordered and supplied separately.
RBC-VNMC (HE1) Heater Controller
The controller will enable the pre-heater if the temperature falls below the value set in configuration item 67 (Please see the Table 1) the heater will operate for a fixed period of time set in configuration item 68 (Please refer to Table 2). The heater will only operate when the Heat Exchange Unit is operating and will provide a run on time to remove any residual heat if the unit is switched off on the remote controller.
Contents:
Control Panel Installation/Operating Manual.

RBC-VNMH1, RBC-VNMH2, RBC-VNMH3 & RBC-VNMH4 Heat Exchanger unit Heater Batteries

The heater batteries are available in three sizes for use with your selected VN unit. The heater batteries can be used as a pre-heater.

Model
RBC-VNMH1 RBC-VNMH2 RBC-VNMH3
RBC-VNMH4

Heater Size Duct Diameter 1x1Kw Heater 100 1x1Kw Heater 150 2x1Kw Heater 200
2x1Kw Heater 250

VN Model
VN-M150HE VN-U00151SYE VN-M250HE & VN-M350HE VN-U00251SY-E & VN-U00351SY-E VN-M500HE & VN-M650HE VN-U00501SY-E & VN-U00651SY-E VN-M800/1000HE & VN-M1000HE(HE1) VN-U00801SY-E & VN-U01001SY-E

Contents:
Heater Battery. Airflow Pressure Switch Installation/Operating Manual.

2

RBC-VNMC(HE1) Heater Controller Installation Operating Instructions VN-M Units Installation
THE HEATER CONTROLLER AND THE HEAT EXCHANGE UNIT MUST BE SUPPLIED FROM THE SAME PHASE
The controller must be used with the correct RBC-VNMHX heater battery for the selected Heat Exchange unit. The controller should be mounted adjacent to the Heat Exchange unit and duct heater. The controller is Class 1 and must be Earthed.
Connect controller here (CN32)
Connect the controller as per the wiring diagram on page 8
3

DN code Configuration
Connect a remote controller and set the DN codes as required. To access the DN codes Press the Test Set and Cl. You can then press the temperature up and down arrows to select the code to be modified. Once the selected code has been updated press the SET button to register the change and then the Spanner button to exit.
THESE CONFIGERATION CODES MUST BE SET FAILURE TO DO THIS COULD RESULT IN BUILDING DAMAGE
Set DN Code 67 to the required on temperature.

Table 1
Set DN Code 68 to the required heater operation time.

Heater Operation

Table 2

When the unit air on sensor in the unit reaches the value set in (Table 1) the
heater will be enabled. The heater will operate for the time set in (Table 2) at the end of this time the heater will switch off. If the unit air on value is still below the set value in Table 1 the process stars again. if it is above the heater remains OFF. Should the temperature significantly rise the heater will turn off. If the unit is switched off on the remote controller the fan will run on for approximately 30s.

4

RBC-VNMC(HE1) Heater Controller Installation Operating Instructions VN-U Units Installation
THE HEATER CONTROLLER AND THE HEAT EXCHANGE UNIT MUST BE SUPPLIED FROM THE SAME PHASE
The controller must be used with the correct RBC-VNMHX heater battery for the selected Heat Exchange unit. The controller should be mounted adjacent to the Heat Exchange unit and duct heater. The controller is Class 1 and must be Earthed.
Connect controller here (CN610)
Connect the controller as per the wiring diagram on page 8 5

DN code Configuration
Connect a remote controller and set the DN codes as required. To access the DN codes Press the Test Set and Cl. You can then press the temperature up and down arrows to select the code to be modified. Once the selected code has been updated press the SET button to register the change and then the Spanner button to exit.
THESE CONFIGERATION CODES MUST BE SET FAILURE TO DO THIS COULD RESULT IN BUILDING DAMAGE
Set DN Code 67 to the required on temperature.

Table 1
Set DN Code 68 to the required heater operation time.
Table 2
Set DN Code 69 to the required heater run on time. When switched off on the remote controller

Heater Operation

Table 3

When the unit air on sensor in the unit reaches the value set in (Table 1) the heater will be enabled. The heater will operate for the time set in (Table 2) at the end of this time the heater will switch off . If the unit air on value is still below the set value in Table 1 the process stars again. if it is above the heater remains OFF. Should the temperature significantly rise the heater will turn off. If the unit is switched of f on the remote controller the fan will run on for the time set in table 3

6

RBC-VNMH1, RBC-VNMH2 RBC-VNMH3 & RBC-VNMH4 Heat Exchanger unit Heater Batteries
Installation Instructions
The electric heater is of resistance type care should be taken to ensure the heater is correctly mounted in the ductwork system with the terminal box accessible. The heater should not be mounted near to materials that can be damaged by heat. Recommended one-meter minimum of duct before the VN unit.
The heaters are supplied in different sizes depending on the VN unit that has been selected.
The heaters are fitted with two thermal cut-outs. The cut-outs are to be wired in series with the airflow switch. The thermal cut-outs are of the manual reset type and their purpose is to ensure the power supply is disconnected in the event of an over-heat condition.
THE SAFETY CIRCUITS MUST BE CONNECTED, FAILURE TO DO THIS COULD RESULT IN SERIOUS BUILDING DAMAGE.
Wiring
The wiring should be under-taken by a competent electrician taking into account current IEE wiring regulations. The wiring should be in accordance with the supplied wiring diagram on page 6. Local isolation should be included where necessary. It is important that the cables connected to the heaters are insulated with suitable heat protective sleeving.
Air Flow Switch
The airflow switch that is provided is to be connected into the safety circuit as indicated on the wiring diagram on page 6. The airflow pressure switch ensures the heater will not operate without the fan in the VN unit operating. The airflow switch should be set up in accordance with the supplied installation instructions.
7

Wiring diagram

CN 32 / CN610
8

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.