Sensitron Smart3g-c2 Gas Detector Instructions

SMART3G-C2 Gas Detector

Product Information

The SMART3G-C2 gas detector with catalytic sensor is designed to
meet industrial requirements. The enclosure is explosion-proof and
can be installed in ATEX Zone 1 and, when equipped with a dust
adapter, in Zone 21. The sensing element is placed in a stainless
steel head, with two available options: Type head 2 with a 40 mm
diameter and Type head 3 with a 48 mm diameter. The gas detector
utilizes pellistor sensors for flammable gas detection, offering
excellent output linearity up to 100% LEL and fast response
time.

The SMART3G-C2 gas detector has a power supply of 12-24 Vdc and
a standard 4-20 mA 3-wires output. It can also be equipped with
optional serial RS485 communication and a 1 or 3 relays board. The
aluminium enclosure has dimensions of 120 x 162 x 90 mm when
equipped with Type head 2 and 120 x 184 x 90 mm when Type head 3 is
used. The enclosure has 3 cable entries with 3/4 NPT threaded
connections.

The gas detector can be ATEX marked as follows: 0722 II 2G Ex db
IIC T5 Gb. When equipped with a dust adapter, it is SIL2 hardware
and SIL3 software. With a redundant system, the hardware is also
SIL3.

Product Usage Instructions

Sensor:

  • Application: Industrial area, ATEX Zone 1 and
    Zone 21 (when equipped with dust adapter, optional)
  • Sensing element: Catalytic
  • Predicted sensor lifetime: 4 / 5 years
  • Gas detected: Flammable gas
  • Full scale: 0 – 100% LFL

Electrical data:

  • Power supply: 12-24 Vdc
  • Output: Analogue 4-20 mA output; 1 or 3 relay
    board (optional); serial RS485 output (optional)
  • Maximum dissipated power: 5.4 W
  • Relays contact ratings (optional board): 1.0 A
    at 24 Vdc

Environmental conditions:

  • Storage temperature: N/A
  • Operating temperature: N/A
  • Operating humidity: N/A
  • Operating pressure: 80 / 120 kPa *
  • Air velocity: 6 m/s *
  • Time of response: t90 < 60 s; t50 < 20 s
    *

* Data tested with tests described in EN 60079-29-1 standard

External case:

  • Material: Enclosure: aluminium pressure
    die-casting with epoxy paint chromating and chemically resistant;
    Sensor head: stainless steel
  • Protection mode: Ex d: Explosion-proof
    enclosure, Ex t: Equipment dust ignition protection by enclosure
    (when equipped with dust adapter, optional)
  • Dimensions: With Type head 2: 120 x 162 x 90
    mm, With Type head 3: 120 x 184 x 90 mm
  • Weight: With Type head 2: 1050 g, With Type
    head 3: 1250 g
  • Cable entries: 3 x 3/4 NPT
  • IP grade: IP65

Compliance:

  • EMC: EN 61000-6-3:2007 + A1:2011; EN 50270:2015
  • ATEX directive: 2014/34/EU EN IEC 60079-0:2018 EN 60079-1:2014
    EN 60079-31:2014 EN 60079-29-1:2016
  • IECEx: IEC 60079-0:2011 IEC 60079-1:2014 IEC 60079-31:2013
  • SIL: EN 61508:2010 Parts 1, 2, 3, 4, 5, 6, 7 EN50402:2017

Note: Sensitron srl reserves the right to change technical data
without notice. For updated product characteristics, please check
the website www.sensitron.it or contact [email protected].

Product Codes:

  • ATEX code: S2097ME Methane gas detector, 12-24 Vdc

For more information and inquiries, please contact Sensitron srl
at the following:

Address: Viale della Repubblica 48, Cornaredo (MI) – 20007

Email: [email protected]

