Proee Pe-r Hf Rectifier Module 24v-60a User Manual

Proee Pe-r Hf Rectifier Module 24v-60a User Manual

ProEE-logoProEE PE-R HF Rectifier Module 24V-60AProEE-PE-R-HF-Rectifier-Module-24V-60A-productElectrical Specifications

Input Feature

InputSingle input
Input Voltage Range90Vac to 290Vac
Rate input Voltage110Vac / 220Vac
Normal Input100Vac to 240Vac
Frequency Range45Hz-65Hz
Max Input Current10.2A±10%@176Vac/1800W
Surge CurrentCompliant Standard:ETSI300132-3
Efficiency≥90%@220Vac@ 220Vac 100% load
PF≥0.99@220Vac/60A
Leakage Current<3.5mA@264Vac
Input FuseL Wire ,Fuse 25A
Max input Voltage310Vac

Output Feature

Output voltage current regulation

Output Voltage+24Vdc
Output Voltage Regulation+24±0.1Vdc
Output Range adjustable Range+21Vdc~+29Vdc
Load sharing(50%~100% Loading)≤±5%
Line regulation±0.1%
Load regulation±0.5%
Voltage precision±0.6%
Min-current0A
Rate current60A
Peaking current65A
Tempe. coefficient(1/℃)≤±0.02%
Rate Capacity1800W(150Vac~290Vac)

1200W(90Vac~150Vac)

Note: The rectifier module output current regulation and communication interruption are as follows:

  1. The output current of the rectifier module can be adjusted according to the current command. The adjustment range is 1A~60A.
  2. Communication fault more than 1 minute (Rectifier and Control monitor),A .Rectifier module output Voltage automatic recovery default Voltage 24V and limited current function not working;b.if the rectifier modules are controller by monitor and Power off, then rectifier system will power on(if the rectifier fault, it can not be turned on again)

Efficiency FigureProEE-PE-R-HF-Rectifier-Module-24V-60A-fig-1

Output ripple and noise

Output VoltageRipple and Noise (Peaking-Peaking)
+24Vdc200mVp-p@ 25℃,(Testing based on rate Input voltage    & Output Voltage ,100%

loading )

Note:Ripple and Noise testing:Ripple and noise Default as 20 MHz

Output dynamic response

Voltage

overshoot

Adjustment

slope

LoadingVoltage

overshoot

 

+24V±5%

 

0.1A/uS

25% to 50% load

50% to 75%load

 

≤200us

Note:Adjustment slope Cycle 4ms

Output Overshoot

Output VoltageOvershoot Voltage
Onoff
+24V≤5%≤5%

Note: Loading Range Minimum to maximum

Power Switch Point

Rated Switching PointMin-Switching PointMax-Switching Point
150Vac145Vac160Vac

ProEE-PE-R-HF-Rectifier-Module-24V-60A-fig-2

Power on output delay time

Output Voltage220Vac@25℃
+24V3S~10S

Note: The power-on delay time is the time from AC power-on to output voltage (to 23VDC)

LED indicator 

The power LED is installed on the power panel side and the output status is shown in the table below

IndicatorLED ColorNormalStatusAbnormal statusAbnormal Reasons
Power running indicatorsGreenOnoff 
 

 

Protect indicators

 

 

Yellow

 

 

Off

 

 

on

Temperature pre-alarm (working    temperature more than 65 °C ,then over temperature shutdown); Sleep shutdown (the module only lights the
    protection indicator when the system is shut down, and the module does not report alarm).
 

Fault Indicator

 

Red

 

Off

 

on

Output Over voltage power off 、

Fan fault、Over-Temp. Power off Rectifier module inner fault。

Noise Voltage

Noise VoltageMaxNote
Phone noise weighting

Voltage

≤2mV 
 

broadband noise Voltage

≤50mV3.4~150KHz
≤20mV0.15~30000KHz
Radio interference noise, or radio frequency noise≤5mV3.4~150KHz
≤3mV150~200KHz
≤2mV200~500KHz
≤1mV500~30000KHz

Rectifier module and monitor module communication function

RS485 communication mode (half-duplex, double-line) is adopted between the rectifier module and the monitoring module.
The RS485 interface in the rectifier module needs to be isolated. The RS485 power supply is +5Vdc (regulation accuracy ±5%), which is provided by the monitoring module.
The main monitoring information of the rectifier module is:

  1. Adjust Voltage and Current function: meet the requirements of battery floating charge and meet the adjust voltage requirements;
  2. Single module switch machine control;
  3. Alarm information:
    • Mains failure: mains failure (AC input over voltage);
    • Module protection: temperature pre-alarm;
    • Module failure: Output over voltage shutdown, fan failure, over temperature shutdown or no output caused by internal causes of other modules; (module is in: sleep shutdown state, mains failure does not report module failure).

Protection Function

Output Limited Current Protection

Output VoltageLimited Current

point

Note
+24V105%~110%Limited current output

Output short circuit Protection

Output VoltageNote
+24VRestart after Protection

Output Over Voltage Protection

Output VoltageProtection Point
+24V33±2V. (Lock)

Note: After entering the lock protection state, you need to disconnect the AC power first, and then re-power on, the rectifier module can be re-operated.

Input Over Voltage Protection

Input VoltageNote
310±10VacOutput off,Self-recovery after normal voltage
 output recovery point backlash>10V

Note: Input overvoltage protection should be tested at 50A rated load

Input under Voltage Protection

Input VoltageNote
80±5VacOutput is closed. Self-recovery after

normal Voltage

 Output Recovery point backlash>5V

Over -Temp.Protection

Temp.Note
≤55℃With maximum output Capacity ability , without

over-temperature protection and the module is running normally.

55℃~65℃The module can be automatically derate to ensure long-term stable output of at least 50% of rated power
>65℃Power off,After power off,Recovery temperature difference    >10℃

Insulation Performance

Insulation resistance

Input & outputTesting     voltage     500VDC,Insulation Resistance ≥10M

(normal atmospheric pressure, normal temperature, relative humidity <90%,

no condensation)

Input & ground
Output & ground

Isolation Voltage

Input & outputDC Voltage 4240Vdc1minute ≤30mA
Input & groundDC Voltage 2120Vdc1minute ≤30mA
Output & groundDC Voltage 710Vdc1minute ≤30mA

Safety standard

Power supply safety meets the following standards:
GB4943-2001

EMC

EMI

  1. Compliant with the the Below Standard:
    Conduction Emission :
    *EN55022/GB9254, CLASS A
  2. Radiated Emission :
    *EN55022/GB9254, CLASS A

EMS
The power supply shall compliance with the following Criterion:

  1. ESD
    *GB17626.2/IEC61000-4-2
    • the Chassis, the parts that can be touch during normal operation: contact discharge +/-6KV; air discharge +/-8KV, Criterion B (power on test)。
    • the Chassis , the parts that can be touch during normal operation: contact discharge +/-8KV; air discharge +/-10KV,Criterion R (not powered during test)。
    • signal interface inner conductor: contact discharge +/- 2KV Criterion R; (power on test, no test on address line and current line)
  2. EFT
    *GB17626.4/IEC61000-4-4 Level 3 Standard: A
  3. SURGE
    *GB17626.5/IEC61000-4-5 Level 4 Standard: B
  4. DIP
    *GB17626.11/IEC61000-4-11
    Power DIP voltage drop requirement Table (220Vac)
Drop toDrop PhaseDrop

Time

Standard
0%Ut0°/45°/90°/135°/180°/225°/270°/315°10msB
40%Ut0°/45°/90°/135°/180°/225°/270°/315°20msB
70%Ut0°/45°/90°/135°/180°/225°/270°/315°100msB

Input harmonic current
*IEC 61000-3-2 [6] CLASS A

voltage fluctuations and flicker
*IEC 61000-3-3
Pst≤1.0;P1t≤0.65;dc≤3%;dmax≤4%;d(t) more than 3% time≤200ms

lightning test
In the system application, the AC input can withstand the impact current
waveform of n more than 5 kA, 8/20us, positive and negative 5 times, each
interval of 1 minute (see standard: YD 5098-2001)

Immunity to conducted disturbances
*IEC61000-4-6 Level 3 Standard:A

Radiated interference
*IEC61000-4-3 Level 3 Standard:A

Testing Standard:

A: The power supply did not have any degradation in performance throughout the test, and it was completely the same as the specifications specified in the power supply specification.
B: During the test, the performance of the power supply is allowed to temporarily decrease, but it can be restored after the test is over.
C: A short-term loss of function is allowed, but the end of the test can be restored automatically or manually.
R: Damage to other devices other than the fuse device is not allowed during the test.

Working Environment

Ambient Temperature

  • Working Temp.:-40℃to +55℃.
  • Storage Temp: -40℃to +70℃.
  • Transport Temp: -40℃to +70℃.

Relative Humidity

  • Working RH: 5%~95% (No condensation)
  • Storage RH: 5%~ 95% (No condensation)

Altitude

  • working Altitude:0~4000M,based 2000m,For every 200 m increase in altitude, the temperature drops by 1℃
  • Storage Altitude :0~4000M,based 2000m,For every 200 m increase in altitude, the temperature drops by 1℃

Cooling

*The rectifier module with fan, forced air cooling, air is sent out after the wind is coming forward, the fan is placed in the front, and the fan has temperature control speed regulation function.

Vibrate Tolerance

  • Working environment: sinusoidal vibration: 5~9Hz: amplitude 3.5mm; 9~200Hz: acceleration 10m/s2; 3 axial direction, sweeping vibration 5 times in each direction, 1OCT/min (1 octave/min).
  • Transportation environment: random vibration: 2~10Hz: 10m2/s3; 10~200Hz: 3m2/s3; 200~500Hz: 1m2/s3;3 axial, 30min in each direction.
    (Reference standard: ETS300019-2)

Impact Tolerance

  • Working environment: acceleration 250m / s2; pulse width 6ms; 3 axes 6 to each collision 500 times.
  • Transportation environment: acceleration 400m / s2; pulse width 6ms; 3 axes 6 to each collision 500 times.
    (Reference standard: ETS300019-2)

Drop
Transportation environment: drop height 1m; bottom surface 1 time.
(Reference standard: ETS300019-2)

Size

H×W×D: 83.8mm×112mm×257mmProEE-PE-R-HF-Rectifier-Module-24V-60A-fig-3

N.Weight: <4.8kg

Chassis IP Protection Level
IP20(User normal maintenance operation surface)

Transportation and storage

The product should be placed in a warehouse that is affected by dry, ventilated and non-corrosive gases with a temperature of -10 ° C to 40 ° C and a relative humidity of not more than 80%.
The product has a strong packaging when transported. The outside of the box complies with the relevant national standards and should have signs such as “careful handling” and “moisture proof”. The box containing the product is allowed to be transported by any means of transport. Direct rain and snow strikes and mechanical impacts should be avoided during transportation.

Other Requirement

ItemRequirementNote
noiseLess than 55dBa 
odornot produce odor and harmful odor 
ComponentsAll devices meet the de-rating 
Hot swapRectifier module for hot swap 
Failure isolationAfter the rectifier module fails, it can

be reliably separated from the system.

 

MTBF

1*105h;25℃,Rate Input,100% loading.

Connector PIN Definition

 PinSignalRemarkContact

sequence

AC input1Rectifier module AC inputL2
2Rectifier module protection GroundPE1
 3Rectifier module AC inputN2
 
 

DC

output and

1Rectifier module address wireADDRES

S0

3
2Rectifier module address wireADDRES

S1

3
3Rectifier module share current wireLOADS

HARE+

3
Signal4Rectifier forbiddenINHIBIT4
     CURRE NT

LIMIT

 
 5Rectifier

function

outputlimitedcurrent3
 6Rectifier functionoutputlimitedcurrentCURRE NT

LIMIT

3
 7Rectifier address wireADDRES

S2

3
 8Rectifier address wireADDRES

S3

3
 9Rectifier address wireLOADS

HARE-

3
 

 

DC

output

10RS485 Power ++3.3V/+

5V

3
11RS485 Power-+3.3V/+

5VGND

3
12Rectifier communication    wireRS485-3
and Signal
13Rectifier address wireADDRES

S4

3
14NCNC3
 15Rectifier communication    wireRS485+3
 16Address Wire GNDADDR_G

ND

3
     
 As

Figure

Pre- chargePre-Cha

rge

1
 As

Figure

Rectifier output 48V+DC+2
 As

Figure

Rectifier output 48V+DC+2
 As

Figure

Rectifier output 48V-DC-2
 As

Figure

Rectifier output 48V-DC-1

Block address definition:

The module internally pulls up the address line. ADDRESS0~4 can be left floating outside the module or shorted to the address line GND.
Shorting means “1”, floating means “0”, such as ADDRESS0 external and address If the line GND is shorted and the other address lines are left floating, the rectifier module address is

  1. The address range of the rectifier module is 0 to 31.。ProEE-PE-R-HF-Rectifier-Module-24V-60A-fig-4
  2. Pre-Charge pin is used to pre-charge the output capacitor inside the rectifier module when the rectifier module is hot swapped.。

Product Maintenance

  1. Product free maintenance time
    The free maintenance level of this product is Class B, and the free maintenance period (warranty period) is 1 year.
  2. On-site maintenance
    The power module has a hot swap function, and the on-site repair mode is module replacement.

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals