HEPA & ULPA
FILTER HANDLING INSTRUCTIONS
INSTRUCTIONS FOR:
• Absolute® VG, XS, & XH
• Filtra 2000
• Megalam
STORAGE INSTRUCTIONS
- Store filter in vertical position in original box.
- Keep in temperatures between 5 ºC – 40 ºC.
- Store in a clean, dry and frost-protected place
- Do not keep filter in direct sunlight.
- Maximum recommended shelf life, before installation, is seven years provided the filter is kept under optimal storage conditions.
HANDLING INSTRUCTIONS
Caution: Handle filter with care. Do not touch the filter media.
The slightest touch may lead to leakage. Do not drop filter to prevent severe damage. Avoid liquid spills/splashes on filter.
- Transport and carry vertically.
- Unpacking filters: lift filter by the frame, be careful not to damage the gasket or media. When available, follow instructions on the box!
- Avoid twisting filter frame.
- Large panel filters require two people when handling.
INSTALLATION INSTRUCTIONS
- Keep filter in box as long as possible before installation to avoid damage.
- For vertical installations, make sure filter is fitted with standing pleats.
- Make sure the gasket is not damaged during installation.
FILTER CHANGE
- Camfil recommends protective equipment such as overalls, gloves and face masks when changing filters.
- Always check local regulations before changing filters
- Filters are not reusable. Used filters should be disposed of according to local regulations.
| DO NOT use a blade to open box | |
| DO NOT apply load on filter media | |
| DO NOT touch filter media or push on the grids | |
| ONLY HANDLE large filters by two persons, carry filters vertically | |
| ONLY LIFT panel filters at the corners of the frame |
www.camfil.us
© Camfil USA, EPA,HEPA,ULPA /ENG/2023

