Telephone: +39 0293548155

Fax: +39 0293548089

SMART3G-C2
with catalytic sensor

SMART3G-C2 gas detector is designed to meet industrial requirements; the enclosure is explosion proof and can be installed in ATEX Zone 1 and, when equipped with dust adapter, in Zone 21.
The sensing element is placed in the stainless steel head. Sensitron has developed two type heads with different dimensions: the model “Type head 2” has a 40 mm diameter, the “Type head 3″ version has a 48 mm diameter. The pellistor sensors employed for the flammable gas detection show an excellent output linearity up to 100% LEL and fast time of response.
The gas detector has a 12-24 Vdc power supply and a standard 4-20 mA 3-wires output. Optionally, the SMART3G-C2 can be equipped with serial RS485 communication and a 1 or 3 relays board.
The aluminium enclosure has dimensions 120 x 162 x 90 mm when equipped with type head 2, 120 x 184 x 90 mm when the head type 3 is used. The enclosure has 3 cable entries 3/4″ NPT threaded.
The gas detector can be ATEX marked as follows:
0722 II 2G Ex db IIC T5 Gb Or, when equipped with dust adapter:
0722 II 2GD Ex db IIC T5 Gb Ex tb IIIC T100°C Db IP65
The gas detector is IECEx compliant and can be marked as follows: Ex db IIC T5 Gb Or, when equipped with dust adapter: Ex db IIC T5 Gb Ex tb IIIC T100°C Db IP65
SMART3G-C2 is SIL2 hardware and SIL3 software; with a redundant system also the hardware is SIL3.

Sensor

Application

Industrial area, ATEX Zone 1 and Zone 21 (when equipped with dust adapter, optional)

Sensing element

Catalytic

Predicted sensor lifetime

4 / 5 years

Gas detected

Flammable gas

Full scale

0 – 100% LFL

Electrical data

Power supply

12-24 Vdc

Output

Analogue 4-20 mA output; 1 or 3 relay board (optional); serial RS485 output (optional)

Maximum dissipated power 5.4 W

Relays contact ratings (op- 1.0 A at 24 Vdc tional board)

Optical indications

Acoustic indications

Hall effect sensor

Environmental conditions

Storage temperature

-40 / +85°C

Operating temperature

-40 / +60°C * with type head 3 -20 / +60°C * with type head 2 codes with -HT have Tmax=70°C

Operating humidity

20 / 90% RH @40°C *

Operating pressure

80 / 120 kPa *

Air velocity

6 m/s *

Time of response

t90 < 60 s ; t50 < 20 s *

* Data tested with tests described in EN 60079-29-1 standard

External case Material
Protection mode
Dimensions Weight Cable entries IP grade Compliance EMC ATEX
IECEx
SIL

Enclosure: aluminium pressure die-casting with epoxy paint chromating and chemically resistant Sensor head: stainless steel
Ex d : Explosion proof enclosure Ex t : Equipment dust ignition protection by enclosure (when equipped with dust adapter, optional)
With type head 2: 120 x 162 x 90 mm With type head 3: 120 x 184 x 90 mm
With type head 2: 1050 g With type head 3: 1250 g
3 x 3/4” NPT
IP65
EN 61000-6-3:2007 + A1:2011; EN 50270:2015
ATEX directive 2014/34/EU EN IEC 60079-0:2018 EN 60079-1:2014 EN 60079-31:2014 EN 60079-29-1:2016
IEC 60079-0:2011 IEC 60079-1:2014 IEC 60079-31:2013
EN 61508:2010 Parts 1, 2, 3, 4, 5, 6, 7 EN50402:2017

Sensitron srl works for a constant improvement of its products and reserves the right to change the technical data without notice. To have the updated product characteristics check on the website www. sensitron.it or write an e-mail to [email protected]

DS4737E R6 11/03/2022
Sensitron srl, Viale della Repubblica 48, Cornaredo (MI) – 20007 [email protected]
TEL. +39 0293548155 FAX. +39 0293548089

SMART3G-C2
with catalytic sensor

Product codes

ATEX code

S2097ME Methane gas detector, 12-24 Vdc

ST / L / E3 / S2

S2097GP LPG gas detector, 12-24 Vdc

ST / L / E3 / S2

S2097PR Propane gas detector, 12-24 Vdc

ST / L / E3 / S2

S2097BU Butane gas detector, 12-24 Vdc

ST / L / E3 / S2

S2097VB Petrol vapours gas detector, 12-24 Vdc

ST / L / E3 / S2

S2097AA Acetic acid gas detector, 12-24 Vdc

ST / L / E3 / S2

S2097AT Acetone gas detector, 12-24 Vdc

ST / L / E3 / S2

S2097AB Butyl acetate gas detector, 12-24 Vdc

ST / L / E3 / S2

S2097BT Butyl alchol gas detector, 12-24 Vdc

ST / L / E3 / S2

S2097CE Ciclohexane gas detector, 12-24 Vdc

ST / L / E3 / S2

S2097CP Ciclopentane gas detector, 12-24 Vdc

ST / L / E3 / S2

S2097EN Ethane gas detector, 12-24 Vdc

ST / L / E3 / S2

S2097AE Ethyl acetate gas detector, 12-24 Vdc

ST / L / E3 / S2

S2097ET Ethyl alcohol gas detector, 12-24 Vdc

ST / L / E3 / S2

S2097EE Ethyl ether gas detector, 12-24 Vdc

ST / L / E3 / S2

S2097EL

Ethylene gas detector, 12-24 Vdc

ST / L / E3 / S2

S2097EP Heptane gas detector, 12-24 Vdc

ST / L / E3 / S2

S2097ES Hexane gas detector, 12-24 Vdc

ST / L / E3 / S2

S2097H2 Hydrogen gas detector, 12-24 Vdc

ST / L / E3 / S2

S2097IB

Isobutane gas detector, 12-24 Vdc

ST / L / E3 / S2

S2097IT

Iso butyl alcohol gas detector, 12-24 Vdc

ST / L / E3 / S2

Mechanical drawings

90,3 mm

ATEX code ST / L / E3 /S3
130 mm

120 mm

Product codes

S2097IN

Iso pentane gas detector, 12-24 Vdc

S2097IP

Iso propyl alcohol gas detector, 12-24 Vdc

S2097MT Methyl alcohol gas detector, 12-24 Vdc

S2097MK Methyl ethil ketone gas detector, 12-24 Vdc

S2097NN Nonane gas detector, 12-24 Vdc

S2097PE Pentane gas detector, 12-24 Vdc

S2097PP Propylene gas detector, 12-24 Vdc

S2097PN Propyl alcohol gas detector, 12-24 Vdc

S2097TM Tri-methylbenzene gas detector, 12-24 Vdc

S2097TO Toluene gas detector, 12-24 Vdc

S2097XI

Xylene gas detector, 12-24 Vdc

S2151AC Acetylene gas detector, 12-24 Vdc

S2155AA Acetic acid gas detector, 12-24Vdc

S2155AM Ammonia gas detector, 12-24 Vdc

S2155BZ Benzene gas detector, 12-24 Vdc

S2155OE Ethylene oxide gas detector, 12-24 Vdc

S2154P8 JP8 gas detector, 12-24 Vdc

S2155ST

Styrene gas detector, 12-24 Vdc

S2155AV Vinyl acetate gas detector, 12-24 Vdc

S2155AF Formaldehyde gas detector, 12-24 Vdc

S2155CO Carbon monoxide gas detector, 12-24Vdc

ATEX code ST / L / E3 / S2 ST / L / E3 / S2 ST / L / E3 / S2 ST / L / E3 / S2 ST / L / E3 / S2 ST / L / E3 / S2 ST / L / E3 / S2 ST / L / E3 / S2 ST / L / E3 / S2 ST / L / E3 / S2 ST / L / E3 / S2 ST / L / E3 / S3 ST / L / E3 / S3 ST / L / E3 / S3 ST / L / E3 / S3 ST / L / E3 / S3 ST / L / E3 / S3 ST / L / E3 / S3 ST / L / E3 / S3 ST / L / E3 / S3 St / L / E3 / S3

ATEX code ST / L / E3 /S2
130 mm
120 mm

25 mm

25 mm

81,4 mm 115 mm
162 mm

81,4 mm 40 mm
115 mm

13 mm
183,9 mm 13 mm

21 mm

130 mm

130 mm

STG/AD3 Dust adapter

20 mm

47,5 mm

19 mm

39,9 mm

STG/AD2 Dust adapter

21 mm

40 mm

48 mm

Sensitron srl works for a constant improvement of its products and reserves the right to change the technical data without notice. To have the updated product characteristics check on the website www. sensitron.it or write an e-mail to [email protected]

DS4737E R6 11/03/2022

20 mm

Sensitron srl, Viale della Repubblica 48, Cornaredo (MI) – 20007 [email protected]
TEL. +39 0293548155 FAX. +39 0293548089

19 mm

mm

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals