National Comfort Products Ncp4181000a Thru The Wall Split System Condensing Unit Installation Guide

NCP4181000A Thru the Wall Split System Condensing Unit

Product Information: Split-System Condensing Units

The Split-System Condensing Units are heating and air
conditioning equipment suitable for all types of multi-family
constructions. These units are designed for thru-the-wall
installation and should be installed only in an outside wall. The
National Comfort Products (NCP) Series includes four models: 1000,
3000, 4000, and 5000. All units are Department of Energy listed and
comply with National Codes. The unit must be permanently grounded
and copper supply wires should be used for installation.

Safety Warnings:

  • Disconnect ALL power before servicing to avoid property damage,
    personal injury, or death due to high voltage.
  • Qualified, licensed service personnel should read the
    instructions thoroughly before attempting installation or operation
    to avoid improper installation, adjustment, service, or maintenance
    resulting in fire, electrical shock, property damage, personal
    injury, or death.
  • Installation and repair of this unit should be performed ONLY
    by individuals meeting the requirements of an entry-level
    technician as specified by National Codes.
  • Use care when handling scroll compressors as some temperatures
    could be hot.
  • Scroll compressors should NEVER be used to evacuate the air
    conditioning system.
  • Do not use oxygen to purge lines or pressurize the system for a
    leak test.
  • Extreme caution should be exercised when opening the Liquid
    Line Service Valve.

Product Usage Instructions:

  1. Consult the DOE Compliance Certification Database for a list of
    rated combinations of indoor and outdoor units.
  2. Fill in the model and serial number as well as the installation
    date for future reference.
  3. Ensure that the unit is installed in an outside wall for
    thru-the-wall installation only.
  4. Do not place the unit on its side or upside down as the
    compressor oil will run in the cooling circuit and seriously damage
    the unit.
  5. Base pan must always be on the bottom of the install.
  6. Use copper supply wires only and never use oxygen to purge
    lines or pressurize the system for a leak test.
  7. Extreme caution should be exercised when opening the Liquid
    Line Service Valve.
  8. The unit must be permanently grounded to avoid electrical shock
    resulting in severe personal injury or death.

NATIONAL® COMFORT PRODUCTS
HEATING & A/C EQUIPMENT
Thru-the-Wall Comfort for all types of Multi-Family Construction

Installation Guide
Split-System Condensing Units
This unit should be installed in an OUTSIDE WALL FOR THRU-THE-WALL INSTALLATION ONLY!
All Units Department of Energy Listed
*Please consult the DOE Compliance Certification Database (https://tinyurl.com/NCPCondensers) for a list of rated combinations of indoor and outdoor units.
Please fill in the following information and file it for future reference. MODEL NO.______________________________ SERIAL NO.______________________________ INSTALL DATE ___________________________

NCP
Series:
1000 3000 4000 5000

Go Thru-the-Wall

NATIONAL® COMFORT PRODUCTS
HEATING & A/C EQUIPMENT

National Comfort Products
A Division of National Refrigeration and Air Conditioning Products, Inc.
539 Dunksferry Road · Bensalem, PA 19020-5908 (800) 523-7138 · Fax (215) 639-1674
www.nationalcomfortproducts.com

Installation Guide | Split-System Condensing Units
Page
Safety Warning …………………………………………………………………………………………………………………………………………. 3 Before You Start………………………………………………………………………………………………………………………………………… 3 Check for Clearances …………………………………………………………………………………………………………………………………. 4 Unit Location Considerations ………………………………………………………………………………………………………………………. 4 Refrigerant Piping Limits ……………………………………………………………………………………………………………………………. 4 Leak Checking…………………………………………………………………………………………………………………………………………… 6 Evacuation, Electrical Connections……………………………………………………………………………………………………………….. 7 High Voltage and Power Supply…………………………………………………………………………………………………………………… 8 Start Up, Sequence of Operations ………………………………………………………………………………………………………………… 9 Refrigerant Charging…………………………………………………………………………………………………………………………………..10 Maintenance, Checkout Procedure………………………………………………………………………………………………………………..11 Noise, Insulated Sound Cover………………………………………………………………………………………………………………………12 Important! Before Removing a Warranty Compressor……………………………………………………………………………………..13 Wiring Diagrams ………………………………………………………………………………………………………………………………………..14 Specifications, Dimensional Drawings …………………………………………………………………………………………………………..15-16 Matched systems with Cased Coils……………………………………………………………………………………………………………….17 Matched systems with Air Handlers………………………………………………………………………………………………………………17 Replacement Parts – NCP 1000 Series…………………………………………………………………………………………………………..18 Replacement Parts – NCP 3000 Series…………………………………………………………………………………………………………..18 Replacement Parts – NCP 4000 Series…………………………………………………………………………………………………………..19 Replacement Parts – NCP 5000 Series…………………………………………………………………………………………………………..20 Warranty …………………………………………………………………………………………………………………………………………………..21-22
IMPORTANT NOTE: DO NOT DESTROY OR THROW AWAY THIS MANUAL. IT SHOULD BE KEPT IN A SAFE PLACE FOR FUTURE REFERENCE.

2

NCP Series 1000 | 3000 | 4000 | 5000

Installation Guide | Split-System Condensing Units Safety Warnings!

! WARNING
HIGH VOLTAGE! Disconnect ALL power before servicing. Multiple power sources may be present. Failure to do so may result in property damage, personal injury or death.
! WARNING
These instructions are intended as an aid to qualified, licensed service personnel for proper installation, adjustment and operation of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment, service or maintenance possibly resulting in fire, electrical shock, property damage, personal injury or death.
! WARNING
Installation and repair of this unit should be performed ONLY by individuals meeting the requirements of an “entry level technician” as specified by National Codes. Attempting to install or repair this unit without such background may result in product damage, personal injury or death.
! CAUTION
Use care when handling scroll compressors. Some temperatures could be hot!
! CAUTION
Scroll compressors should NEVER be used to evacuate the air conditioning system. Vacuums this low can cause internal electrical arcing resulting in a damaged or failed compressor.
! WARNING
The unit must be permanently grounded. Failure to do so can cause electrical shock resulting in severe personal injury or death.
“USE COPPER SUPPLY WIRES ONLY”
! WARNING
Do not use oxygen to purge lines or pressurize system for leak test. Oxygen reacts violently with oil, which can cause an explosion resulting in severe personal injury or death.

! WARNING
Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn counter clockwise until the valve stem just touches the rolled edge. No torque is required. Failure to follow this warning will result in abrupt release of system charge and may result in personal injury and /or property damage.
Before You Start
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES. The manufacturer assumes no responsibility for equipment installed in violation of any code requirements. Be sure that the electrical data specified on the unit rating plate corresponds to what is available at the installation site and NEC for installation requirements. This unit MUST be installed in an outside wall for thru-the-wall installation ONLY. No pad mounts. Be sure that the electrical service provided to the building can handle the load imposed by the unit.
IMPORTANT — This Document is customer property and is to remain with this unit. Please refer to service information pack upon completion of work to register the unit’s warranty. These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to your installing dealer or local distributor before contacting the manufacturer.
Note: The manufacturer recommends installing only approved matched split systems. Our split systems are A.H.R.I. and DOE rated only with TXV indoor systems. (Please consult the DOE Compliance Certification Database (https://tinyurl.com/NCPCondensers) for a list of rated combinations of indoor and outdoor units. Combinations of outdoor and indoor units that are not rated will require factory testing and listing with DOE. Please consult the factory.) Some of the benefits of installing approved matched split systems are maximum efficiency, optimum performance and the best overall system reliability. Self-equalizing components are required to reduce compressor starting problems. If self-equalizing components are not used, field installed hard start kits will be required. Hard start kits MUST be compatible with compressors. Hard start kits MUST be compatible with Copeland compressors 88-106/330 µF/Volts Start relays to be sized to µF of capacitor used.
The unit must never be placed on its side or upside down as the compressor oil will run in the cooling circuit and seriously damage the unit. Base pan must always be on the bottom of the install.

NCP Series 1000 | 3000 | 4000 | 5000

3

Installation Guide | Split-System Condensing Units

Check for Clearances
Minimum 48″ Vertical Clearance Between Units
Minimum 12″ Horizontal Clearance Between Units
WARNING: Warranty will be void on all units installed behind brick facades (e.g. pigeon holes) or connected to ductwork (See Note 1 below). All obstacles added to impede air flow of the condensing unit will decrease performance, cause premature equipment failure, and void all warranties. Consult factory with any questions.
Note 1: No ducts are permitted to be connected to the intake or discharge of the unit.
Unit Location Considerations
In thru-the-wall installation, due to the various types of wall construction, it is not possible to provide detailed instructions. The following is a list of general requirements and cautions for installing these units. The unit must be installed level, both – top front to back and left to right. 1. Masonry walls must have a lintel to support the wall. 2. Extend the unit approximately 3/4″ beyond outside surface of the wall. Optional mounting angles can be purchased from the factory or field fabricated for locating and mounting the unit in the wall.

3. The wall opening across the top and bottom must be flashed. Bottom flashing to cover the full footprint of unit and extend up 2″ on 3 sides. All openings around the top, sides and bottom must be caulked and sealed. Care must be taken not to plug the openings in the front of the base pan of the unit. If the optional wall sleeve is used, caulk the spaces between the sleeve and the wall. Completely fill the clearance between the unit and the wall sleeve with a polyurethane foam sealant.
4. During periods of rain and wind the primary drainage path may not be adequate to handle the load. Secondary precautions may also be required but not limited to the following:
a. Seal flashing to unit
b. Floor drain
c. Additional field sealing of sheet metal joints
d. Sealing of unused access opening
5. Clearances to air inlets and outlets must be adequate to ensure no air flow obstructions or recirculation of condenser air flow. Care must be taken to locate the coil side of the unit away from loose debris that may clog airflow inlet or outlet.
6. Some architectural designs of buildings will require the unit to be mounted behind a decorative grille. The performance (capacity and efficiency) of the unit may be reduced with the use of these decorative grilles. The less resistive these grilles are to air flow, the better the units performance will be. Outdoor louvers provided by others must be approved by NCP to maintain unit performance and warranty.
7. If the unit is mounted behind a decorative grille, one or both of the following items must be done to eliminate recirculation of air to the unit:
a. The front of the unit must be mounted tight to the inside of the architectural grille
b. A barrier must be provided to prevent recirculation of air to the unit (mixing of inlet and outlet air) when the front of the unit is mounted back from the inside of the architectural grille
8. The unit must not be mounted in dead-end hallways or areas where there is no fresh outside air circulation. Cool fresh outside air must be provided for best unit operation. Thru-the-wall units may not be located where hot exhausts from clothes dryer vents, kitchen vents, steam vents or corrosive fumes could come in contact with coil side of unit.
9. 30″ clearance is required for service accessibility on the inside service panel.
10. A minimum 48″ of vertical clearance and 12″ of horizontal clearance between units is required to minimize recirculation of condenser exhaust air. For horizontal clearances less than 12″, please consult National Comfort Products.
11. Care must be taken when locating the unit. Locate away form bedrooms as operational sounds may be objectionable. (See sound cover on page 12)
Refrigerant Piping
1. The maximum length of refrigerant lines from the through the wall unit to indoor unit should NOT exceed fifty (50) feet without contacting National Comfort Products.
2. The maximum vertical change should not exceed twenty (20) feet without contacting National Comfort Products.
Maximum Allowable Liquid Line Pressure Drop = 50 PSI Subtract .43 PSI for each foot of Liquid Lift (if any) Do Not Exceed this value when selecting Liquid Line

4

NCP Series 1000 | 3000 | 4000 | 5000

Installation Guide | Split-System Condensing Units

*Call National Comfort Products for Greater Line Lengths
Air Handler or Coil
Air Handler or Coil

Note: Always use refrigeration grade copper tubing that is internally clean and dry for refrigerant lines. Use clean hard drawn copper tubing if no appreciable amount of bending is necessary. If soft copper is used, avoid sharp bends which may cause a restriction. Always use heat sink materials during brazing to prevent damage to service valves (See page 6).

4. Run refrigerant lines as directly as possible. Field piping inside the condensing unit should not block access to major components. Refrigerant lines should not be in direct contact with the floor or ceiling joists. Use insulated or suspension type hangers. When refrigerant lines run through a wall, seal openings around the lines with a flexible material to avoid vibration to the structure.

Note: Take precautions to prevent noise within the building structure due to vibration transmission from the refrigerant lines For example: When the refrigerant lines have to be fastened to floor joists or other framing in a structure, use isolation type hangers.
Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings.
Where the refrigerant lines run through a wall or sill, they should be insulated and isolated.
Isolate lines from all ductwork.
Minimize the number of 90 turns.

5. Standard refrigeration piping practices must be employed when installing traps. When installing the condenser below the evaporator, the suction line must be trapped with an inverted trap the height of the evaporator coil. Consult the factory when total equivalent length of refrigerant lines exceeds 50 ft.
6. Insulate the vapor line with a minimum 1/2″ foam rubber or other type insulation having an adequate vapor barrier. For indoor units with a TXV, a liquid line filter drier must be installed (SPORLAN #C-083-S or similar).

Liquid Line

Vapor Line Insulation

Air Handler or Coil

3. The unit has internally mounted service valves. Field tubing may be routed through the locations provided in either the top or rear panels. Care should be taken not to block access to internal components. Seal unused knockouts with high grade sealant. Gaskets are provided for liquid and suction lines.

IMPORTANT: The Vapor Line must always be insulated. DO NOT allow the liquid line and vapor line to come in direct (metal to metal) contact.

NCP Series 1000 | 3000 | 4000 | 5000

5

Installation Guide | Split-System Condensing Units

7. Install the refrigerant lines using the following procedure (See Steps 1 thru 4.)
a. Remove the service port caps and Schrader Cores of the liquid line service valve and the vapor line service valve of the condensing unit. Connect low pressure dry nitrogen to the liquid line valve service port.

Step 3:

CAUTION: Dry nitrogen should always be supplied through the tubing while it is being brazed, as the high temperature required for brazing will cause oxidation of the copper unless an inert atmosphere is provided. The flow of dry nitrogen should continue until the joints have cooled. Always use a pressure regulator and safety valve to ensure that only low pressure nitrogen is introduced into the tubing. Only a small flow is necessary to displace air and prevent oxidation.
b. Provide a heat sink at the service valve such as wrapping a wet rag around it, to prevent damage during the brazing operation
c. Braze the liquid line to the service valve. Allow the nitrogen to keep flowing when brazing the refrigerant line until all brazed joints are completed.
d. Provide a heat sink to the vapor line service valve of the condensing unit
e. Braze the vapor line to the service valve
f. When tubing installation is complete, seal openings around tubing where tubing enters the unit cabinet.

Step 4:

Flux the copper tube and insert into the stub. Braze the joint. No flux is necessary if a low to zero-silver braze alloy is used.
After brazing, quench with a wet rag to cool the joint and remove any flux residue.

Step 1: Step 2:

The tubing should be cut square. Make sure it is round and free of burrs at the connecting ends. Clean the tubing to prevent contaminants from entering the system.
Wrap a wet rag around the copper stub of the service valve before brazing.

Leak Checking
Leak checking of refrigerant line braze joints and evaporator unit using dry nitrogen. (See Step 5a)
1. Replace service port cap of the vapor line service valve (cap was removed for brazing operations). 2. Connect dry nitrogen source to the service port of the liquid line service valve. Pressurize refrigerant lines and indoor coil to approximately 100 psig. 3. Check for leaks using a liquid soap solution. If any leaks are detected, purge the nitrogen, repair the leak(s) and repeat the leak check procedure.
Leak checking of refrigerant line braze joints and evaporator unit using R410a refrigerant. (See Step 5b)
1. Connect R410a source to the service port of the liquid line service valve. Use of a manifold gauge set will facilitate connecting and disconnecting of the refrigerant source for leak checking. Pressurize refrigerant lines and indoor coil with refrigerant gas. 2. Leak check with an electronic leak detector or liquid soap solution. If any leaks are detected, use a refrigerant recovery system to remove the refrigerant. Repair the leak(s) and repeat the leak check procedure.

6

NCP Series 1000 | 3000 | 4000 | 5000

Installation Guide | Split-System Condensing Units

Step 5a: Using a liquid soap solution

b. If the evacuation is being performed on an installation where the condensing unit factory charge has been lost, the service valves should be opened.
2. Following the vacuum pump manufacturer’s instructions, allow the pump to operate until the system has been evacuated down to 300 microns.

Note: Check for leaks if unable to get to 300 microns.

Apply liquid soap solution to check for leaks
Bubbles forming in the liquid soap solution indicates a leak
Step 5b: Using an electronic leak detector Leak check with an electronic leak detector

3. Allow the pump to continue running an additional 15 minutes. Turn off the pump and leave connections secured. After 10 minutes if system fails to hold 500 microns or less, check all connections for tight fit and repeat evacuation procedure.
4. Isolate the vacuum pump by closing the shut-off valves on vacuum pump lines or test gauge manifold.
5. Open the service valves. Opening the service valves will allow the refrigerant in the condensing unit to enter the refrigerant lines and evaporator coil. The vacuum pump can now be disconnected. (See Step 6 and 7)

Step 6: Step 7:

This is not a back seating valve. To open the valve remove the valve cap with an adjustable wrench. Insert a 3/16″ or 5/16″ hex wrench into the stem. Back out counter-clockwise until the valve stem just touches the retaining ring. CAUTION (Certain combination hex wrenches designed for service valves may not properly seat into the valve stem and may lead to stripping. Make sure the hex wrench is seated completely in the valve when first opening)
Replace the valve cap finger tight then tighten an additional 1/12 turn or 1/2 hex flat. A metal-to-metal seal is now complete. Complete normal factory recommended procedures.

Evacuation
1. Connect the vacuum pump to the service ports of the liquid line and vapor line service valves. If the vacuum pump lines do not contain shut-off valves, hook up the vacuum pump through a manifold gauge set, as the vacuum pump lines must be closed for step 4 below.
a. If the evacuation is being performed on a new system installation, the condensing unit service valves should be kept in the closed position. The vacuum pump will then be able to evacuate the refrigerant lines and evaporator coil.

Electrical Connections
Note: Make certain that the volts, hertz, and phase correspond to that specified on the unit rating plate, and that the service provided by the utility is sufficient to handle the additional load imposed by this equipment.

NCP Series 1000 | 3000 | 4000 | 5000

7

Installation Guide | Split-System Condensing Units

Make all electrical connections in accordance with the National Electrical Code and any pertinent local codes or ordinances. Use a separate branch electrical circuit for this unit. Locate a disconnecting means within sight of and readily accessible to the unit.
a. Line Voltage Connections
b. Connect the single phase power supply to unit contactor terminal L1 and L2
c. Connect ground wire to lug
d. Low Voltage Connections
Consult the indoor unit installation instructions for thermostat connections. Use a 2-wire thermostat cable between the units.
When locating the room thermostat, it should be in the natural circulating path of room air. Avoid locations where the thermostat would be exposed to cold air infiltration; drafts from windows, doors or other openings leading to the outside; exposure to air currents from warm-or-cold air registers or to exposure where the natural circulation of the air is cut off, such as behind doors, above or below mantels, shelves, etc.

Electrical – Low Voltage

Low Voltage Maximum Wire Length:
Table defines the maximum total length of low voltage wiring from the condensing unit to the indoor unit and to the thermostat.

24 VOLTS

WIRE SIZE 18 AWG 16 AWG 14 AWG

MAX. WIRE LENGTH 150 ft. 225 ft. 300 ft.

Low Voltage Hook-up Diagram Field Wiring Low Voltage

Electrical – High Voltage

NOMINAL VOLTAGE
208-230

MINIMUM VOLTAGE
197

MAXIMUM VOLTAGE
253

Please refer to pages 14-17 for proper capacitor sizing.

High Voltage Power Supply

! WARNING
LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

The high voltage power supply must agree with the equipment nameplate.
OR
Make certain that the volts, hertz, and phase correspond to that specified on the unit rating plate, and that the service provided by the utility is sufficient to handle the additional load imposed by this equipment.
Power wiring must comply with national, state, and local codes.
Follow instructions on unit wiring diagram located on the inside of the access door, or cabinet and in the wiring diagrams included with the unit.

Install a separate disconnect switch at the location of the through the wall unit.
Ground the unit per national, state, and local code requirements.

Disconnect Switch
ON OFF

White Red
Blue
Contactor 8

Thru-the-Wall Condensing Unit
NCP Series 1000 | 3000 | 4000 | 5000

Installation Guide | Split-System Condensing Units

Start Up

Sequence of Operations

1. Ensure that directions on Page 4 through 8 have been completed. Check numbers once done.
2. Turn on disconnect(s) to apply power to all equipment.
3. Wait one (1) hour before starting the unit if compressor crankcase heater accessory is used and the Outdoor Ambient is below 70º
4. Set system thermostat to ON.

On a “call for cooling”, the thermostat completes circuits R-Y and R-G. Circuit R-Y energizes the contactor starting the condenser fan motor and compressor circuit. R-G energizes the indoor unit blower relay starting the indoor blower motor.
When the thermostat is satisfied, its contacts open, de-energizing the contactor and blower relay. Compressor and motors should stop.

NATIONAL COMFORT PRODUCTS R-410A CHARGING CHART

°F

°F

°F

°F

°F

°F

°F

°F

°F

°F

°F

LIQUID PRESSURE AT SERVICE VALVE (psig)

12

13

14

15

16

17

18

19

20

21

22

R-410A REQUIRED LIQUID LINE TEMPERATURE (°F)

251

72

71

70

69

68

67

66

65

64

63

62

259

74

73

72

71

70

69

68

67

66

65

64

266

76

75

74

73

72

71

70

69

68

67

66

274

78

77

76

75

74

73

72

71

70

69

68

283

80

79

78

77

76

75

74

73

72

71

70

291

82

81

80

79

78

77

76

75

74

73

72

299

84

83

82

81

80

79

78

77

76

75

74

308

86

85

84

83

82

81

80

79

78

77

76

317

88

87

86

85

84

83

82

81

80

79

78

326

90

89

88

87

86

85

84

83

82

81

80

335

92

91

90

89

88

87

86

85

84

83

82

345

94

93

92

91

90

89

88

87

86

85

84

364

98

97

96

95

94

93

92

91

90

89

88

374

100

99

98

97

96

95

94

93

92

91

90

384

102

101

100

99

98

97

96

95

94

93

92

395

104

103

102

101

100

99

98

97

96

95

94

406

106

105

104

103

102

101

100

99

98

97

96

416

108

107

106

105

104

103

102

101

100

99

98

427

110

109

108

107

106

105

104

103

102

101

100

439

112

111

110

109

108

107

106

105

104

103

102

450

114

113

112

111

110

109

108

107

106

105

104

462

116

115

114

113

112

111

110

109

108

107

106

474

118

117

116

115

114

113

112

111

110

109

108

Note: It is important to return in the spring or summer to accurately charge the system in the cooling mode when outdoor ambient temperature is above 55º F.
Stabilize the system by operating for a minimum of 20 minutes. At startup, or whenever charge is removed or added, the system must be operated for a minimum of 20 minutes to stabilize before accurate measurements can be made.
System Charge Adjustment
Temperature Measurements Check that the outdoor temperature is 65°F or higher before adjusting charge based on subcooling. Subcooling (in cooling mode) is the only

recommended method of charging the system. For reference, use the charge chart above and refer to page 17 for your systems proper subcooling value. For best results the indoor temperature should be kept between 70º F to 80º F.
Installers Notes:
· Condenser door must be in place while adjusting subcooling · Ambient temperature must be between 65°F-95°F · Indoor return air temperature must be above 70°F · Allow 20 minutes of run time at premium conditions before adjusting
charge · Driving rain against the condenser coil can affect setting proper subcooling · Add charge to increase subcooling · Remove charge to decrease subcooling · Indoor units must be equipped with a thermal expansion valve (TXV)

NCP Series 1000 | 3000 | 4000 | 5000

9

Installation Guide | Split-System Condensing Units

Refrigerant Charging
The condensing units are tested in factory based on 10 ft of refrigerant lines. If the actual line length is greater or less than 10ft, add or remove refrigerant at the rate of 0.6 ounces per foot.
If the condensing unit charge was lost for any reason, add factory refrigerant charge listed on condensing unit data plate plus adjustments describe above to meet the required subcool as instructed on page #17. If the unit is operating during charge adjustment, the access panel must be in place to prevent high head pressure which would shut down the unit.
Note: For longer linesets, the charge MUST be adjusted to meet the required subcool and superheat values as instructed on page #17 for cooling operation. Use actual linear length with the table below.

When replacing an R-22 system, it is recommended that new line sets be used. If the old line sets are to be used, they MUST be flushed with a commercial flushing agent. R410A refrigerant oil is not compatible with mineral oil.
IMPORTANT: The outdoor unit comes with refrigerant, which may not be enough for your system. When installing a condensing unit with a matched Indoor coil or air-handler, system charge and TXV setting MUST be adjusted to meet the required subcool and superheat values as instructed on page #17. All other indoor units will require factory testing and certification with DOE. Be sure both service valves are closed during tubing installation and leak checked to avoid loss of charge. A liquid line filter drier must be installed (SPORLAN #083-S or similar).

Weight Ounces Pounds

Ounces & Pounds of R410A Required for Line Sets

Tubing Size 3/8″ – 3/4″ 3/8″ – 3/4″

10′

15′

20′

25′

30′

35′

40′

45′

50′

0

3.5

7

10.5

14

17.5

21

24.5

28

0

0.21875 0.4375 0.65625

0.875

1.09375 1.3125 1.53125

1.75

! CAUTION
Low Suction Pressure Operation! Compressor Damage!
Do not operate with a restricted suction. Do not operate with the lowpressure cut-out bridged. Do not operate compressor without enough system charge to maintain at least 0.5 bar (7.25 psi) suction pressure. Allowing pressure to drop below 0.5 bar (7.25 psi) for more than a few seconds may overheat scrolls and cause early drive bearing damage.
The system should be liquid-charged through the liquid-receiver shut-off valve or through a valve in the liquid line. The use of a filter drier in the charging line is highly recommended. Because R410A and R407C are blends and scrolls have discharge check valves, systems should be liquid-charged on both high and low sides simultaneously to ensure a positive refrigerant pressure is present in the compressor before it runs. The majority of the charge should be placed in the high side of the system to prevent bearing washout during first-time start on the assembly line.
1. Connect the charging cylinder to the manifold gauge set. Open the charging cylinder valve and bleed air out of the charging hose at the manifold gauge set connection.
2. Tighten the manifold gauge set charging connection. Open the main manifold gauge set valve and introduce refrigerant into the liquid side of the system.
Note: Oil charge is polyester 32bce.
CAUTION: It is very important that when charging a system to charge liquid refrigerant into the high side only. It is not good practice to flood liquid refrigerant from a refrigerant cylinder into the crankcase of the a stationary compressor through the suction line. If additional charge is required carefully charge liquid incrementally into the low side of the system with the compressor operating. Excessive liquid introduced into the suction line will damage the compressor.

3. When the correct refrigerant charge level is obtained, remove the manifold gauge set. 4. Replace the gauge port caps. Permanently stamp the unit data plate with the total amount of refrigerant in the system.
Note: All information based on the following Air Flow Chart. Required superheat varies for each system. Refer to page 17 for recommended superheat. Superheat temperature measurements should be taken within 3 feet of the compressor suction line connection.

Air Flow Chart for Coil Matches

Outdoor Model

Indoor Model

Airflow (SCFM)1

NCP4181000A-**

NCC418AA-*

620

NCP4243000A-**

NCC418AA-*

620

NCP4184000A-**

NCC418AA-*

620

NCP4185000A-**

NCC418AA-*

620

NCP4241000A-**

NCC424AA-*

820

NCP4243000A-**

NCC424AA-*

820

NCP4244000A-**

NCC424AA-*

820

NCP4245000A-**

NCC424AA-*

820

NCP4305000A-**

NCC430AA-*

920

1. The airflow is conducted at wet coil conditions. The airflow in the table above is recommended to get best performance out of your system

10

NCP Series 1000 | 3000 | 4000 | 5000

Installation Guide | Split-System Condensing Units

Air Flow Chart for Air Handler Matches

Outdoor Model

Indoor Model

Motor Speed Color (Tap)

Static (in. wc.)

Airflow (SCFM)1

NCP4181000A-** NAH424MF*-** Black (2)

0.3

600

NCP4183000A-** NAH424MF*-** Blue (3)

0.3

600

NCP4184000A-** NAH424MF*-** Black (2)

0.3

600

NCP4185000A-** NAH424MF*-** Blue (3)

0.3

600

NCP4241000A-** NAH430MF*-** Black (2)

0.3

790

NCP4243000A-** NAH430MF*-** Blue (3)

0.3

790

NCP4244000A-** NAH430MF*-** Black (2)

0.3

790

NCP4245000A-** NAH430MF*-** Blue (3)

0.3

790

NCP4305000A-** NAH430MF*-** Red (5)

0.3

950

1. The airflow is conducted with a filter at wet coil conditions. The airflow in the table above is recommended to get best performance out of your system

Maintenance
1. Annually clean the inside of the unit to keep the weep holes in the base pan open to assure proper drainage of water from the unit.
2. Keep the condenser coil clean and free of anything that restricts free air flow. For sea coast applications the condenser coil should be washed periodically to remove salt accumulation.
3. Reduced indoor air flow through a duct system will cause the indoor coil to ice up in cooling. If this condition is not corrected, premature system failure will result. Indoor air filters should be cleaned and changed regularly.
4. Annually check units mounting to structure to ensure integrity. Seal between cabinet and/or sleeve for air or water leakage. Check exposed surfaces for corrosion. Replace or paint parts as required. This maintenance is critical to prevent stains and damage to exterior surface of building.
5. Inspect refrigerant piping for leaks and suction line insulation for deterioration and damage. Improper insulation can cause condensate water damage.
6. Pressure and temperature readings of the high and low sides of the system should be checked for proper superheat and/or subcooling. Correct if required. See System Charge Adjustment on Page 9.
7. Check motor amperage to nameplate value, inspect the motor mounting and prop fan hub for tightness and rust or corrosion. Observe the prop fan blade for balance.
8. Inspect the wire connections and contactor dry contacts for evidence of arcing, over heating, or deterioration.

Checkout Procedures and Troubleshooting

Checkout Procedures

After installation has been completed, it is recommended that the system be checked against the following list:

1. Leak check refrigerant lines.

2. Properly insulate suction lines and fittings.

3. Properly secure and isolate all refrigerant

lines.

4. Seal passages through masonry. If mortar is used, prevent mortar from coming into direct

contact with copper tubing.

5. Verify that all electrical connections are tight.

6. Observe outdoor fan during on cycle for

clearance and smooth operation.

7. Be sure the indoor condensate line drains freely. Pour water into drain pan.

8. Be sure that supply registers and return

grilles are open and unobstructed.

9. Be sure that a return air filter is installed.

10. Be sure that the correct indoor airflow setting

is used.

Service Access

Note: 30″ of clearance is required for service accessibility on the inside. All units are serviceable from the inside.

NCP Series 1000 | 3000 | 4000 | 5000

11

Installation Guide | Split-System Condensing Units
Noise
We design our unit as quiet as possible; please keep in mind when locating the unit that it does make noise. Use common precautions as you would for other mechanical appliances pertaining to noise.
Outdoor Sound: 79.8 dBA (AHRI Standard 270-2008) Sound Cover As an option, we offer an Insulated Sound Cover for installation over the inside cover of the unit. Indoor Sound Without Insulated Sound Cover: 70.4 dBA With Insulated Sound Cover: 68.3 dBA (AHRI Standard 350-2008)

Refrigerant Line Access
Insulated Sound Cover

Wall Sleeve

The Insulated Sound Cover will be supplied with insulated handles installed and assembled.
To install onto the unit, either the top or bottom will need to be removed depending on the exit point of the tubing. (3 screws)
Sound Covers Available 1000 I.D. Cover 3000 I.D. Cover 4000 I.D. Cover 5000 I.D. Cover

Access provided to Line Set Connections, Line Voltage, Low Voltage and Refrigerant Line Access
12

NCP Series 1000 | 3000 | 4000 | 5000

Installation Guide | Split-System Condensing Units
IMPORTANT!!!
BEFORE REMOVING A WARRANTY COMPRESSOR, PLEASE FILL OUT THE FOLLOWING AND CALL (800) 523-7138.
REMOVAL OF COMPRESSOR WITHOUT FACTORY VERIFICATION CAN LEAD TO WARRANTY CREDIT BEING DENIED
1. Incoming Voltage to Compressor at Contactor is:__________Volts AC 2. Compressor Starting AMP Draw:__________ A 3. Compressor Winding OHM Reading between Terminals C & S:__________ 4. Compressor Winding OHM Reading between Terminals C & R:__________ 5. Compressor Winding OHM Reading between Terminals R & S:__________ 6. Compressor Winding OHM Reading between Terminals C & Ground:__________ 7. Compressor Winding OHM Reading between Terminals R & Ground:__________ 8. Compressor Winding OHM Reading between Terminals S & Ground:__________

9. Run Capacitor Reading from HERM to COM:__________ + uF 10. Start Capacitor Reading if Used:__________ + uF
11. If the Compressor is Operating Please Indicate the Following:
Suction Pressure:__________psig Discharge Pressure___________psig Super Heat:_____________F Subcooling:______________F
NCP Series 1000 | 3000 | 4000 | 5000

TOP VIEW OF CAPACITOR HERM
C FAN
13

Installation Guide | Split-System Condensing Units

208-230 VAC NOMINAL VOLTAGE 197 VAC MINIMUM VOLTAGE 253 VAC MAXIMUM VOLTAGE

CAPACITOR CHART NCP418(1000,3000,4000) NCP418(5000) NCP424(1000,3000,4000) NCP424(5000) NCP430(1000,3000,4000,5000)

= 30+5/440VAC = 30/440VAC = 35+5/440VAC = 35/440VAC = 35/440VAC

FUSED OR NON-FUSED DISCONNECT OPTIONAL

14

G

L1 L2

CYR

BLACK BLACK

WHITE

RED

1 (OPTIONAL)
CCH

CC

BLUE

BLUE RED

LPS

HPS

WHITE
CAP

H C
F 2

YELLOW

RED BLACK

YELLOW BLACK

C

S

R

COMP

BROWN

CFM

NOTE: 1. Crankcase heater is available as a factory installed option. 2. Certain units utilize CFM’s that do not require a capacitor. This BROWN wire will not be included and a single capacitor will be used for the COMP. See Capacitor Chart above.

539 DUNKSFERRY RD. Bensalem, Pa. 19020 Phone: 800-523-7138
FAX: 215-639-1674

WIRING DIAGRAM NCP SERIES
1000, 3000, 4000 & 5000

DRAWN BY BS

DATE 12/1/2022

JOB NUMBER 14299226

LEGEND CAP – DUAL CAPACITOR CC – COMPRESSOR CONTACTOR CCH – CRANKCASE HEATER (OPTIONAL) COMP – COMPRESSOR CFM – CONDENSER FAN MOTOR HPS – HIGH PRESSURE SWITCH LPS – LOW PRESSURE SWITCH

NCP Series 1000 | 3000 | 4000 | 5000

Installation Guide | Split-System Condensing Units

1000 Series w/ matches up to 12.5 SEER2*

All Units 208/230-1~-60Hz

Model

Shipping Compressor weight (lbs) RLA LRA

MCA

MOP

NCP4181000A-**

160

10.3 45.7

14.20

20

NCP4241000A-**

165

11.7 59.5

15.90

25

NCP4301000A-**

Coming Soon

Cond. Fan Motor Specs Condenser Coil Specs
Dimensions

418/424

1/4 HP, 1600 RPM, 1.3 FLA

3.61 ft2 Face Area, 16 FPI

26 1/4″ W x 28 5/8″ H x 18 1/2″ D

Liquid Valve

3/8″

Suction Valve

3/4″

*When matched with NAH4**MF Air Handler

18

7 8

26

1 8

28

3 4

19

1 8

3000 Series w/ matches up to 12.5 SEER2*

All Units 208/230-1~-60Hz

Model

Shipping Compressor weight (lbs) RLA LRA

MCA

MOP

NCP4183000A-**

160

NCP4243000A-**

165

NCP4303000A-**

Cond. Fan Motor Specs

10.3 45.7

14.20

20

11.7 59.5

15.90

25

Coming Soon

418/424

1/4 HP, 1600 RPM, 1.3 FLA

Condenser Coil Specs Dimensions

3.77 ft² Face Area, 16 FPI 24 1/8″ W x 32″ H x 18 1/2″ D

Liquid Valve

3/8″

Suction Valve

3/4″

* When matched with NAH4**MF Air Handler

18

7 8

4

3 8

26

1 8

22

1 4

6

1 8

10

7 8

1

7 8

3

7 8

6

3 4

8

1 2

5

1 4

24

1 4

25

3 4

24

1 4

18

7 8

NCP Series 1000 | 3000 | 4000 | 5000

32

1 4

12

1 8

7

3 8

1

5 8

3

5 8

8

1 2

28

7 8

13

1 2

5

7 8

10

1 8

17

3 8

32

1 4

1

1 2

5

1 4

9

5 8

15

1 2

15

Installation Guide | Split-System Condensing Units

4000 Series w/ matches up to 12.5 SEER2*

All Units 208/230-1~-60Hz

Model
NCP4184000A-** NCP4244000A-**

Shipping weight (lbs)
160 170

Compressor RLA LRA 10.3 45.7 11.7 59.5

MCA
14.70 16.40

MOP
20 25

NCP4304000A-**

Coming Soon

Cond. Fan Motor Specs Condenser Coil Specs
Dimensions

1/5 HP, 1650 RPM, 1.8 FLA 3.14 ft² Face Area, 16 FPI 30″ W x 23″ H x 22 1/2″ D

Liquid Valve

3/8″

Suction Valve

3/4″

* When matched with NAH4**MF Air Handler

30

1 8

3

3 8

23″

1

3 8

1

5 8

23

1 8

23

1 8

3

7 8

16

3 4

1

1 4

15

5 8

11″

1

5 8

2

1 4

4

1 4

6

3 4

11

1 2

29

7 8

3

3 8

23

1 8

5000 Series w/ matches up to 14 SEER2*
All Units 208/230-1~-60Hz

7

5 8

27

1 4

Model

Shipping Compressor weight (lbs) RLA LRA

MCA

MOP

NCP4185000A-**

170

10.3 45.7

14.68

20

NCP4245000A-**

185

11.5 59.5

16.18

25

NCP4305000A-**

190

14.1 67.9

19.43

30

Cond. Fan Motor Specs

1/5 HP, 1650 RPM, 1.8 FLA

Condenser Coil Specs

418 424/430

4.59 ft2 Face Area 16 FPI 4.59 ft2 Face Area 14 FPI

Dimensions

26 7/8 W” x 38 7/8″ H x 18 1/2″ D

27

5 8

39

1 8

Liquid Valve

3/8″

Suction Valve

3/4″

* When matched with NAH4**MF Air Handler

27

1 4

19

1 8

18

7 8

39″

1

1 2

15

1 2

10

7 8

1

1 4

3

3 8

10

5 8

15

1 2

10

7 8

1

3 8

3

1 8

10

7 8

1

5 8

5

3 4

10

7 8

16″

16

NCP Series 1000 | 3000 | 4000 | 5000

Installation Guide | Split-System Condensing Units

Matched system with Cased Coil

Outdoor Model

Indoor Model

Rated Capacity (Btu/h)

Rated EER21

NCP4181000A-** NCC418AA-*

18000

10.2

NCP4241000A-** NCC424AA-*

22600

10.5

NCP4183000A-** NCC418AA-*

18000

10.2

NCP4243000A-** NCC424AA-*

22600

10.5

NCP4184000A-** NCC418AA-*

18000

10.5

NCP4244000A-** NCC424AA-*

22600

10.5

NCP4185000A-** NCC418AA-*

18500

11

NCP4245000A-** NCC424AA-*

24000

11

NCP4305000A-** NCC430AA-*

28000

10.5

1. EER2 is determined based on the Evaporator match listed in this table 2. Airflow values are determined at wet coil conditions 3. SEER2 is determined base on the Evaporator match listed in this table
4. Subcooling must be measured at evaporator inlet 5. Superheat must be measured at compressor suction line

Nominal Airflow2 (SCFM)
620 820 620 820 620 820 620 820 920

SEER23
11.7 11.7 11.7 11.7 11.7 11.7 12 12 12

Liquid Subcool4 (°F)
17-19 15-17 18-20 15-17 19-21 17-19 15-17 14-16 16-18

Suction Superheat5 (°F)
18-20 23-25 22-24 20-22 21-23 22-24 17-19 21-23 17-19

Matched system with Air Handler

Outdoor Model

Indoor Model

Indoor Motor Speed

Rated Capacity (Btu/h)

NCP4181000A-**

NAH424MF*-**

Black (2)

18000

NCP4241000A-**

NAH430MF*-**

Blue (3)

22600

NCP4183000A-**

NAH424MF*-**

Black (2)

18000

NCP4243000A-**

NAH430MF*-**

Blue (3)

23000

NCP4184000A-**

NAH424MF*-**

Black (2)

18000

NCP4244000A-**

NAH430MF*-**

Blue (3)

23000

NCP4185000A-**

NAH424MF*-**

Black (2)

18000

NCP4245000A-**

NAH430MF*-**

Blue (3)

24000

NCP4305000A-**

NAH430MF*-**

Red (5)

28400

1. EER2 is determined based on the Evaporator match listed in this table 2. Airflow values are determined at wet coil conditions 3. SEER2 is determined base on the Evaporator match listed in this table
4. Subcooling must be measured at evaporator inlet 5. Superheat must be measured at compressor suction line

Rated EER21
11 11 11 11 11 11 12 12 11.5

Nominal Airflow2 (SCFM)
600 790 600 790 600 790 600 790 950

SEER23

Liquid Subcool4 (°F)

12.5

19-21

12.5

16-18

13

18-20

13

17-19

12.5

19-21

12.5

18-20

14

13-15

14

14-16

13.5

17-19

Suction Superheat5
(°F) 18-20 15-17 16-18 19-21 19-21 18-20 22-24 19-21 19-21

NCP Series 1000 | 3000 | 4000 | 5000

17

Installation Guide | Split-System Condensing Units

1000 Series Replacement Parts Guide

3000 Series Replacement Parts Guide

Item 1 2 3 4 5 6 7 8

Description
Contactor
Start/Run Capacitor Low Pressure
Switch High Pressure
Switch
Compressor
Liquid Service Valve
Vapor Service Valve
Condenser Coil

NCP4181000A-** NCP4241000A-**

142-62-082

142-62-082

142-25-376

142-25-375

142-65-026

142-65-026

142-65-029

142-65-029

142-10-264

142-10-265

142-58-614

142-58-614

142-58-616

142-58-616

142-08-360

142-08-362

9

Motor

142-70-049

142-70-049

10

Fan Blade

142-14-040

142-14-040

11

Motor Mount

142-70-103

142-70-103

12

Base Pan

143-56-042

143-56-042

13

Unit Leveler

143-56-047

143-56-047

14

Access Panel

143-56-041

143-56-041

15

Top Panel

143-56-046

143-56-046

16 Right Side Panel

143-56-045

143-56-045

17

Left Side Panel

143-56-043

143-56-043

18

Wire Grill

142-69-001A

142-69-001A

19 Radial Fan Mount

143-56-044

143-56-044

20

Touch Up Paint

142-99-630

142-99-630

21

Air Diffuser

143-56-039

143-56-039

22

Air Diffuser Rear

143-56-040

143-56-040

Item 1 2 3 4 5 6 7 8

Description
Contactor
Start/Run Capacitor Low Pressure
Switch High Pressure
Switch
Compressor
Liquid Service Valve
Vapor Service Valve
Condenser Coil

NCP4183000A-** NCP4243000A-**

142-62-082

142-62-082

142-25-376

142-25-375

142-65-026

142-65-026

142-65-029

142-65-029

142-10-264

142-10-265

142-58-614

142-58-614

142-58-616

142-58-616

142-08-356

142-08-357

9

Motor

142-70-049

142-70-049

10

Fan Blade

142-14-040

142-14-040

11

Motor Mount

142-70-103

142-70-103

12

Base Pan

143-56-024

143-56-024

13

Unit Leveler

143-56-026

143-56-026

14

Access Panel

143-56-021

143-56-021

15

Top Panel

143-56-029

143-56-029

16 Right Side Panel

143-56-025

143-56-025

17

Left Side Panel

143-56-022

143-56-022

18

Wire Grill

142-69-003A

142-69-003A

19 Radial Fan Mount

143-56-023

143-56-023

20

Touch Up Paint

142-99-630

142-99-630

21

Air Diffuser

143-56-019

143-56-019

22

Air Diffuser Rear

143-56-018

143-56-018

18

NCP Series 1000 | 3000 | 4000 | 5000

Installation Guide | Split-System Condensing Units 4000 Series Replacement Parts Guide

Item 1

Description Contactor

NCP4184000A-** NCP4244000A-**

142-62-082

142-62-082

2

Run Capacitor

3

Low Pressure Switch

4

High Pressure Switch

5

Compressor

6

Liquid Service Valve

7

Vapor Service Valve

8

Condenser Coil

142-25-387 142-65-026 142-65-029 142-10-264 142-58-614 142-58-616 142-08-359

142-25-395 142-65-026 142-65-029 142-10-265 142-58-614 142-58-616 142-08-358

9

Motor

142-70-056

142-70-056

10

Fan Blade

142-14-047

142-14-047

11

Motor Mount

142-70-110

142-70-110

12

Base Pan

143-56-051

143-56-051

13

Unit Leveler

143-56-056

143-56-056

14

Access Panel

143-56-050

143-56-050

15

Top Panel

143-56-055

143-56-055

16 Right Side Panel

143-56-054

143-56-054

17

Left Side Panel

143-56-052

143-56-052

18

Wire Grill

142-69-004A

142-69-004A

19 Radial Fan Mount

143-56-053

143-56-053

20

Touch Up Paint

142-99-630

142-99-630

21

Air Diffuser

143-56-048

143-56-048

22

Air Diffuser Rear

143-56-049

143-56-049

NCP Series 1000 | 3000 | 4000 | 5000

19

Installation Guide | Split-System Condensing Units 5000 Series Replacement Parts Guide

Item 1

Description Contactor

NCP4185000A-** NCP4245000A-**

142-62-082

142-62-082

2

Run Capacitor

3

Low Pressure Switch

4

High Pressure Switch

5

Compressor

6

Liquid Service Valve

7

Vapor Service Valve

8

Condenser Coil

142-25-387 142-65-026 142-65-029 142-10-264 142-58-614 142-58-616 142-08-372

142-25-395 142-65-026 142-65-029 142-10-266 142-58-614 142-58-616 142-08-371

9

Motor

142-70-056

142-70-056

10

Fan Blade

142-14-040

142-14-040

11

Motor Mount

142-70-103

142-70-103

12

Base Pan

143-56-020

143-56-020

13

Unit Leveler

143-56-005

143-56-005

14

Access Panel

143-56-017

143-56-017

15

Top Panel

143-56-003

143-56-003

16 Right Side Panel

143-56-036

143-56-036

17

Left Side Panel

143-56-035

143-56-035

18

Wire Grill

142-69-005

142-69-005

19 Radial Fan Mount

143-56-037

143-56-037

20

Touch Up Paint

142-99-630

142-99-630

21

Air Diffuser

143-56-011

143-56-011

22

Air Diffuser Rear

143-56-012

143-56-012

NCP4305000A-** 142-62-082 142-25-395 142-65-026 142-65-029 142-10-268 142-58-614 142-58-616 142-08-371 142-70-056 142-14-040 142-70-103 143-56-020 143-56-005 143-56-017 143-56-003 143-56-036 143-56-035 142-69-005 143-56-037 142-99-630 143-56-011 143-56-012

20

NCP Series 1000 | 3000 | 4000 | 5000

Installation Guide | Split-System Condensing Units

539 Dunksferry Road | Bensalem, PA 19020 | 215-244-1400 | 1-800-523-7138 | Fax: 215-639-1674
THRU-THE-WALL CONDENSING UNIT & HEAT PUMP LIMITED WARRANTY
1. National Comfort Products warrants to its customers that its product shall be free from defects in material and workmanship under normal use and regular service and maintenance as follows:
COMPRESSORS: For five years from the date of original installation. ALL OTHER PARTS: For all other parts except the Compressor, for two years from the date of original installation. Customer must register the product within 60 days of purchase. If Customer cannot adequately document date of installation, then, for purposes of determining the warranty period, the date of installation shall be 60 days from the date of purchase. The 2 year parts warranty is effective for units purchased after January 1, 2016.
2. This warranty does not extend to any damages or losses due to misuse, accident, abuse, neglect, normal wear and tear, negligence (other than National Comfort’s), unauthorized modification or alteration; use beyond rated capacity; unsuitable power sources or environmental conditions; improper installation, repair, handling, maintenance or application; damage as a result of fire, wind, floods, lightning, or corrosive conditions; or any other cause not the fault of National Comfort. By way of example and without limitation, the following do not constitute a defect in workmanship and materials and are not covered by this warranty: slugging of liquid refrigerant or oil, unstable line voltage, lightning, operating without proper lubrication, and operating without factory provided safeties. Any installation that impairs or impedes air flow negatively impacts performance and causes premature equipment failure that voids this warranty. For example, installation behind a brick facade or the addition of a brick pattern facade, i.e. pigeon holes impedes air flow and shall void this warranty.
3. SOLE WARRANTY The warranties identified herein constitute National Comfort’s sole and exclusive warranties with respect to the goods and are in lieu of and exclude all other warranties, express or implied, arising by operation of law or otherwise, including without limitation, merchantability and fitness for a particular purpose whether or not the purpose or use has been disclosed to National Comfort in specifications, drawings or otherwise, and whether or not National Comfort’s goods are specifically designed and/or manufactured by National Comfort for Customer’s use or purpose.
4. LIMITATION OF REMEDY The sole and exclusive remedy for breach of any warranty hereunder (other than the warranty provided herein) shall be limited to repair, replacement, credit or refund of the purchase price to distribution as set forth herein. National Comfort is not responsible for any other item including but not limited to local transportation, freight, removal of any compressor or part, any labor associated therewith, service or diagnosis calls, refrigerant, or costs for returning any defective compressor or part.
5. LIMITATION OF WARRANTY NATIONAL COMFORT MAKES NO OTHER WARRANTIES, EXPRESS OR IMPLIED, ORAL OR WRITTEN, RELATED TO THE GOODS, INCLUDING ANY WARRANTY OF MERCHANTABILITY OF FITNESS FOR A PARTICULAR PURPOSE, WHICH ARE EXPRESSLY DISCLAIMED. NATIONAL COMFORT SHALL NOT BE LIABLE FOR SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES OR LOSSES FROM ANY CAUSE WHATSOEVER, INCLUDING, WITHOUT LIMITATION, LOSS OF USE, COMMERCIAL PROFITS, OR CUSTOMER GOODWILL, AND ANY OTHER CLAIMS BASED ON CONTRACT OR TORT, WHETHER OR NOT ARISING FROM NATIONAL COMFORT’S NEGLIGENCE. National Comfort shall not be liable for damages caused by delay in performance and the remedies of Customer set forth in this agreement are exclusive. In no event, regardless of the form of the claim or cause of action (whether based in contract, infringement, negligence, strict liability, other tort or otherwise) shall National Comfort’s liability to Customer and/or its customers exceed the price paid by Customer for the specific goods or portion of the goods provided by National Comfort giving rise to the claim or cause of action, and Customer shall indemnify and hold harmless National Comfort for any damages incurred by National Comfort in excess thereof. Customer agrees that in no event shall National Comfort’s liability to Customer and/or its customers extend to include incidental, consequential, or punitive damages. The term “consequential damages” shall include, but not be limited to, loss of anticipated profits, business interruption, loss of use, revenue, reputation and data, costs incurred, including without limitation, for capital, fuel, power and loss or damage to capital or equipment. Customer agrees that all instructions and warnings supplied by National Comfort will be passed on to those persons

Continued on next page

NCP Series 1000 | 3000 | 4000 | 5000

21

Installation Guide | Split-System Condensing Units
who use the Goods. National Comfort’s Goods are to be used in their recommended applications and all warning labels adhered to the Goods by National Comfort are to be left intact.
It is expressly understood that any technical advice furnished by National Comfort before or after delivery in regard to the use or application of the Goods is furnished without charge, and National Comfort assumes no obligation or liability for the advice given or results obtained, all advice being given and accepted at Customer’s sole risk.
6. WARRANTY PROCEDURE For All Warranty Claims. Customer must register the product with National Comfort within 60 days from purchase. Failure to timely register the product may void the warranty. Any claim for warranty shall be made within thirty days of discovery and in any event, within thirty days from removal of the compressor or part from the unit. Failure to make a timely claim shall void the warranty. Prior authorization from National Comfort is required for all warranty claims. Any claim for warranty must be first reported to National Comfort in writing specifying the unit, serial number, date of purchase and date of original installation. Customer shall also request a Return Material Authorization (“RMA”) from National Comfort to initiate the warranty claim process. Issuance of an RMA by National Comfort is not an acknowledgment that the defect is covered by this Warranty. Any replacement compressor or part is warranted for the original product warranty, or for one year from the date of shipment of the replacement compressor/part, whichever is later.
A. Compressors. In addition to the above-referenced requirements, Customer is also required to purchase a replacement compressor and return the original compressor to National Comfort at National’s discretion. If the defect is reported to National Comfort within one year from the date of original installation or within 20 months from the date of manufacture of the compressor (as determined by the compressor serial number), whichever occurs first, then Customer may take the compressor to any Authorized Copeland Distributor for replacement of said compressor. If the defect is reported to National Comfort after one year from the date of installation or after 20 months from the date of manufacture of the compressor (as determined by the compressor serial number), whichever occurs first, but before the expiration of five years from the date of installation, then the compressor should be returned to National Comfort at National’s discretion and Customer shall purchase a new compressor. If National Comfort determines that there is a defect in material or workmanship that is covered by this Warranty, then National shall credit Customer for the cost of the new replacement compressor. If National Comfort determines that the defect in material or workmanship is not covered by this Warranty, then no credit shall be issued. A copy of the invoice of the replacement compressor and completed RMA must accompany the compressor. National Comfort, at its sole discretion, may also require Customer to supply the compressor tag. The failure to follow this procedure shall render the warranty void.
B. Other Parts. In addition to the above-referenced requirements, Customer is required to purchase a replacement part for the original part for which Customer is making a warranty claim. The original part for which warranty is claimed is to be returned to National Comfort at National’s discretion, freight prepaid. If National Comfort determines that there is a defect in material or workmanship in the part that is covered by this Warranty, then National Comfort shall credit Customer for the cost of the new replacement part. If National Comfort determines that the defect in material or workmanship is not covered by this Warranty, then no credit shall be issued. A copy of the invoice of the replacement part and completed RMA must accompany the original part for which warranty is claimed. National Comfort reserves the right to request additional documentation. The failure to follow this procedure shall render the warranty void.
7. SHIPPING INSTRUCTIONS A. Compressors. Returned compressors must be totally secured by use of shipping lugs taken from the replacements compressors and clearly marked with the RMA number. Do not use tape, rags or putty to seal the compressor. Line connections should be sealed with rubber plugs. All scroll compressors must be securely bolted, banded, and stretch wrapped to a skid in the upright position. B. Parts. All other returned parts must be securely packaged and clearly marked with its corresponding RMA number provided from NCP.

22

NCP Series 1000 | 3000 | 4000 | 5000

Installation Guide | Split-System Condensing Units
NOTES _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________

NCP Series 1000 | 3000 | 4000 | 5000

23

National Comfort Products 539 Dunksferry Road | Bensalem, PA 19020-5908
(800) 523-7138 Fax (215) 639-1674
IM NCP 14299224 2/2023

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals