Kanion Qsytd-002u One Five Split Type Air Conditioner Owner's Manual

QSYTD-002U One Five Split Type Air Conditioner

INVERTER ONE-TWO/ONE-THREE/ONE-FOUR/ONE-FIVE SPLIT-TYPE AIR
CONDITIONER

Owner’s Manual

Table of Contents

  1. Safety Precautions
  2. Unit Parts and Major Functions
  3. Manual Operation and Maintenance
  4. Troubleshooting
    • Common Problems
    • Troubleshooting Tips
  5. European Disposal Guidelines

Caution: Risk of fire (for R32/R290 refrigerant
only)

WARNING: Servicing shall only be performed as
recommended by the equipment manufacturer. Maintenance and repair
requiring the assistance of other skilled personnel shall be
carried out under the supervision of the person competent in the
use of flammable refrigerants. For more details, please refer to
the Information on servicing on INSTALLATION MANUAL. (This is only
required for the unit adopts R32/R290 Refrigerant)

Product Introduction

The INVERTER ONE-TWO/ONE-THREE/ONE-FOUR/ONE-FIVE SPLIT-TYPE AIR
CONDITIONER is a cooling and heating system that consists of an
indoor unit and an outdoor unit. It is designed to provide
efficient and comfortable temperature control for residential and
commercial spaces.

Safety Precautions

Please follow the safety precautions listed below to ensure
proper operation and avoid injury or equipment damage:

  1. The appliance must be installed in accordance with national
    regulations.
  2. Do not operate the unit with wet hands.
  3. Do not block the air inlet or outlet of the unit.
  4. Do not use the unit for special purposes, such as preserving
    foods, animals, plants, or precision instruments.
  5. Do not touch the aluminum fins of the unit with sharp
    objects.
  6. Do not use flammable substances near the unit.

Unit Parts and Major Functions

The INVERTER ONE-TWO/ONE-THREE/ONE-FOUR/ONE-FIVE SPLIT-TYPE AIR
CONDITIONER has different types of indoor units (wall-mounted,
duct/ceiling, floor and standing, compact four-way cassette), but
they all have similar parts and functions:

  • Indoor unit:
    • Panel frame
    • Rear air intake grille
    • Front panel
    • Air purifying filter & Air filter (behind)
    • Horizontal louver
    • LCD display window
    • Vertical louver
    • Manual control button (behind)
    • Remote controller holder
    • Air outlet (for some types)
    • Air inlet (for some types)
    • Air flow louver (for some types)
    • Remote controller (for some types)
    • Installation part (for some types)
    • Air-in grill (for some types)
    • Drain pump (for some types)
    • Drain hose (for some types)
    • Display panel (for some types)
  • Outdoor unit:
    • Drain hose, refrigerant connecting pipe
    • Connective cable
    • Stop valve
    • Fan hood
    • Electric control cabinet (for some types)
    • Wire controller (for some types)
    • Refrigerant connecting pipe (for some types)

Product Usage Instructions

Please follow the instructions below to operate and maintain
your INVERTER ONE-TWO/ONE-THREE/ONE-FOUR/ONE-FIVE SPLIT-TYPE AIR
CONDITIONER:

  1. Install the unit according to national regulations.
  2. Turn on the power and select the desired mode (cooling or
    heating) and temperature using the remote controller or manual
    control button.
  3. Clean the air filters regularly to maintain proper airflow and
    prevent dust accumulation.
  4. If there is abnormal noise, vibration, or odor from the unit,
    turn off the power immediately and contact a qualified technician
    for inspection and repair.
  5. If you need to dispose of the unit, follow the European
    Disposal Guidelines or national regulations for proper
    disposal.

INVERTER ONE-TWO/ONE-THREE/ONE-FOUR/ONE-FIVE SPLIT-TYPE AIR CONDITIONER
Ow ner’s M anual
IMPORTANT NOTE: · Read this manual carefully before installing or
operating your new air conditioning unit. Make sure to save this manual for future reference. · This manual only describes the outdoor unit of user’s. When using the indoor unit,refer to the user’s manual of indoor unit.

Table of Contents
Owner’s Manual

1 Safety Precautions …………………………………………….

04

2 Unit Parts and Major Functions ……………………. 06 3 Manual Operation and Maintenance ………….. 10

4″‘&5: ‘*345

4 Troubleshooting…………………………… 11
Common Problems …………………………… 11 Troubleshooting Tips …………………………. 13

5 European Disposal Guidelines ……………………………………………………..

14

Caution : Risk of fire
(for R32/R290 refrigerant only )
WARNING: Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants. For more details ,please refer to the Information on servicing on INSTALLATION MANUAL .(This is only required for the unit adopts R32/R290 Refrigerant)

GenSaefreatl y IntProredcuacuttioionns

Safety Precautions

1

Thank you for purchasing this air conditioner. This manual will provide you with information on how to operate, maintain, and troubleshoot your air conditioner. Following the instructions will ensure the proper function and extended lifespan of your unit.
Please pay attention to the follow ing signs:

WARNING CAUTION

Failure to observe a warning may result in death. The appliance must be installed in accordance with national regulations.
Failure to observe a caution may result in injury or equipment damage.
5IJTTZNCPMJOEJDBUFTUIBUZPVNVTUOFWFSQFSGPSNUIFBDUJPOJOEJDBUFE

WARNING
· Ask an authorized dealer to install this air conditioner. Inappropriate installation may cause water leakage, electric shock, or fire.
· The warranty will be voided if the unit is not installed by professionals.
· If abnormal situation arises (like burning smell), turn off the power supply and call your dealer for instructions to avoid electric shock, fire or injury.
· DO NOT let the indoor unit or the remote control get wet. It may cause electric shock or fire.
· DO NOT insert fingers, rods or other objects into the air inlet or outlet. This may cause injury, since the fan may be rotating at high speeds.
· DO NOT use a flammable spray such as hair spray, lacquer or paint near the unit. This may cause fire or combustion.
· Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
· The appliance shall be stored so as to prevent mechanical damage from occurring.
· Be aware that the refrigerants may not contain an odour.
Page 4

· Compliance with national gas regulations shall be observed.
· Keep ventilation openings clear of obstruction.
· DO NOT pierce or burn.
· A warning that the appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation.
· Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry-accredited assessment authority, which authorises their competence to handle refrigerants safely in accordance with an industry recognised assessment specification.
· Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants.
· The appliance shall be installed in accordance with national wiring regulations. (In North America,installation must be performed in accordance with the requirement of NEC and CEC by authorized personnel only.)

Saf et y Precaut ions

CAUTION
· DO NOT touch the air outlet while the swing flap is in motion. Fingers might get caught or the unit may break down.
· DO NOT inspect the unit by yourself. Ask an authorized dealer to perform the inspection.
· To prevent product deterioration, do not use the air conditioner for preservation purposes (storage of food, plants, animals, works of art, etc.).
· DO NOT touch the evaporator coils inside the indoor unit. The evaporator coils are sharp and may cause injury.
· DO NOT operate the air conditioner with wet hands. It may cause electric shock.
· DO NOT place items that might be affected by moisture damage under the indoor unit. Condensation can occur at a relative humidity of 80%.
· DO NOT expose heat-producing appliances to cold air or place them under the indoor unit. This may cause incomplete combustion or deformation of the unit due to the heat.
· After long periods of usage, check the indoor unit to see if anything is damaged. If the indoor unit is damaged, it may fall and cause injury.
· If the air conditioner is used together with other heating devices, thoroughly ventilate the room to avoid oxygen deficiency.
· DO NOT climb onto or place objects on top of the outdoor unit.
· DO NOT operate the air conditioner when using fumigant insecticides. The chemicals may become layered with the unit and endanger those who are hypersensitive to chemicals.
· DO NOT let children play with the air conditioner.
· DO NOT operate the air conditioner in a wet room (e.g. bathroom or laundry room). This can cause electrical shock and cause the product to deteriorate.

· This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.

Page 5

Unit Parts And M ajor Funct ions

Unit Parts And M ajor Functions

2

Unit Parts Wall-mounted type

Duct / Ceiling type

Fig. 2.1
Indoor unit 1. Panel frame 2. Rear air intake grille 3. Front panel 4. Air purifying filter & Air filter(behind) 5. Horizontal louver 6. LCD display window 7. Vertical louver 8. Manual control button(behind) 9. Remote controller holder Outdoor unit 10. Drain hose, refrigerant connecting pipe 11. Connective cable 12. Stop valve 13. Fan hood
Page 6

Fig. 2.2
Indoor unit 1. Air outlet 2. Air inlet 3. Air filter 4. Electric control cabinet 5. Wire controller Outdoor unit 6. Drain hose, refrigerant connecting pipe 7. Connective cable 8. Stop valve 9. Fan hood

Floor and standing type(console)

Compact four-way cassette type

Unit Parts And M ajor Funct ions

Fig. 2.3
Indoor unit 1. Air flow louver (at air outlet) 2. Air inlet (containing air filter) 3. Remote controller 4. Installation part 5. Display panel Outdoor unit 6. Drain hose, refrigerant connecting pipe 7. Connective cable 8. Stop valve 9. Fan hood

Fig. 2.4 Indoor unit 1. Drain pump(drain water from indoor unit) 2. Drain hose 3. Air outlet 4. Air inlet 5. Air-in grill 6. Display panel 7. Remote controller Outdoor unit 8. refrigerant connecting pipe 9. Connective cable 10. Stop valve 11. Fan hood
Page 7

Unit Parts And M ajor Funct ions

NOTE: For multi-split type air conditioners, one outdoor unit can be matched to different types of indoor units. All of the pictures in this manual are for demonstration purposes only. Your air conditioner may be slightly different, if similar in shape. The following pages introduce several kinds of indoor units that can be matched with the outdoor units.

Operating Conditions
Use the system under the following temperatures for safe and effective operation. If the air conditioner is used under different conditions, it may malfunction or become less efficient.

Indoor Temperat ure Outdoor Temperat ure

COOL M ode
17°C-32°C(63°F-90°F)
0°C-50°C (32°F-122°F) -15°C-50°C (5°F-122°F)
(For models with low-temp cooling systems)
0°C-52°C (32°F-126°F)
(For special tropical models)

HEAT mode 0°C-30°C (32°F-86°F)
-15°C-30°C (5°F-86°F)

DRY mode 10°C-32°C(50°F-90°F)
0°C-50°C (32°F-122°F)
0°C-52°C (32°F-126°F)
(For special tropical models)

Feat ures

Protection of the air conditioner Compressor protection · The compressor cannot restart for 3 minutes
after it stops. Anti-cold air (Cooling and heating models only) · The unit is designed not to blow cold air on

White mist emerging from the indoor unit
· A white mist may be generated due to a large temperature difference between air inlet and air outlet on COOL mode in places with high relative humidity.
· A white mist may be generated due to moisture

HEAT mode, when the indoor heat exchanger

created in the defrosting process when the air

is in one of the following three situations and

conditioner restarts in HEAT mode operation

the set temperature has not been reached.

after defrosting.

A) When heating has just started.

B) During defrosting.

Noise coming from the air conditioner

C) Low temperature heating.

· You may hear a low hissing sound when the

· The indoor or outdoor fan stop running when

compressor is running or has just stopped

defrosting (Cooling and heating models only).

running. This sound is the sound of the

Defrosting (Cooling and heating models only) · Frost may be generated on the outdoor unit

·

refrigerant flowing or coming to a stop. You may also hear a low “squeaking” sound

during a heat cycle when outdoor temperature

when the compressor is running or has just

is low and humidity is high resulting in lower heating efficiency in the air conditioner. · Under these conditions, the air conditioner will stop heating operations and start defrosting automatically. · The time to defrost may vary from 4 to 10

stopped running. This is caused by tempera
heat expansion and cold contraction of the
plastic parts in the unit when the temperature
is changing. · A noise may be heard due to the louver

minutes, depending the outdoor temperature

restoring itself to its original position when

and the amount of frost buildup on the

power is first turned on.

outdoor unit. Auto-Restart (some models) In case of power failure, the system will immediately stop. When power returns, the

Dust blow ing out from the indoor unit.
This is happens when the air conditioner has not been used for a long time or during its first use.

Operation light on the indoor unit will flash. To restart the unit, press the ON/ OFF button on the remote control. If the system has an auto restart function, the unit will restart using the same settings.

Smell emitting from the indoor unit.
This is caused by the indoor unit giving off smells permeated from building materials, furniture,or smoke.

Page 8

Unit Parts And M ajor Funct ions

The air conditioner turns to FAN ONLY mode from COOL or HEAT (for cooling and heating models only) mode.
When the indoor temperature reaches the set temperature setting, the compressor will stop automatically, and the air conditioner turns to FAN only mode. The compressor will start again when the indoor temperature rises on COOL mode or falls on HEAT mode to the set point.
Droplets of water may form on the surface of the indoor unit when cooling occurs in relatively high humidity (defined as higher than 80%). Adjust the horizontal louver to the maximum air outlet position and select HIGH fan speed.

Heating mode (For cooling and heating models only)
The air conditioner draws in heat from the outdoor unit and releases it via the indoor unit during heating. When the outdoor temperature falls, heat drawn in by the air conditioner decreases accordingly. At the same time, heat loading of the air conditioner increases due to larger difference between indoor and outdoor temperature. If a comfortable temperature cannot be achieved with the air conditioner alone, it is recommended that you use a supplementary heating device.
Lightning or a car wireless telephone operating nearby may cause the unit to malfunction. Disconnect the unit from its power source and then re-connect the unit with the power source again. Push the ON/OFF button on the remote controller to restart operations.

Energy Saving Tips
· DO NOT set the unit to excessive temperature levels. · While cooling, close the curtains to avoid direct sunlight. · Doors and windows should be kept closed to keep cool or warm air in the room. · DO NOT place objects near the air inlet and outlet of the unit. This will reduce the efficiency of the unit. · Set a timer and use the built-in SLEEP/ECONOMY mode if applicable. · If you don’t plan to use the unit for a long time, remove the batteries from the remote control. · Clean the air filter every two weeks. A dirty filter can reduce cooling or heating efficiency. · Adjust louvers properly and avoid direct airflow.

Closing curtains during heating also helps keep the heat in

Doors and w indow s should be kept closed

Page 9

M anual Operations And M aintenance

3

M anual Operations And M aintenance

Operation mode selection

Optimal operation

While two or more indoor units are simultaneously operating, make sure the modes do not conflict with each other. The heat mode claims precedence over all other modes. If the unit intially started to operate in HEAT mode, the other units can operate in HEAT mode only. For example: If the unit intially started operates under COOL (or FAN) mode, the other units can operate under any mode except HEAT. If one of the unit selects HEAT mode, the other operating units will stop operation and diplay “–” (for units with display window only) or the auto and operation indication light will flash rapidly, the defrost indication light will turn off, and the timer indication light will remain on (for units without a display window). Alternatively, the defrost and alarm indication light (if applicable) wil light up, or the operation indication light will flash rapidly, and the timer indication light will turn off ( for the floor and standing type).
M aintenance
If you plan to leave the unit idle for a long time, perform the following tasks: 1. Clean the indoor unit and air filter. 2. Select FAN ONLY mode and let the indoor fan
run for a time to dry the inside of the unit. 3. Disconnect the power supply and remove the
battery from the remote control. 4. Check components of the outdoor unit
periodically. Contact a local dealer or a customer service centre if the unit requires servicing.
NOTE: Before you clean the air conditioner, be sure to switch off the unit and disconnect the power supply plug.

To achieve optimal performance, please note the following: · Adjust the direction of the air flow so that it is
notblowing directly on people. · Adjust the temperature to achieve the highest
possible level of comfort. Do not adjust the unit to excessive temperature levels. · Close doors and windows in COOL mode or HEAT mode. · Use the TIMER ON button on the remote controller to select a time you want to start your air conditioner. · Do not place any object near the air inlet or air outlet, as the efficiency of the air conditioner may be reduced and the air conditioner may stop running. · Clean the air filter periodically, otherwise cooling or heating per formance may be reduced. · Do not operate unit with horizontal louvre in closed position.
Suggest ion: For units that feature an electric heater, w hen the outside ambient temperature is below 0°C (32°F), it is strongly recommended that you to keep the machine plugged in so as to guarantee smooth operation.
When the air conditioner is to be used again:
· Use a dry cloth to wipe off the dust accumulated on the rear air intake grille in order to avoid the dust being dispersed from the indoor unit.
· Check that the wiring is not broken off or disconnected.
· Check that the air filter is installed. · Check if the air outlet or inlet is blocked after
the air conditioner has not been used for a long time.

Page 10

Troubleshoot ing

Troubleshoot ing

4

CAUTIONS
If one of the following conditions occurs, switch off the power supply immediately and contact your dealer for further assistance.
· The operation light continues to flash rapidly after the unit has been restarted. · The remote control buttons do not work. · The unit continually trips fuses or circuit breakers. · A foreign object or water enters the air conditioner. · Other abnormal situations.

Common Problems The following symptoms are not a malfunction and in most situations will not require repairs.

Problem
Unit does not turn on w hen pressing ON/ OFF button

Possible Causes
The unit has a 3-minute protection feature that prevents the unit from overloading. The unit cannot be restarted within three minutes of being turned off.
Cooling and Heating Models: If the Operation light and PRE-DEF (Pre-heating/ Defrost) indicators are lit up, the outdoor temperature is too cold and the unit’s anti-cold wind is activated in order to defrost the unit.
In Cooling-only Models: If the “Fan Only” indicator is lit up, the outdoor temperature is too cold and the unit’s anti-freeze protection is activated in order to defrost the unit.

The unit changes its setting to prevent frost from forming on the unit. Once

The unit changes the temperature increases, the unit will start operating again.

from COOL mode

to FAN mode

The set temperature has been reached, at which point the unit turns off the

compressor. The unit will resume operating when the temperature fluctuates

again.

The indoor unit In humid regions, a large temperature difference between the room’s air and emits w hite mist the conditioned air can cause white mist.

Both the indoor When the unit restarts in HEAT mode after defrosting, white mist may be

and outdoor units emit w hite mist

emitted due to moisture generated from the defrosting process.

Page 11

Problem
The indoor unit makes noises

Possible Causes
A squeaking sound is heard when the system is OFF or in COOL mode. The noise is also heard when the drain pump (optional) is in operation.
A squeaking sound may occur after running the unit in HEAT mode due to expansion and contraction of the unit’s plastic parts.

A low hissing sound may occur during operation. This is normal and is caused Both the indoor by refrigerant gas flowing through both the indoor and outdoor units.
unit and outdoor A low hissing sound may be heard when the system starts, has just stopped unit make noises running or is defrosting. This noise is normal and is caused by the refrigerant
gas stopping or changing direction.

The outdoor unit makes noises

The unit will make different sounds based on its current operating mode.

Dust is emitted from The unit may accumulate dust during extended periods of non-use, which

either the indoor or will be emitted when the unit is turned on. This can be mitigated by covering

outdoor unit

the unit during long periods of inactivity.

The unit emits a bad odor

The unit may absorb odors from the environment (such as furniture, cooking, cigarettes, etc.) which will be emitted during operations.
The unit’s filters have become moldy and should be cleaned.

The fan of the

outdoor unit

During operation, the fan speed is controlled to optimize product operation.

does not operate

Troubleshoot ing

Page 12

Troubleshoot ing

Troubleshooting Tips

When troubles occur, please check the following points before contacting a repair company.

Problem
The unit is not w orking

Possible Causes Power failure The power switch is off The fuse is burned out
Remote control batteries are dead The unit’s 3-minute protection has been activated Temperature setting may be higher than the ambient room temperature
The heat exchanger on the indoor or outdoor unit is dirty
The air filter is dirty

Poor cooling The air inlet or outlet of either unit performance is blocked

Doors and windows are open

Excessive heat is generated by sunlight
Low refrigerant due to leak or long-term use

The unit starts and st ops f requent ly

There’s too much or too little refrigerant in the system There is air, incompressible gas or foreign material in the refrigeration system.
System circuit is blocked

The compressor is broken The voltage is too high or too low

The outdoor temperature is lower than 7°C (44.5°F) Poor heating Cold air is entering through doors performance and windows
Low refrigerant due to leak or long-term use

Solut ion Wait for the power to be restored Turn on the power Replace the fuse Replace the remote control batteries
Wait three minutes after restarting the unit
Lower the temperature setting
Clean the affected heat exchanger
Remove the filter and clean it according to instructions Turn the unit off, remove the obstruction and turn it back on Make sure that all doors and windows are closed while operating the unit Close windows and curtains during periods of high heat or bright sunshine Check for leaks, re-seal if necessary and top off refrigerant Check for leaks and recharge the system with refrigerant Evacuate and recharge the system with refrigerant
Determine which circuit is blocked and replace the malfunctioning piece of equipment Replace the compressor Install a manostat to regulate the voltage Check for leaks and recharge the system with refrigerant Make sure that all doors and windows are closed during use Check for leaks, re-seal if necessary and top off refrigerant

Page 13

European Disposal Guidelines

5

Users in European Countries may be required to properly dispose of this unit. This appliance contains refrigerant and other potentially hazardous materials. When disposing of this appliance, the law requires special collection and treatment. DO NOT dispose of this product as household waste or unsorted municipal waste.
When disposing of this appliance, you have the following options: · Dispose of the appliance at designated municipal electronic waste collection facility. · When buying a new appliance, the retailer will take back the old appliance free of charge. · The manufacturer will also take back the old appliance free of charge. · Sell the appliance to certified scrap metal dealers.
NOTE: Disposing of this appliance in the forest or other natural surroundings endangers your health and is bad for the environment. Hazardous substances may leak into the ground water and enter the food chain.

European Disposal Guidelines

Page 14

5IFEFTJHOBOETQFDJGJDBUJPOTBSFTVCKFDUUPDIBOHFXJUIPVUQSJPSOPUJDFGPS QSPEVDUJNQSPWFNFOU$POTVMUXJUIUIFTBMFTBHFODZPSNBOVGBDUVSFSGPSEFUBJMT “OZVQEBUFTUPUIFNBOVBMXJMMCFVQMPBEFEUPUIFTFSWJDFXFCTJUF
QMFBTFDIFDL GPSUIFMBUFTUWFSTJPO
QSYTD-002U

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals